6ES7305-1BA80-0AA0

6ES7305-1BA80-0AA0

Sales, Repair, Purchase

SIEMENS

SIMATIC S7-300 with Regulated power supply PS305 input: 24-110 V DC output: 24 V DC/2 A More

Code: 6ES7305-1BA80-0AA0

from 304 EUR excl. VAT (367,84 EUR Incl. VAT)
Total in stock: 10 pcs External stock 10 pcs
Variant does not exist

Rezervace termínu

Get a quote
SIEMENS

SIMATIC S7-300 with Regulated power supply PS305 input: 24-110 V DC output: 24 V DC/2 A More

Code: 6ES7305-1BA80-0AA0

Part Sales 2

Condition Code Warranty Availability Delivery
Express?
Price excl. VAT
New in sealed box (NC) 6ES7305-1BA80-0AA0 NC 12/24 months In external stock 4 pcs
Within 2-4 days / Express
On request
Refurbished (R) 6ES7305-1BA80-0AA0 R 12/24 months In external stock 6 pcs
Within 2-4 days / Express
On request

Repair of the part

Name Code Delivery Warranty Price excl. VAT
Complete part repair 6ES7305-1BA80-0AA0 O 3-6 weeks 24 months On request Enquire a repair

6ES7305-1BA80-0AA0 – PS305

SIMATIC PS305/24-110VDC/24V/2A/Outdoor SIMATIC S7-300 with Regulated power supply PS305 input: 24-110 V DC output: 24 V DC/2 A

Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.

Request a quote for purchase or repair
24 ... 110 Vinput / supply voltage at DC
16.8 ... 138 Vinput / input voltage at DC
2.4 Ainput / input current / at rated input voltage 24 V

Application and selection

Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.

Technical specifications

ManufacturerSiemens
Order number6ES7305-1BA80-0AA0
General information / product type designationPS305
General information / product designationPower supply S7-300
General information / type of current supply24 V/2 A
input / type of the power supply networkDC voltage
input / voltage curve at inputDC
input / supply voltage at DC24 ... 110 V
input / input voltage at DC16.8 ... 138 V
input / wide range inputYes
input / overvoltage overload capability154 V; 0.1 s
input / buffering time for rated value of the output current in the event of10 ms
input / operating condition of the mains bufferingat Vin rated
input / input current / at rated input voltage 24 V2.4 A
input / input current / at rated input voltage 110 V0.6 A
input / current limitation of inrush current at 25 °C maximum20 A
input / duration of inrush current limiting at 25 °C / maximum10 ms
input / I2t value maximum5 A²·s
input / fuse protection typeT 6.3 A/250 V (not accessible)
input / fuse protection type in the feederRecommended miniature circuit breaker: from 10 A characteristic C, suitable for DC
output / voltage curve at outputControlled, isolated DC voltage
output / product function output voltage controlledYes
output / product function output voltage stabilizedYes
output / output voltage at DC rated value24 V
output / output voltage / at output 1 at DC rated value24 V
output / output voltage / at output 1 at DC24 V
output / output voltage adjustableNo; -
output / relative overall tolerance of the voltage3 %
output / relative control precision of the output voltage / on slow fluctuation of input voltage0.2 %
output / relative control precision of the output voltage / on slow fluctuation of ohm loading0.4 %
output / residual ripple / maximum150 mV
output / residual ripple / typical30 mV
output / voltage peak / maximum240 mV
output / voltage peak / typical150 mV
output / display version for normal operationGreen LED for 24 V OK
output / behavior of the output voltage when switching onNo overshoot of Vout (soft start)
output / response delay maximum3 s
output / voltage increase time of the output voltage / typical5 ms
output / output current / rated value2 A
output / output current / rated range0 ... 3 A; 3 A to +60 °C with Ue > 24 V
output / supplied active power typical48 W
output / short-term overload current / on short-circuiting during the start-up typical9 A
output / short-term overload current / at short-circuit during operation typical9 A
output / duration of overloading capability for excess current / on short-circuiting during the start-up270 ms
output / duration of overloading capability for excess current / at short-circuit during operation270 ms
output / bridging of equipmentYes
output / number of parallel-switched equipment resources for increasing2
efficiency / efficiency in percent75 %
efficiency / power loss [W] / at rated output voltage for rated value of the output16 W
closed-loop control / relative control precision of the output voltage with rapid0.3 %
closed-loop control / relative control precision of the output voltage load step of2.5 %
closed-loop control / setting time / load step 50 to 100% typical2.5 ms
closed-loop control / setting time / load step 100 to 50% typical2.5 ms
closed-loop control / setting time / maximum5 ms
protection and monitoring / design of the overvoltage protectionAdditional control loop, shutdown at approx. 30 V, automatic restart
protection and monitoring / property of the output short-circuit proofYes
protection and monitoring / design of short-circuit protectionElectronic shutdown, automatic restart
protection and monitoring / response value current limitation3.3 ... 3.9 A
protection and monitoring / enduring short circuit current RMS value / maximum2 A
safety / galvanic isolation between input and outputYes
safety / galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
safety / operating resource protection classClass I
safety / protection class IPIP20
EMC / standard / for emitted interferenceEN 55011 Class A
EMC / standard / for mains harmonics limitationnot applicable
EMC / standard / for interference immunityEN 61000-6-2
ambient conditions / ambient temperature / during operation-25 ... +70 °C; with natural convection
ambient conditions / ambient temperature / during transport-40 ... +85 °C
ambient conditions / ambient temperature / during storage-40 ... +85 °C
ambient conditions / environmental category according to IEC 60721Climate class 3K5, transient condensation permitted
connection method / type of electrical connectionscrew terminal
connection method / at inputL+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
connection method / at outputL+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
connection method / for auxiliary contacts-
mechanical data / width × height × depth of the enclosure80 × 125 × 120 mm
mechanical data / installation width × mounting height80 mm × 225 mm
mechanical data / required spacing / top50 mm
mechanical data / required spacing / bottom50 mm
mechanical data / required spacing / left0 mm
mechanical data / required spacing / right0 mm
mechanical data / fastening methodCan be mounted onto S7 rail
mechanical data / required spacing / DIN-rail mountingNo
mechanical data / required spacing / S7 rail mountingYes
mechanical data / required spacing / wall mountingNo
mechanical data / housing can be lined upYes
mechanical data / net weight0.57 kg
accessories / mechanical accessoriesMounting adapter for standard mounting rail (6ES7390-6BA00-0AA0)
Output voltage24 V DC

Connections and conditions of use

  • connection method / type of electrical connection: screw terminal
  • connection method / at input: L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
  • connection method / at output: L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
  • connection method / for auxiliary contacts: -

Scope of supply

We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.

Frequently asked questions

Is the same product family enough to identify a replacement?

The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.

What information is needed to check connections and accessories?

Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.

Can you assess a faulty part?

Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.

Why buy from FOXON

1

Replacement part availability

We will check current part availability and confirm the possible delivery date before you order.

2

New original and refurbished parts

We will specify the available version and condition of the particular unit in the quotation.

3

Parts with a warranty

We will confirm the warranty period according to the part condition and specific quotation.

4

Diagnostics and repairs

For a faulty unit, we will check the options for diagnostics and professional repair.

More than 3,500customers
We deliver tomore than 100 countries
Express delivery?We will check. Contact us now.

Part conditions available for sale

Part conditions and warranty
  • New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
  • New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
  • New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
  • New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
  • Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
  • Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
  • Used (U): Functional used part. 3-month warranty.

Sales, repairs and buyback of automation parts

We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.

More about parts sales, repairs and buyback

Need to buy or repair this part?

Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.

Request a quote for purchase or repair