- UPS and power supplies
- UPS 12/24 VDC
- 144 W 24 VDC / 6 A UPS backup power supply Bicker, LiFePO4 battery
144 W 24 VDC / 6 A UPS backup power supply Bicker, LiFePO4 battery
Smart Industrial DC UPS Backup Power Supply 24 VDC / 6 A, 144 W, Integrated LiFePO4 Battery, configuration via UPScom software, DIN Rail Design More
Code: UPSI-2406DP3
Smart Industrial DC UPS Backup Power Supply 24 VDC / 6 A, 144 W, Integrated LiFePO4 Battery, configuration via UPScom software, DIN Rail Design More
Code: UPSI-2406DP3
Bicker UPSI-2406DP3 · UPS with LiFePO₄ battery
Protect your 24V devices and data against power outages
Bicker UPSI-2406DP3 helps keep your 24V devices running during a power outage, giving them time to save data or shut down safely. This 144 W class UPS supplies a rated current of 6 A. The integrated LiFePO₄ battery has a capacity of 33 Wh and provides approximately 11 minutes of backup at a load of 6 A. The compact unit mounts on a DIN rail and communicates with a computer via USB or RS232. FOXON will help you choose the right solution and arrange worldwide shipping.

How long do you need to keep your devices running during an outage?
Tell us which devices you want to back up and for how long. If you know their power consumption in watts, include it; we will help you choose a suitable backup unit and power supply.
Reliable backup for industrial automation
An uninterruptible power supply, or UPS, helps protect industrial computers, programmable logic controllers (PLC), network devices and measuring instruments powered by 24 V against power outages. It switches to the battery in less than 600 µs, or 0.6 milliseconds. During backup operation, it maintains an output of 23.5 VDC. When selecting the UPS, check the connected devices' supply voltage range and whether the switching time is suitable for them.

During backup operation, it supplies 6 A at a regulated 23.5 VDC, corresponding to 141 W. The full 6 A is available from 0 to +40 °C; the load must be reduced at lower and higher temperatures.
USB type B connects the unit to a computer. RS232 with a D-Sub connector is available for serial communication. A potential-free relay contact can also signal a power failure.
The LiFePO₄ battery with a capacity of 33 Wh supports up to 6 000 charge and discharge cycles. Its long service life helps reduce battery replacement frequency and associated service costs.
For new control cabinets and upgrades to existing equipment
Use the UPSI-2406DP3 when building a new control cabinet or adding backup power to existing equipment. It is designed for a 24V supply circuit. It helps protect connected devices against brief outages and voltage fluctuations.
An industrial computer, machine controller or communication device with a suitable supply voltage range can therefore ride through a brief outage without an unnecessary restart. If the outage lasts longer, backup power can provide time to save data or complete the necessary tasks. DIN rail mounting makes installation in a control cabinet easier.

LiFePO₄: energy for longer operation during outages
The integrated lithium iron phosphate battery, abbreviated LiFePO₄, has a capacity of 2.5 Ah / 33 Wh. It offers stable chemistry and up to 6 000 charge and discharge cycles. An electronic battery management system (BMS) manages charging and cell protection. It helps keep the battery within its specified operating limits.
Long cell life can reduce total operating costs compared with solutions using lead-acid batteries that need replacing more frequently. Actual service life depends on temperature, load and usage. When the UPS is switched off, Smart Battery Lock reduces the battery electronics' own power consumption, helping conserve energy during downtime. It does not completely eliminate the cells' natural self-discharge.

How long will your devices keep running during an outage?
At an output current of 6 A, UPSI-2406DP3 provides approximately 11 minutes of backup. The duration increases at lower loads. The graph shows time in minutes against output power in watts at +25 °C. Actual duration depends on battery charge and condition, temperature and UPS settings. Add up the power consumption of all devices requiring backup and allow a margin for completing work and shutting down.

View the charge level and settings in your browser
The free UPScom software lets you see the battery's current state of charge and set how the UPS responds to an outage. The software is installed on a computer and operated through a web browser. Versions are available for Windows and Linux.
When connected via USB, supported operating systems recognise the device as a UPS without an additional driver. The technical designation is HID Power Class. UPS Gen2 Configuration Software lets you change settings and update the firmware, the unit's internal control software, in Windows. Use UPScom for continuous monitoring, email notifications and running your own program before the computer shuts down.
- monitoring current draw in mA and detecting when it drops below a set threshold,
- shutdown delay, maximum backup time and minimum charge before startup,
- email notifications in case of loss of connection, power outage or system shutdown,
- safe shutdown and, if needed, running a custom script — a prepared sequence of commands — before the computer switches off.
Safe shutdown and automatic computer restart
During a power outage, the UPS notifies the connected computer. With the correct settings, the computer can save data, complete predefined tasks and shut down safely. Approximately 11 minutes of backup is available at a load of 6 A. Once power returns, automatic restart, known as Reboot, can be used. Also check the operating system settings and the industrial computer's (IPC) automatic power-on settings.
Connections are available via USB type B and the RS232 serial interface. If you want to send data to a machine controller or another system, check its communication support and the required software. A serial connector alone does not guarantee compatibility.

Connections for computers, machines and power failure signalling
Practical features that help in real operation
UPSI-2406DP3 monitors the current drawn by connected devices and the battery's state of charge. It lets you adapt backup duration, shutdown conditions and restart conditions to the actual needs of your machine or computer.
Charging takes approximately 60 minutes at maximum charging current. When a higher load is supplied at the same time, charging is reduced and takes longer. Below 0 °C, the battery charges more slowly. Recharge as soon as possible after a full discharge.
Shutdown can be configured according to the remaining charge, maximum permitted backup time, a schedule or a drop in load. The UPS also supports a shutdown command via an external signal. The connected computer or machine controller must complete the necessary tasks before power is disconnected.
Dynamic Powerboost allows a short-term current draw of 6–8 A and is available from firmware 2.2.1. The duration of increased output depends on the energy drawn over the last 58 seconds. This does not allow a continuous draw of 8 A or guarantee 58 seconds at maximum current. Size continuous loads using the rated 6 A and take ambient temperature into account.
Immunity and protection functions
UPSI-2406DP3 operates at −20 to +50 °C. The full 6 A is available from 0 to +40 °C; in cold conditions the permissible current decreases to approximately 1.5 A at −20 °C, and at +50 °C it is limited to 5 A. Charging also takes longer in cold conditions. The IP20 aluminium housing measures 63 × 120 × 100 mm without front connectors and the DIN rail bracket. Provide protection against water, dirt and contact inside the cabinet. This is not a safety controller.
Allow space around the unit for cooling. For effective cooling, use vertical mounting on a horizontal DIN rail, with 20 mm clearance on the left and right and 50 mm above and below the unit. Do not cover the ventilation openings. Very low or high temperatures may reduce backup time.
The UPS withstands short sequences of fast electrical transients at 2 kV according to EN 61000-4-4 and surge voltages of ±0.5 kV between L–N and ±1 kV between L–PE/N–PE according to EN 61000-4-5. Performance criterion A applies in both cases: operation within specified limits. Connect functional earth FE to meet the radiated and conducted emissions requirements of EN 55016-2-3.
The output is protected against overcurrent and short circuits. Input reverse-polarity protection applies when connecting a device that is still switched off; it does not protect against reversed input polarity during backup operation. After an overcurrent or short circuit, the UPS attempts to restore its output in normal mode, but makes no automatic attempt in battery mode. Always check the wiring before commissioning. A direct short circuit at the terminals can damage the device.
The UPS detects when current consumption falls below a set threshold and can disconnect its output after work is complete. Battery protection monitors excessively low voltage. Schedule the connected system's shutdown in good time; do not rely on fully discharging the battery as the normal way to end operation.
Technical parameters
| Manufacturer's order code | UPSI-2406DP3 |
|---|---|
| Input voltage | 24 VDC; operating range 22.5–30 VDC |
| Undervoltage threshold | 22.5 VDC; the input withstand limit of 35 VDC is not an operating voltage |
| Output voltage | Normal mode: input minus a voltage drop of max. 0.5 V depending on load; backup mode: regulated 23.5 VDC |
| Rated current and power | 6 A; 144 W power class at 24 V, actual power in normal mode is affected by the voltage drop; backup power 141 W (23.5 V × 6 A) |
| Short-term current and power boost | Dynamic Powerboost: 6–8 A; normal mode 144–192 W before accounting for the voltage drop, without simultaneous charging; backup mode 141–188 W. From firmware 2.2.1, depending on energy drawn, max. 58 s |
| Brief current pulse | 30 A for 5 ms |
| Protective overcurrent shutdown | 6–8 A: up to 58 s depending on Dynamic Powerboost conditions; 8–10.8 A: max. 100 ms; above 10.8 A: max. 5 ms |
| No-load operation / short circuit | No-load operation supported; output short-circuit protection, disconnection in less than 5 ms |
| Capacitive load at startup | Max. 3 000 µF in normal mode at a load of 0 A |
| Input current | 6.1 A at rated load without charging; max. 6.2 A at rated load with charging; short-term 6.1–8.1 A at increased load without charging |
| No-load consumption / charging | Less than 100 mA without load or charging; charging only, with no output load: 1.8 A from the input |
| Input power consumption | 146.5 W rated; max. 150 W; short-term 146.5–194.5 W; charging only without output load: 43 W |
| Internal input fuse | 15 A |
| Integrated battery | LiFePO₄, 2.5 Ah / 33 Wh; up to 6 000 charge and discharge cycles depending on operating conditions |
| Battery voltage | Nominal 13.2 V; final charging voltage 13.8 V; protection when the first cell drops to 2.5 V |
| Charging current and method | 4.5–5 A into the battery, max. 2 C; CC / CV / CP – current, voltage and power control |
| Charging time | Approximately 60 min at maximum charging current; depends on load, input voltage and temperature |
| Backup time at 6 A | Approximately 11 min at +25 °C |
| Switchover to battery | Less than 600 µs (0.6 ms) |
| Power-on / battery start | Starts in less than 5 s after input power is connected; manual battery start is not supported |
| USB | USB 2.0, type B socket, HID / VCOM; cable max. 3 m; no galvanic isolation |
| RS232 | D-Sub, 9-pin female; TX/RX, 38 400 Bd, 1:1 cable, max. 10 m; no galvanic isolation |
| Relay contact | Potential-free; 24 VDC / 1 A or 125 VAC / 0.5 A; NO/NC configurable in software; switching time max. 1,500 ms |
| Input and output connection | Pluggable screw connector; conductor cross-section 0.129–1.31 mm²; stripping length 6–7 mm; tightening torque 0.3–0.4 Nm |
| Mounting and degree of protection | DIN rail EN 60715; aluminium housing; IP20; protection class III |
| Dimensions (W × H × D) | 63 × 120 × 100 mm excluding front connectors and DIN rail bracket |
| Weight | 0.8 kg, UPS only |
| Operating temperature and load | −20 to +50 °C; full 6 A from 0 to +40 °C; approximately 1.5 A at −20 °C, 5 A at +50 °C; slower charging in cold conditions |
| Storage and transport | −30 to +55 °C; recommended battery charge 80 % |
| Humidity and altitude | Max. 95 % at +25 °C, non-condensing; up to 4,000 m |
| Operating environment | Climate class 3k3 according to EN 60721; pollution degree 2; overvoltage category I; outdoor use only in a suitable protective enclosure |
| Cooling and clearances | Vertical mounting on a horizontal DIN rail; recommended clearances 20 mm left/right and 50 mm top/bottom |
| Safety standards | IEC 61010-1 and IEC 61010-2-201; safety extra-low voltage SELV |
| Electromagnetic immunity | EN 61000-4-2: 4 kV contact / 8 kV air, criterion B; EN 61000-4-4: 2 kV, criterion A; EN 61000-4-5: ±0.5 kV L–N / ±1 kV L–PE, N–PE, criterion A |
| Electromagnetic emissions | EN 55016-2-3; requires functional earth FE to be connected |
| Power supply upstream of the UPS | Min. 24 V / 6.25 A (150 W); with Powerboost min. 24 V / 8.25 A (approximately 200 W); SELV or PELV, no constant-current mode |
| Connecting multiple UPS units | Series and parallel connection are not permitted |
| Warranty | 3 years under the warranty terms |
Unless otherwise stated, specifications apply at +25 °C, an input voltage of 24 VDC and rated current.
What the 144 W rating means in practice
UPSI-2406DP3 belongs to the 144 W power class for 24V devices drawing 6 A. During backup operation it regulates the output to 23.5 VDC, delivering 141 W at 6 A. In normal mode the output follows the input with a voltage drop of up to 0.5 V depending on load. Account for these values when checking the supply voltage range and power consumption of connected devices.
Short-term extra power helps with temporary increases in demand. Size continuous loads according to the rated 6 A and operating temperature. This UPS does not support manual battery start; it starts when input power is connected.
Scope of delivery
- 1× UPSI-2406DP3 UPS with integrated LiFePO₄ battery
- 1× VIN/VOUT input and output mating connector
- 1× mating relay connector
Select the power supply and connection cables separately to suit your devices; we will be happy to help.
About the manufacturer
Bicker Elektronik
Bicker Elektronik is a German manufacturer that has been developing, manufacturing and supplying industrial power supplies, UPS backup systems and system components since 1994.
Bicker products are used in automated machines, robots, measuring instruments, production data collection equipment, medical equipment and communication systems, among other applications. For the UPSI-2406DP3, the manufacturer focuses on long-term operation in control cabinets, connections to other equipment and backup power for important devices.
Frequently Asked Questions
How long can the UPSI-2406DP3 keep a device running during an outage?
At 6 A, backup time is approximately 11 minutes at +25 °C. It increases at lower loads. It also depends on charge level, battery age, temperature and settings. Send us the total power consumption of your devices and the required runtime during an outage – we will help you choose.
How do I connect the UPS to a computer or control system?
You can connect to a computer via USB type B; a supported operating system recognises the unit as a UPS (HID-UPS). Another option is RS232 with a D-Sub connector. For a custom control system, check the communication protocol and software. A relay contact can also signal an outage.
Can the unit be started manually without input power?
This model does not support manual battery start without input power. It starts when a suitable 24V power supply is connected. Automatic backup during an outage and restart after power returns are separate functions.
What happens when current draw is low or the energy storage is discharged?
When current falls below a set threshold, the UPS can disconnect power to devices that have already shut down and conserve the remaining energy. The battery is protected against excessively low voltage. Recharge it as soon as possible after full discharge; check its charge regularly during extended downtime.
Should you choose a UPS with a battery or a supercapacitor?
A LiFePO₄ battery is suitable for longer operation during an outage. A supercapacitor is a different way of storing electrical energy: it is mainly suited to short, very frequent outages. The main factor when choosing is how long your devices need to work without the main power supply.
Can this UPS safely shut down any computer?
Always check the power consumption and the time needed to save data and close all applications. UPSI-2406DP3 provides approximately 11 minutes of backup at 6 A. Schedule shutdown with a time margin, check communication and test the entire sequence, including automatic restart, in your application.
What can the relay contact switch?
The potential-free contact is used for operational signalling. The contact is rated for 24 VDC / 1 A or 125 VAC / 0.5 A. Signalling by closing or opening the contact (NO/NC) can be configured in software. Observe the applicable electrical limits and insulation requirements when wiring it.
Do you ship UPS units outside the Czech Republic?
Yes, we ship products worldwide. Tell us the quantity, country and delivery location. We will check availability and provide a specific shipping quotation and delivery estimate.
Why buy from FOXON
Want to protect your devices from power outages?
Tell us what you want to back up, for how long and where we should deliver the unit. If you know your devices' power consumption and the required connection to a computer or machine, include those details. We will help you choose and prepare a quotation including shipping. We ship worldwide.
Request a solutionSchedule an online meeting
Need help with backup time, wiring or connecting the unit to your devices? Choose a time for a short online consultation directly in the calendar below.
Technical parameters
Basic features
- Device type: intelligent DC UPS module for 24 V systems
- Model: UPSI-2406DP3
- Input voltage: 24 VDC (range 22.5–30 VDC)
- Output voltage: normal mode VIN − 0.5 VDC max. (depending on load) / backup mode 23.5 VDC
- Output current: 6 A nominal
- Power: 144 W
- Battery technology: LiFePO4
- Mounting: on DIN rail
Backup and battery
- Battery capacity: 2.5 Ah / 33 Wh
- Backup time: approx. 11 min at 6 A output current
- Charging time: approx. 60 min
- Battery lifetime: up to 6000 cycles
- Battery management system (BMS): integrated
- Charging method: CC / CV / CP
Output and power
- Dynamic output current: 6–8 A short-term
- Power in backup mode: 141 W nominal
- Switching time: <600 µs
- Capacitive load: max. 3000 µF (in normal mode during start-up, load 0 A)
Input parameters and power supply
- Max. input current: 6.2 A
- Internal input fuse: yes, 15 A
Communication and signalling
- Communication interfaces: USB, RS232, HID UPS
- Signalling: potential-free relay contact on power failure
- Configuration: via UPScom software
Functions and protections
- Functions: intelligent input current detection, regulated output voltage in backup mode, minimum load detection, timer on power failure, controlled system shutdown, automatic restart of the connected device, battery charge status indicator
- Protections: protection against input polarity reversal, overcurrent and output short circuit
Operating conditions
- Operating temperature: −20 to +50 °C
- Storage and transport temperature: −30 to +55 °C
- Max. humidity: ≤95% at +25 °C, non-condensing
- Max. altitude: 4000 m
Mechanical design
- Dimensions (W x H x D): 63 x 120 x 100 mm (without front connectors and DIN rail holder)
- Weight: 0.8 kg
- Warranty: 3 years

New: Bicker DC UPS — Keeping Your Production Technology and Data Safe
Power outages mean downtime, scrap, and data loss. That’s why we’re bringing a new line to the Czech market and to our online shop—products from the German manufacturer Bicker Elektronik. Their DC UPS units maintain 24 V (or 12 V), safely save data, and—where possible—restart devices. Bicker products come with a 3-year warranty. The devices also offer smart functions for system optimization and safety.

Bicker Review: Jarda Blažek compared 2 smart UPS units with a supercapacitor and a battery
Smart industrial backup power supplies from Bicker protect your production systems and industrial PCs against unexpected power outages, voltage drops, and fluctuations. Jarda Blažek (blaja.cz) investigated the practical differences between UPS units with an integrated supercapacitor and those with a LiFePO4 battery.
Highlighted items are mandatory.





