6AG2134-6HD01-1BA1
- SIEMENS
- SIMATIC ET 200 / DP
- SIMATIC ET 200SP
- 6AG2134-6HD01-1BA1
6AG2134-6HD01-1BA1
SIPLUS ET 200SP AI 4xU/I 2-wire T1 rail based on 6ES7134-6HD01-0BA1 with conformal coating, -40…+60 °C, OT1 with ST1/2 (+70 °C für 10 minutes), analog input module, suitable for BU type A0, A1, color code CC03, module diagnostics, 16 bit, +/-0.3% More
Code: 6AG2134-6HD01-1BA1
SIPLUS ET 200SP AI 4xU/I 2-wire T1 rail based on 6ES7134-6HD01-0BA1 with conformal coating, -40…+60 °C, OT1 with ST1/2 (+70 °C für 10 minutes), analog input module, suitable for BU type A0, A1, color code CC03, module diagnostics, 16 bit, +/-0.3% More
Code: 6AG2134-6HD01-1BA1
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6AG2134-6HD01-1BA1 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6AG2134-6HD01-1BA1 – AI 4x U/I 2-wire
Siemens 6AG2134-6HD01-1BA1: SIPLUS ET 200SP AI 4xU/I 2-wire T1 rail based on 6ES7134-6HD01-0BA1 with conformal coating, -40…+60 °C, OT1 with ST1/2 (+70 °C für 10 minutes), analog input module, suitable for BU type A0, A1, color code CC03, module diagnostics, 16 bit, +/-0.3%.
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6AG2134-6HD01-1BA1 |
| Product type | AI 4x U/I 2-wire |
| Firmware version / FW update possible | Yes |
| Supply voltage / Rated value (DC) | 24 V |
| Input current / Current consumption, max. | 37 mA; without sensor supply |
| Encoder supply / 24 V encoder supply / Output current, max. | 20 mA; max. 50 mA per channel for a duration < 10 s |
| Power loss / Power loss, typ. | 0.85 W; Without encoder supply voltage |
| Analog inputs / Number of analog inputs | 4; Differential inputs |
| Analog inputs / Input ranges (rated values), voltages / 0 to +10 V | Yes; 15 bit |
| Analog inputs / Input ranges (rated values), voltages / Input resistance (0 to 10 V) | 120 kΩ |
| Analog inputs / Input ranges (rated values), voltages / 1 V to 5 V | Yes; 15 bit |
| Analog inputs / Input ranges (rated values), voltages / Input resistance (1 V to 5 V) | 120 kΩ |
| Analog inputs / Input ranges (rated values), voltages / -10 V to +10 V | Yes; 16 bit incl. sign |
| Analog inputs / Input ranges (rated values), voltages / Input resistance (-10 V to +10 V) | 120 kΩ |
| Analog inputs / Input ranges (rated values), voltages / -5 V to +5 V | Yes; 16 bit incl. sign |
| Analog inputs / Input ranges (rated values), voltages / Input resistance (-5 V to +5 V) | 120 kΩ |
| Analog inputs / Input ranges (rated values), currents / 0 to 20 mA | Yes; 15 bit |
| Analog inputs / Input ranges (rated values), currents / Input resistance (0 to 20 mA) | 100 Ω; + approx. 0.7 V diode forward voltage |
| Analog inputs / Input ranges (rated values), currents / 4 mA to 20 mA | Yes; 15 bit |
| Analog inputs / Input ranges (rated values), currents / Input resistance (4 mA to 20 mA) | 100 Ω; + approx. 0.7 V diode forward voltage |
| Analog inputs / Cable length / shielded, max. | 1 000 m; 200 m for voltage measurement |
| Ambient temperature during operation / horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -30 °C |
| Ambient temperature during operation / horizontal installation, max. | 60 °C; = Tmax; +70 °C for 10 min (OT1, ST1/ST2 acc. to EN 50155) |
| Ambient temperature during operation / vertical installation, min. | -40 °C; = Tmin; startup @ -30 °C |
| Ambient temperature during operation / vertical installation, max. | 50 °C; = Tmax |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weights / Weight, approx. | 31 g |
Part variants and further information
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Buy parts and arrange repairs with FOXON
We supply new original and refurbished parts with a warranty. We confirm current availability and the possible delivery date before you place an order. For faulty parts, we check the options for diagnostics and professional repair.
Need to buy or repair this part?
Send the full order number, required quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.