6ES7416-2FK04-0AB0

6ES7416-2FK04-0AB0

Sales, Repair, Purchase

SIEMENS

SIMATIC S7-400, CPU 416F-2 Central processing unit with: work memory 2.8 MB, (1.4 MB code, 1.4 MB data), 1st interface MPI/DP 12 Mbit/s, 2nd interface PROFIBUS DP Can be used with software package Distributed Safety as of V5.2 More

Code: 6ES7416-2FK04-0AB0

from 614 EUR excl. VAT (742,94 EUR Incl. VAT)
Total in stock: 15 pcs External stock 15 pcs
Variant does not exist

Rezervace termínu

Get a quote
SIEMENS

SIMATIC S7-400, CPU 416F-2 Central processing unit with: work memory 2.8 MB, (1.4 MB code, 1.4 MB data), 1st interface MPI/DP 12 Mbit/s, 2nd interface PROFIBUS DP Can be used with software package Distributed Safety as of V5.2 More

Code: 6ES7416-2FK04-0AB0

Part Sales 2

Condition Code Warranty Availability Delivery
Express?
Price excl. VAT
New without box (NW) 6ES7416-2FK04-0AB0 NW 12/24 months In external stock 1 pcs
Within 2-4 days / Express
On request
Refurbished (R) 6ES7416-2FK04-0AB0 R 12/24 months In external stock 14 pcs
Within 2-4 days / Express
On request

Repair of the part

Name Code Delivery Warranty Price excl. VAT
Complete part repair 6ES7416-2FK04-0AB0 O 3-6 weeks 24 months On request Enquire a repair

6ES7416-2FK04-0AB0 – CPU 416F-2

SIMATIC S7-400, CPU 416F-2 central processing unit.

Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.

Request a quote for purchase or repair
1,400 KByteMemory / RAM / integrated (for program)
1,400 KByteMemory / RAM / integrated (for data)
RS-485 / PROFIBUS1st interface / Physics

CPU application

The CPU executes the user program and handles SIMATIC S7-400 communication. Before replacement, check the complete order number, actual firmware version, memory card and interface configuration in the original project.

Technical specifications

ManufacturerSiemens
Order number6ES7416-2FK04-0AB0
Product typeCPU 416F-2
Firmware version covered by these specificationsV 4.0
Product status / associated programming packageSTEP 7 V 5.2 SP1 or higher HF3 with HW-update
Voltages and currents / Feeding of external buffer voltage to CPU5 to 15 V DC
Current consumption / from backplane bus DC 5 V, max.1.6 A
Current consumption / Power loss, typ.4.5 W
Backup battery / Buffer current, typ.550 µA
Backup battery / Buffer current, max.1,539 µA
Memory / RAM / integrated (for program)1,400 KByte
Memory / RAM / integrated (for data)1,400 KByte
Memory / RAM / expandableNo
Memory / Load memory / expandable FEPROMYes; with Memory card (FLASH)
Memory / Load memory / expandable FEPROM, max.64 MByte
Memory / Load memory / integrated RAM, max.256 KByte
Memory / Load memory / expandable RAMYes; with Memory Card (RAM)
Memory / Backup / presentYes
Memory / Backup / with batteryYes; all data
Memory / Backup / without batteryNo
CPU/blocks / DB / Size, max.64 KByte
CPU/blocks / FB / Number, max.2,048
CPU/blocks / FB / Size, max.64 KByte
CPU/blocks / FC / Number, max.2,048
CPU/blocks / FC / Size, max.64 KByte
CPU/blocks / OB / Size, max.64 KByte
CPU/blocks / Nesting depth / per priority class24
CPU/blocks / Nesting depth / additional within an error OB2
CPU/processing times / for bit operations, min.0.04 µs
CPU/processing times / for word operations, min.0.04 µs
CPU/processing times / for fixed point arithmetic, min.0.04 µs
CPU/processing times / for floating point arithmetic, min.0.12 µs
Times/counters and their remanence / S7 counter / Number2,048
Times/counters and their remanence / S7 counter / Remanence / adjustableYes
Times/counters and their remanence / S7 counter / Remanence / lower limit0
Times/counters and their remanence / S7 counter / Remanence / upper limit2,047
Times/counters and their remanence / S7 counter / Remanence / presetFrom Z 0 to Z 7
Times/counters and their remanence / S7 counter / Counting range / lower limit0
Times/counters and their remanence / S7 counter / Counting range / upper limit999
IEC counter / presentYes
IEC counter / TypeSFB
S7 times / Number2,048
S7 times / Remanence / adjustableYes
S7 times / Remanence / lower limit0
S7 times / Remanence / upper limit2,047
S7 times / Remanence / presetno timers retentive
S7 times / Time range / lower limit10 ms
S7 times / Time range / upper limit9,990 s
IEC timer / presentYes
IEC timer / TypeSFB
Data areas and their remanence / remanent data area, totaltotal working and load memory (with backup battery)
Data areas and their remanence / Flag / Number, max.16 KByte
Data areas and their remanence / Flag / Remanence availableYes; MB 0 to MB 16383
Data areas and their remanence / Flag / Number of clock memories8; (1 memory byte)
Address area / I/O address area / Inputs16 KByte
Address area / I/O address area / Outputs16 KByte
Address area / I/O address area / of which, distributed / MPI/DPinterface, inputs2 KByte
Address area / I/O address area / of which, distributed / MPI/DP interface, outputs2 KByte
Address area / I/O address area / of which, distributed / DP interface, inputs8 KByte; (For each line that is operated in isochronous mode, i.e. to which an OB 61 to 62 has been assigned, the distributed IO address areas are halved)
Address area / I/O address area / of which, distributed / DP interface, outputs8 KByte; (For each line that is operated in isochronous mode, i.e. to which an OB 61 to 62 has been assigned, the distributed IO address areas are halved)
Address area / Process image / Inputs, adjustable16 KByte
Address area / Process image / Outputs, adjustable16 KByte
Address area / Process image / Inputs, preset512 Byte
Address area / Process image / Outputs, preset512 Byte
Address area / Process image / consistent data, max.244 Byte
Address area / Process image / Access to consistent data in process imageYes
Subprocess images / Number of subprocess images, max.15
Digital channels / Inputs131,072
Digital channels / Outputs131,072
Digital channels / Inputs, of which central131,072
Digital channels / Outputs, of which central131,072
Analog channels / Inputs8,192
Analog channels / Outputs8,192
Analog channels / Inputs, of which central8,192
Analog channels / Outputs, of which central8,192
Hardware config. / connectable OPs63 without message processing, 12 with message processing
Hardware config. / Central devices, max.1
Hardware config. / Expansion devices, max.21; (of which 6 ER with K-bus)
Hardware config. / MulticomputingYes; max. 4 CPUs (with UR1 or UR2)
Hardware config. / IM / Number of connectable IMs (total), max.6
Hardware config. / IM / Number of connectable IM 460s, max.6
Hardware config. / IM / Number of connectable IM 463s, max.4; IM 463-2
Hardware config. / Number of DP masters / integrated2
Hardware config. / Number of DP masters / via IM 4674
Hardware config. / Number of DP masters / via CP10; CP 443-5 Ext.
Hardware config. / Number of DP masters / Mixed mode IM + CP permittedNo; IM 467 cannot be used jointly with CP 443-5 Ext.
Hardware config. / Number of DP masters / Number of pluggable S5 modules (via adapter capsule in central device), max.6
Hardware config. / Number of operable FMs and CPs (recommended) / PROFIBUS and Ethernet CPs14; incl. CP 443-5 Ext. and IM 467
Time / Clock / Hardware clock (real-time clock)Yes
Time / Clock / Battery backed and synchro- nizedYes
Time / Clock / Resolution1 ms
Time / Operating hours counter / Number8
Clock synchronization / supportsYes
Clock synchronization / to MPI, MasterYes
Clock synchronization / to MPI, SlaveYes
Clock synchronization / to DP, MasterYes
Clock synchronization / to DP, SlaveYes
Clock synchronization / in AS, MasterYes
Clock synchronization / in AS, SlaveYes
S7 message functions / Number of login stations for message functions, max.12
S7 message functions / Symbol-related messagesYes
S7 message functions / Number of messages / overall, max.1,024
S7 message functions / Block related messagesYes
S7 message functions / Alarm 8-blocksYes
S7 message functions / Instrumentation & control messagesYes
Test commissioning functions / Status/control / Status/control variableYes
Monitoring functions / ForcingYes
Monitoring functions / Status blockYes
Monitoring functions / Single stepYes
Monitoring functions / Number of breakpoints4
Monitoring functions / Diagnostic buffer / presentYes
Monitoring functions / Diagnostic buffer / Number of entries, max.3,200
Monitoring functions / Diagnostic buffer / adjustableYes
Monitoring functions / Diagnostic buffer / preset120
Communication functions / PG/OP communicationYes
Communication functions / Global data communication / supportedYes
Communication functions / Global data communication / Size of GD packets, max.64 Byte
Communication functions / Clock synchronization / supportsYes; in MPI mode: via SFC X_SEND, X_RCV, X_GET and X_PUT; in DP master mode: via SFC I_GET and I_PUT
Communication functions / Clock synchronization / Useful data per job, max.76 Byte
Communication functions / S7 communication / supportedYes
Communication functions / S7 communication / as serverYes
Communication functions / S7 communication / as clientYes
Communication functions / S7 communication / Useful data per job, max.64 KByte
S5-compatible communication / supportedYes; via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5
S5-compatible communication / Useful data per job, max.8 KByte
Standard communication (FMS) / supportedYes; via CP and loadable FB
Number of connections / overall64
1st interface / PhysicsRS-485 / PROFIBUS
1st interface / isolatedYes
1st interface / Functionality / MPIYes
1st interface / Functionality / DP masterYes
1st interface / Functionality / DP slaveYes
1st interface / MPI / Number of connections44
1st interface / MPI / Services / PG/OP communicationYes
1st interface / MPI / Services / RoutingYes
1st interface / MPI / Services / Global data communicationYes
1st interface / MPI / Services / S7 basic communicationYes
1st interface / MPI / Services / S7 communicationYes
1st interface / MPI / Transmission speeds, max.12 Mbit/s
1st interface / DP master / Number of connections, max.32; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1
1st interface / DP master / Services / PG/OP communicationYes
1st interface / DP master / Services / RoutingYes
1st interface / DP master / Services / S7 basic communicationYes
1st interface / DP master / Services / S7 communicationYes
1st interface / DP master / Services / equidistance supportYes
1st interface / DP master / Services / Activation/deactivation of DP slavesYes
1st interface / DP master / Services / direct data exchange (cross traffic)Yes
1st interface / DP master / Transmission speeds, max.12 Mbit/s
1st interface / DP master / Number of DP slaves, max.32
1st interface / DP master / Address area / Inputs, max.2 KByte
1st interface / DP master / Address area / Outputs, max.2 KByte
1st interface / DP master / Useful data per DP slave / Inputs, max.244 Byte
1st interface / DP master / Useful data per DP slave / Outputs, max.244 Byte
DP slave / Services / RoutingYes
DP slave / Services / Status/controlYes
DP slave / Services / ProgrammingYes
DP slave / Transmission speeds, max.12 Mbit/s
DP slave / Transfer memory / Inputs244 Byte
DP slave / Transfer memory / Outputs244 Byte
DP slave / Address area, max.32
DP slave / Useful data per address area, max.32 Byte
DP slave / Useful data per address area, of which consistent, max.32 Byte
2nd interface / PhysicsRS 485 / PROFIBUS
2nd interface / isolatedYes
2nd interface / Functionality / DP masterYes
2nd interface / Functionality / DP slaveYes
2nd interface / DP master / Number of connections, max.32; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1
2nd interface / DP master / Services / PG/OP communicationYes
2nd interface / DP master / Services / RoutingYes
2nd interface / DP master / Services / S7 basic communicationYes
2nd interface / DP master / Services / S7 communicationYes
2nd interface / DP master / Services / equidistance supportYes
2nd interface / DP master / Services / Activation/deactivation of DP slavesYes
2nd interface / DP master / Services / direct data exchange (cross traffic)Yes
2nd interface / DP master / Transmission speeds, max.12 Mbit/s
2nd interface / DP master / Number of DP slaves, max.125
2nd interface / DP master / Address area / Inputs, max.8 KByte
2nd interface / DP master / Address area / Outputs, max.8 KByte
2nd interface / DP master / Useful data per DP slave / Inputs, max.244 Byte
2nd interface / DP master / Useful data per DP slave / Outputs, max.244 Byte
Isochronous mode / Useful data per isochronoous slave, max.244 Byte
Isochronous mode / equidistanceYes
Isochronous mode / shortest clock pulse1 ms; 0.5 ms without use of SFC 126, 127
CiR configuration in RUN / CiR synchronization time, basic load100 ms
CiR configuration in RUN / CiR synchronization time, time per I/O slave40 µs
CPU/programming / Programming language / STEP 7Yes
CPU/programming / Programming language / LADYes
CPU/programming / Programming language / FUPYes
CPU/programming / Programming language / AWLYes
CPU/programming / Programming language / SCLYes
CPU/programming / Programming language / CFCYes
CPU/programming / Programming language / GRAPHYes
CPU/programming / Programming language / HiGraphYes
CPU/programming / Nesting levels8
CPU/programming / User program protection/password protectionYes
Dimensions and weight / Width25 mm
Dimensions and weight / Height290 mm
Dimensions and weight / Depth219 mm
Dimensions and weight / Required slots1
Weights / Weight, approx.720 g

Communication and configuration

  • Firmware version covered by these specifications: V 4.0
  • Product status / associated programming package: STEP 7 V 5.2 SP1 or higher HF3 with HW-update
  • Memory / Load memory / expandable FEPROM: Yes; with Memory card (FLASH)
  • Memory / Load memory / expandable FEPROM, max.: 64 MByte
  • Memory / Load memory / integrated RAM, max.: 256 KByte
  • Memory / Load memory / expandable RAM: Yes; with Memory Card (RAM)
  • Address area / I/O address area / of which, distributed / MPI/DPinterface, inputs: 2 KByte
  • Address area / I/O address area / of which, distributed / MPI/DP interface, outputs: 2 KByte

Scope of supply

We will confirm the specific scope of supply, packaging and any accessories in the quotation. For replacement CPUs, we will also check the memory card and other items needed for commissioning.

Frequently asked questions

Is the same product family enough to identify a replacement?

The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.

What must be checked for firmware and a STEP 7 or TIA Portal project?

Check the replacement unit's actual firmware and the availability of this exact CPU in the hardware catalog of your engineering version. TIA Portal support cannot be confirmed from the product family name alone. A change of CPU type normally requires modification or at least a thorough check of the project.

Does the memory card need to be checked?

Yes. Check the memory card type and capacity, program and data contents and the original CPU's backup arrangement. We will specify the required card and accessories in the quotation.

Can you assess a faulty part?

Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.

Why buy from FOXON

1

Replacement part availability

We will check current part availability and confirm the possible delivery date before you order.

2

New original and refurbished parts

We will specify the available version and condition of the particular unit in the quotation.

3

Parts with a warranty

We will confirm the warranty period according to the part condition and specific quotation.

4

Diagnostics and repairs

For a faulty unit, we will check the options for diagnostics and professional repair.

More than 3,500customers
We deliver tomore than 100 countries
Express delivery?We will check. Contact us now.

Part conditions available for sale

Part conditions and warranty
  • New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
  • New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
  • New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
  • New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
  • Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
  • Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
  • Used (U): Functional used part. 3-month warranty.

Sales, repairs and buyback of automation parts

We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.

More about parts sales, repairs and buyback

Need to buy or repair this part?

Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.

Request a quote for purchase or repair