6ES7334-0CE01-0AA0

6ES7334-0CE01-0AA0

Sales, Repair, Purchase

SIEMENS

SIMATIC S7-300, Analog module SM 334, Non-isolated 4 AI/2 AO, 1x 20-pole, Removing and inserting possible with active backplane bus More

Code: 6ES7334-0CE01-0AA0

from 316 EUR excl. VAT (382,36 EUR Incl. VAT)
Total in stock: 22 pcs External stock 22 pcs
Variant does not exist

Rezervace termínu

Get a quote
SIEMENS

SIMATIC S7-300, Analog module SM 334, Non-isolated 4 AI/2 AO, 1x 20-pole, Removing and inserting possible with active backplane bus More

Code: 6ES7334-0CE01-0AA0

Part Sales 3

Condition Code Warranty Availability Delivery
Express?
Price excl. VAT
New in sealed box (NC) 6ES7334-0CE01-0AA0 NC 12/24 months In external stock 8 pcs
Within 2-4 days / Express
On request
Refurbished (R) 6ES7334-0CE01-0AA0 R 12/24 months In external stock 13 pcs
Within 2-4 days / Express
On request
Used (U) 6ES7334-0CE01-0AA0 U 3 months In external stock 1 pcs
Within 2-4 days / Express
On request

Repair of the part

Name Code Delivery Warranty Price excl. VAT
Complete part repair 6ES7334-0CE01-0AA0 O 3-6 weeks 24 months On request Enquire a repair

6ES7334-0CE01-0AA0 – SM 334

SIMATIC S7-300, analog module SM 334, non-isolated 4 AI/2 AO, 1x 20-pole, removing and inserting with active backplane bus possible

Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.

Request a quote for purchase or repair
24 VSupply voltage / Load voltage L+ / Rated value (DC)
4Analog inputs / Number of analog inputs
20 VAnalog inputs / permissible input voltage for voltage input (destruction limit),

Application and selection

Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.

Technical specifications

ManufacturerSiemens
Order number6ES7334-0CE01-0AA0
Supply voltage / Load voltage L+ / Rated value (DC)24 V
Input current / from supply and load voltage L+ (without load), max.110 mA
Input current / from backplane bus 5 V DC, max.55 mA
Power loss / Power loss, typ.3 W
Analog inputs / Number of analog inputs4
Analog inputs / For voltage measurement4
Analog inputs / permissible input voltage for voltage input (destruction limit),20 V
Analog inputs / permissible input current for current input (destruction limit),40 mA
Analog inputs / Cycle time (all channels) max.5 ms
Analog inputs / Input ranges / VoltageYes
Analog inputs / Input ranges / CurrentYes
Analog inputs / Input ranges / ThermocoupleNo
Analog inputs / Input ranges / Resistance thermometerNo
Analog inputs / Input ranges / ResistanceNo
Analog inputs / Input ranges (rated values), voltages / 0 to +10 VYes
Analog inputs / Input ranges (rated values), voltages / Input resistance (0 to 10 V)100 kΩ
Analog inputs / Input ranges (rated values), currents / 0 to 20 mAYes
Analog inputs / Input ranges (rated values), currents / Input resistance (0 to 20 mA)50 Ω
Analog inputs / Cable length / shielded, max.200 m
Analog outputs / Number of analog outputs2
Analog outputs / Voltage output, short-circuit protectionYes
Analog outputs / Voltage output, short-circuit current, max.11 mA
Analog outputs / Current output, no-load voltage, max.15 V
Analog outputs / Output ranges, voltage / 0 to 10 VYes
Analog outputs / Output ranges, current / 0 to 20 mAYes
Analog outputs / Load impedance (in rated range of output) / with voltage outputs, min.5 kΩ
Analog outputs / Load impedance (in rated range of output) / with voltage outputs, capacitive load, max.1 µF
Analog outputs / Load impedance (in rated range of output) / with current outputs, max.300 Ω
Analog outputs / Load impedance (in rated range of output) / with current outputs, inductive load, max.1 mH
Analog outputs / Cable length / shielded, max.200 m
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.8 bit
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Integration time, parameterizableNo
Analog value generation for the outputs / Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.8 bit
Analog value generation for the outputs / Integration and conversion time/resolution per channel / Conversion time (per channel)500 µs
Analog value generation for the outputs / Settling time / for resistive load0.3 ms
Analog value generation for the outputs / Settling time / for capacitive load3 ms
Analog value generation for the outputs / Settling time / for inductive load0.3 ms
Encoder / Connection of signal encoders / for voltage measurementYes
Encoder / Connection of signal encoders / for current measurement as 2-wire transducerNo
Encoder / Connection of signal encoders / for current measurement as 4-wire transducerYes
Errors/accuracies / Operational error limit in overall temperature range / Voltage, relative to input range, (+/-)0.9 %
Errors/accuracies / Operational error limit in overall temperature range / Current, relative to input range, (+/-)0.8 %
Errors/accuracies / Operational error limit in overall temperature range / Voltage, relative to output range, (+/-)0.6 %
Errors/accuracies / Operational error limit in overall temperature range / Current, relative to output range, (+/-)1 %
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Voltage, relative to input range, (+/-)0.7 %
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-)0.6 %
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Voltage, relative to output range, (+/-)0.5 %
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Current, relative to output range, (+/-)0.5 %
Interrupts/diagnostics/status information / AlarmsNo
Interrupts/diagnostics/status information / Diagnostics functionNo
Potential separation / Potential separation analog inputs / between the channels and backplane busNo
Potential separation / Potential separation analog outputs / between the channelsNo
Potential separation / Potential separation analog outputs / between the channels and backplane busNo
Potential separation / Potential separation analog outputs / between the channels and the power supply of theYes
Isolation / Isolation tested with500 V DC
Connection method / required front connector20-pin
Dimensions / Width40 mm
Dimensions / Height125 mm
Dimensions / Depth117 mm
Weights / Weight, approx.285 g
Product type designationSM 334
Number of poles20

Connections and conditions of use

  • Encoder / Connection of signal encoders / for voltage measurement: Yes
  • Encoder / Connection of signal encoders / for current measurement as 2-wire transducer: No
  • Encoder / Connection of signal encoders / for current measurement as 4-wire transducer: Yes
  • Connection method / required front connector: 20-pin

Scope of supply

We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.

Frequently asked questions

Is the same product family enough to identify a replacement?

The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.

What information is needed to check connections and accessories?

Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.

Can you assess a faulty part?

Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.

Why buy from FOXON

1

Replacement part availability

We will check current part availability and confirm the possible delivery date before you order.

2

New original and refurbished parts

We will specify the available version and condition of the particular unit in the quotation.

3

Parts with a warranty

We will confirm the warranty period according to the part condition and specific quotation.

4

Diagnostics and repairs

For a faulty unit, we will check the options for diagnostics and professional repair.

More than 3,500customers
We deliver tomore than 100 countries
Express delivery?We will check. Contact us now.

Part conditions available for sale

Part conditions and warranty
  • New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
  • New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
  • New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
  • New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
  • Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
  • Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
  • Used (U): Functional used part. 3-month warranty.

Sales, repairs and buyback of automation parts

We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.

More about parts sales, repairs and buyback

Need to buy or repair this part?

Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.

Request a quote for purchase or repair