from 330,33 EUR Incl. VAT
6ES7305-1BA80-0AA0
- SIEMENS
- SIMATIC S7-300
- Power Supply
- 6ES7305-1BA80-0AA0
6ES7305-1BA80-0AA0
SIMATIC S7-300 with Regulated power supply PS305 input: 24-110 V DC output: 24 V DC/2 A More
Code: 6ES7305-1BA80-0AA0
SIMATIC S7-300 with Regulated power supply PS305 input: 24-110 V DC output: 24 V DC/2 A More
Code: 6ES7305-1BA80-0AA0
Part Sales 2
| Condition | Code | Warranty | Availability |
Delivery Express? | Price excl. VAT | |
|---|---|---|---|---|---|---|
| New in sealed box (NC) | 6ES7305-1BA80-0AA0 NC | 12/24 months | In external stock 4 pcs |
Within 2-4 days / Express
|
On request
|
|
| Refurbished (R) | 6ES7305-1BA80-0AA0 R | 12/24 months | In external stock 6 pcs |
Within 2-4 days / Express
|
On request
|
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6ES7305-1BA80-0AA0 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6ES7305-1BA80-0AA0 – PS305
SIMATIC PS305/24-110VDC/24V/2A/Outdoor SIMATIC S7-300 with Regulated power supply PS305 input: 24-110 V DC output: 24 V DC/2 A
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Application and selection
Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6ES7305-1BA80-0AA0 |
| General information / product type designation | PS305 |
| General information / product designation | Power supply S7-300 |
| General information / type of current supply | 24 V/2 A |
| input / type of the power supply network | DC voltage |
| input / voltage curve at input | DC |
| input / supply voltage at DC | 24 ... 110 V |
| input / input voltage at DC | 16.8 ... 138 V |
| input / wide range input | Yes |
| input / overvoltage overload capability | 154 V; 0.1 s |
| input / buffering time for rated value of the output current in the event of | 10 ms |
| input / operating condition of the mains buffering | at Vin rated |
| input / input current / at rated input voltage 24 V | 2.4 A |
| input / input current / at rated input voltage 110 V | 0.6 A |
| input / current limitation of inrush current at 25 °C maximum | 20 A |
| input / duration of inrush current limiting at 25 °C / maximum | 10 ms |
| input / I2t value maximum | 5 A²·s |
| input / fuse protection type | T 6.3 A/250 V (not accessible) |
| input / fuse protection type in the feeder | Recommended miniature circuit breaker: from 10 A characteristic C, suitable for DC |
| output / voltage curve at output | Controlled, isolated DC voltage |
| output / product function output voltage controlled | Yes |
| output / product function output voltage stabilized | Yes |
| output / output voltage at DC rated value | 24 V |
| output / output voltage / at output 1 at DC rated value | 24 V |
| output / output voltage / at output 1 at DC | 24 V |
| output / output voltage adjustable | No; - |
| output / relative overall tolerance of the voltage | 3 % |
| output / relative control precision of the output voltage / on slow fluctuation of input voltage | 0.2 % |
| output / relative control precision of the output voltage / on slow fluctuation of ohm loading | 0.4 % |
| output / residual ripple / maximum | 150 mV |
| output / residual ripple / typical | 30 mV |
| output / voltage peak / maximum | 240 mV |
| output / voltage peak / typical | 150 mV |
| output / display version for normal operation | Green LED for 24 V OK |
| output / behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
| output / response delay maximum | 3 s |
| output / voltage increase time of the output voltage / typical | 5 ms |
| output / output current / rated value | 2 A |
| output / output current / rated range | 0 ... 3 A; 3 A to +60 °C with Ue > 24 V |
| output / supplied active power typical | 48 W |
| output / short-term overload current / on short-circuiting during the start-up typical | 9 A |
| output / short-term overload current / at short-circuit during operation typical | 9 A |
| output / duration of overloading capability for excess current / on short-circuiting during the start-up | 270 ms |
| output / duration of overloading capability for excess current / at short-circuit during operation | 270 ms |
| output / bridging of equipment | Yes |
| output / number of parallel-switched equipment resources for increasing | 2 |
| efficiency / efficiency in percent | 75 % |
| efficiency / power loss [W] / at rated output voltage for rated value of the output | 16 W |
| closed-loop control / relative control precision of the output voltage with rapid | 0.3 % |
| closed-loop control / relative control precision of the output voltage load step of | 2.5 % |
| closed-loop control / setting time / load step 50 to 100% typical | 2.5 ms |
| closed-loop control / setting time / load step 100 to 50% typical | 2.5 ms |
| closed-loop control / setting time / maximum | 5 ms |
| protection and monitoring / design of the overvoltage protection | Additional control loop, shutdown at approx. 30 V, automatic restart |
| protection and monitoring / property of the output short-circuit proof | Yes |
| protection and monitoring / design of short-circuit protection | Electronic shutdown, automatic restart |
| protection and monitoring / response value current limitation | 3.3 ... 3.9 A |
| protection and monitoring / enduring short circuit current RMS value / maximum | 2 A |
| safety / galvanic isolation between input and output | Yes |
| safety / galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| safety / operating resource protection class | Class I |
| safety / protection class IP | IP20 |
| EMC / standard / for emitted interference | EN 55011 Class A |
| EMC / standard / for mains harmonics limitation | not applicable |
| EMC / standard / for interference immunity | EN 61000-6-2 |
| ambient conditions / ambient temperature / during operation | -25 ... +70 °C; with natural convection |
| ambient conditions / ambient temperature / during transport | -40 ... +85 °C |
| ambient conditions / ambient temperature / during storage | -40 ... +85 °C |
| ambient conditions / environmental category according to IEC 60721 | Climate class 3K5, transient condensation permitted |
| connection method / type of electrical connection | screw terminal |
| connection method / at input | L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded |
| connection method / at output | L+, M: 3 screw terminals each for 0.5 ... 2.5 mm² |
| connection method / for auxiliary contacts | - |
| mechanical data / width × height × depth of the enclosure | 80 × 125 × 120 mm |
| mechanical data / installation width × mounting height | 80 mm × 225 mm |
| mechanical data / required spacing / top | 50 mm |
| mechanical data / required spacing / bottom | 50 mm |
| mechanical data / required spacing / left | 0 mm |
| mechanical data / required spacing / right | 0 mm |
| mechanical data / fastening method | Can be mounted onto S7 rail |
| mechanical data / required spacing / DIN-rail mounting | No |
| mechanical data / required spacing / S7 rail mounting | Yes |
| mechanical data / required spacing / wall mounting | No |
| mechanical data / housing can be lined up | Yes |
| mechanical data / net weight | 0.57 kg |
| accessories / mechanical accessories | Mounting adapter for standard mounting rail (6ES7390-6BA00-0AA0) |
| Output voltage | 24 V DC |
Connections and conditions of use
- connection method / type of electrical connection: screw terminal
- connection method / at input: L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
- connection method / at output: L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
- connection method / for auxiliary contacts: -
Scope of supply
We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.
Frequently asked questions
Is the same product family enough to identify a replacement?
The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.
What information is needed to check connections and accessories?
Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.
Can you assess a faulty part?
Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.
Why buy from FOXON
Replacement part availability
We will check current part availability and confirm the possible delivery date before you order.
New original and refurbished parts
We will specify the available version and condition of the particular unit in the quotation.
Parts with a warranty
We will confirm the warranty period according to the part condition and specific quotation.
Diagnostics and repairs
For a faulty unit, we will check the options for diagnostics and professional repair.
Part conditions available for sale
Part conditions and warranty
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Sales, repairs and buyback of automation parts
We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.
Need to buy or repair this part?
Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.