6ES7431-1KF00-0AB0, repair and sale of PLC / CNC SIEMENS

6ES7431-1KF00-0AB0, repair and sale of PLC / CNC SIEMENS

Sales, Repair, Purchase

SIEMENS

SIMATIC S7-400, SM 431 ANALOG INPUT MODULE OPTIC. ISOLATED, 8 AI, 13 BIT RESOLUTION, U/I/RESIST. More

Code: 6ES7431-1KF00-0AB0

from 303 EUR excl. VAT (366,63 EUR Incl. VAT)
Total in stock: 121 pcs External stock 121 pcs
Variant does not exist

Rezervace termínu

Get a quote
SIEMENS

SIMATIC S7-400, SM 431 ANALOG INPUT MODULE OPTIC. ISOLATED, 8 AI, 13 BIT RESOLUTION, U/I/RESIST. More

Code: 6ES7431-1KF00-0AB0

Part Sales 4

Condition Code Warranty Availability Delivery
Express?
Price excl. VAT
New in sealed box (NC) 6ES7431-1KF00-0AB0 NC 12/24 months In external stock 8 pcs
Within 2-4 days / Express
On request
New without box (NW) 6ES7431-1KF00-0AB0 NW 12/24 months In external stock 1 pcs
Within 2-4 days / Express
On request
Refurbished (R) 6ES7431-1KF00-0AB0 R 12/24 months In external stock 112 pcs
Within 2-4 days / Express
On request
Used (U) 6ES7431-1KF00-0AB0 U 3 months In stock
On request

Repair of the part

Name Code Delivery Warranty Price excl. VAT
Complete part repair 6ES7431-1KF00-0AB0 O 3-6 weeks 24 months On request Enquire a repair

6ES7431-1KF00-0AB0 – SM 431

SIMATIC S7-400, analog input SM 431, isolated 8 AI, resolution 13 bit, voltage/current/resistance

Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.

Request a quote for purchase or repair
not necessarySupply voltage / Load voltage L+ / Rated value (DC)
8Analog inputs / Number of analog inputs
50 VAnalog inputs / permissible input voltage for voltage input (destruction limit),

Application and selection

Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.

Technical specifications

ManufacturerSiemens
Order number6ES7431-1KF00-0AB0
Supply voltage / Load voltage L+ / Rated value (DC)not necessary
Input current / from backplane bus 5 V DC, max.350 mA
Power loss / Power loss, typ.1.8 W
Analog inputs / Number of analog inputs8
Analog inputs / For voltage/current measurement8
Analog inputs / For resistance measurement4
Analog inputs / permissible input voltage for voltage input (destruction limit),50 V
Analog inputs / permissible input current for current input (destruction limit),50 mA; 40 mA continuous
Analog inputs / Constant measurement current for resistance-type transmitter,1.67 mA
Analog inputs / Input ranges / VoltageYes
Analog inputs / Input ranges / CurrentYes
Analog inputs / Input ranges / ThermocoupleNo
Analog inputs / Input ranges / Resistance thermometerNo
Analog inputs / Input ranges / ResistanceYes
Analog inputs / Input ranges (rated values), voltages / 1 V to 5 VYes
Analog inputs / Input ranges (rated values), voltages / Input resistance (1 V to 5 V)200 kΩ
Analog inputs / Input ranges (rated values), voltages / -1 V to +1 VYes
Analog inputs / Input ranges (rated values), voltages / Input resistance (-1 V to +1 V)200 kΩ
Analog inputs / Input ranges (rated values), voltages / -10 V to +10 VYes
Analog inputs / Input ranges (rated values), voltages / Input resistance (-10 V to +10 V)200 kΩ
Analog inputs / Input ranges (rated values), currents / -20 mA to +20 mAYes
Analog inputs / Input ranges (rated values), currents / Input resistance (-20 mA to +20 mA)80 Ω
Analog inputs / Input ranges (rated values), currents / 4 mA to 20 mAYes
Analog inputs / Input ranges (rated values), currents / Input resistance (4 mA to 20 mA)80 Ω
Analog inputs / Input ranges (rated values), resistors / 0 to 600 ohmsYes
Analog inputs / Input ranges (rated values), resistors / Input resistance (0 to 600 ohms)usable up to 500 ohms
Analog inputs / Cable length / shielded, max.200 m
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.13 bit
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Integration time, parameterizableYes
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Basic conversion time (ms)23 / 25 ms
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Integration time (ms)16,7 / 20 ms
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Interference voltage suppression for interference50 / 60 Hz
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Basic execution time of the module (all channels200 ms; 184 / 200 ms
Encoder / Connection of signal encoders / for voltage measurementYes; possible
Encoder / Connection of signal encoders / for current measurement as 2-wire transducerYes; with external transmitter supply
Encoder / Connection of signal encoders / for current measurement as 4-wire transducerYes
Encoder / Connection of signal encoders / for resistance measurement with two-wire connectionYes; Line resistances are also measured
Encoder / Connection of signal encoders / for resistance measurement with three-wire connectionYes; Line resistances are also measured
Encoder / Connection of signal encoders / for resistance measurement with four-wire connectionYes
Errors/accuracies / Temperature error (relative to input range), (+/-)0.02 %/K; ±0.02 %/K in impedance measuring range; ±0.007 % in all other measuring ranges
Errors/accuracies / Operational error limit in overall temperature range / Voltage, relative to input range, (+/-)1 %; ±1.0 % at ±1 V; ±0.6 % at ±10 V; ±0.7 % at 1 to 5 V
Errors/accuracies / Operational error limit in overall temperature range / Current, relative to input range, (+/-)1 %; at ±20 mA, 4 to 20 mA
Errors/accuracies / Operational error limit in overall temperature range / Resistance, relative to input range, (+/-)1.25 %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms)
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Voltage, relative to input range, (+/-)0.7 %; 0.7% at ±1 V; 0.4% at ±10 V; 0.5% at 1 to 5 V
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-)0.7 %; at ±20 mA, 4 to 20 mA
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Resistance, relative to input range, (+/-)0.8 %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms)
Interrupts/diagnostics/status information / Diagnostics functionNo
Potential separation / Potential separation analog inputs / Potential separation analog inputsYes; internal/external
Potential separation / Potential separation analog inputs / between the channelsNo
Potential separation / Potential separation analog inputs / between the channels and backplane busYes
Isolation / Isolation tested with2 120 V DC between bus and analog part; 500 V DC between bus and local ground; 2 120 V DC between analog part and local ground
Dimensions / Width25 mm
Dimensions / Height290 mm
Dimensions / Depth210 mm
Weights / Weight, approx.500 g

Supported signals and ranges

  • Supply voltage / Load voltage L+ / Rated value (DC): not necessary
  • Analog inputs / For voltage/current measurement: 8
  • Analog inputs / For resistance measurement: 4
  • Analog inputs / permissible input voltage for voltage input (destruction limit),: 50 V
  • Analog inputs / Constant measurement current for resistance-type transmitter,: 1.67 mA
  • Analog inputs / Input ranges / Voltage: Yes
  • Analog inputs / Input ranges / Current: Yes
  • Analog inputs / Input ranges / Thermocouple: No

Scope of supply

We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.

Frequently asked questions

Is the same product family enough to identify a replacement?

The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.

What information is needed to check connections and accessories?

Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.

Can you assess a faulty part?

Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.

Why buy from FOXON

1

Replacement part availability

We will check current part availability and confirm the possible delivery date before you order.

2

New original and refurbished parts

We will specify the available version and condition of the particular unit in the quotation.

3

Parts with a warranty

We will confirm the warranty period according to the part condition and specific quotation.

4

Diagnostics and repairs

For a faulty unit, we will check the options for diagnostics and professional repair.

More than 3,500customers
We deliver tomore than 100 countries
Express delivery?We will check. Contact us now.

Part conditions available for sale

Part conditions and warranty
  • New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
  • New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
  • New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
  • New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
  • Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
  • Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
  • Used (U): Functional used part. 3-month warranty.

Sales, repairs and buyback of automation parts

We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.

More about parts sales, repairs and buyback

Need to buy or repair this part?

Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.

Request a quote for purchase or repair