3LD2704-0TK51
3LD2704-0TK51
SENTRON, Switch disconnector 3LD, main switch, 3-pole, Iu: 100 A, Operating power / at AC-23 A at 400 V: 37 kW, front-mounted, rotary operating mechanism, black, 4-hole mounting of the handle More
Code: 3LD2704-0TK51
SENTRON, Switch disconnector 3LD, main switch, 3-pole, Iu: 100 A, Operating power / at AC-23 A at 400 V: 37 kW, front-mounted, rotary operating mechanism, black, 4-hole mounting of the handle More
Code: 3LD2704-0TK51
Part Sales 1
| Condition | Code | Warranty | Availability |
Delivery Express? | Price excl. VAT | |
|---|---|---|---|---|---|---|
| New in sealed box (NC) | 3LD2704-0TK51 NC | 12/24 months | In external stock 2 pcs |
Within 2-4 days / Express
|
On request
|
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 3LD2704-0TK51 O | 3-6 weeks | 24 months | On request | Enquire a repair |
3LD2704-0TK51 – Siemens 3LD2704-0TK51
Siemens 3LD2704-0TK51.
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Application and selection
Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 3LD2704-0TK51 |
| Model / product brand name | SENTRON |
| Model / product designation | Switch disconnector |
| Model / design of the product | Main switch |
| Model / display version for switch position indicator manual | 1 ON - 0 OFF |
| Model / type of switch | front mounted |
| Model / design of the actuating element | Short rotary knob |
| Model / color of the actuating element | black |
| Model / design of handle | rotary operating mechanism, black |
| Model / type of the driving mechanism motor drive | No |
| General technical data / number of poles | 3 |
| General technical data / size of switch disconnector | 4 |
| General technical data / mechanical service life (operating cycles) typical | 100 000 |
| General technical data / electrical endurance (operating cycles) / at AC-23 A at 690 V | 6 000 |
| General technical data / operating frequency maximum | 50 1/h |
| General technical data / degree of pollution | 3 |
| Voltage / insulation voltage rated value | 690 V |
| Voltage / surge voltage resistance rated value | 6 kV |
| Voltage / operating voltage / at AC rated value | 690 V |
| Voltage / operating frequency rated value / minimum | 50 Hz |
| Voltage / operating frequency rated value / maximum | 60 Hz |
| Protection class / protection class IP | IP65 |
| Protection class / degree of protection NEMA rating | 1, 3R, 4X, 12 |
| Protection class / protection class IP on the front | IP65 |
| Dissipation / power loss [W] for rated value of the current at AC in hot | 2.77 W |
| Main circuit / operational current / at AC-21 at 690 V rated value | 100 A |
| Main circuit / operational current / at AC-21 A at 240 V rated value | 100 A |
| Main circuit / operational current / at AC-21 A at 400 V rated value | 100 A |
| Main circuit / operational current / at AC-21 A at 440 V rated value | 100 A |
| Main circuit / operational current / at AC-23 A at 400 V rated value | 70 A |
| Main circuit / operating power / at AC-23 A at 240 V rated value | 18.5 kW |
| Main circuit / operating power / at AC-23 A at 400 V rated value | 37 kW |
| Main circuit / operating power / at AC-23 A at 440 V rated value | 37 kW |
| Main circuit / operating power / at AC-23 A at 690 V rated value | 30 kW |
| Main circuit / operating power / at AC-3 at 240 V rated value | 18.5 kW |
| Main circuit / operating power / at AC-3 at 400 V rated value | 30 kW |
| Main circuit / operating power / at AC-3 at 690 V rated value | 22 kW |
| Auxiliary circuit / number of CO contacts for auxiliary contacts | 0 |
| Auxiliary circuit / number of NC contacts for auxiliary contacts | 0 |
| Auxiliary circuit / number of NO contacts for auxiliary contacts | 0 |
| Auxiliary circuit / operating voltage of auxiliary contacts at AC maximum | 500 V |
| Auxiliary circuit / continuous current of the auxiliary contact rated value | 10 A |
| Auxiliary circuit / insulation voltage of the auxiliary switch rated value | 500 V |
| Suitability / suitability for use main switch | Yes |
| Suitability / suitability for use switch disconnector | Yes |
| Suitability / suitability for use EMERGENCY OFF switch | No |
| Suitability / suitability for use maintenance/repair switch | Yes |
| Product details / product feature can be locked into OFF position | Yes |
| Accessories / product extension optional / motor drive | No |
| Accessories / product extension optional / voltage trigger | No |
| Accessories / number of connectable NC contacts for auxiliary contacts | 3 |
| Accessories / number of connectable NO contacts for auxiliary contacts | 3 |
| Accessories / number of connectable CO contacts for auxiliary contacts | 0 |
| Accessories / number of bracket locks maximum | 3 |
| Accessories / hasp thickness of the bracket locks | 4 ... 8 mm |
| Short circuit / protection / at 690 V by gG fuse rated value | 50 kA |
| Short circuit / let-through current with closed switch / at 240 V for combination switch + gG fuse maximum | 10 kA |
| Short circuit / let-through current with closed switch / at 440 V for combination switch + gG fuse maximum | 10 kA |
| Short circuit / let-through current with closed switch / at 690 V for combination switch + gG fuse maximum | 10 kA |
| Short circuit / I2t value with closed switch / at 240 V for combination switch + gG fuse maximum | 64 kA²·s |
| Short circuit / I2t value with closed switch / at 440 V for combination switch + gG fuse maximum | 64 kA²·s |
| Short circuit / I2t value with closed switch / at 690 V for combination switch + gG fuse maximum | 64 kA²·s |
| Short circuit / design of the fuse link / for short-circuit protection of the main circuit | fuse gL/gG: 100 A |
| Short circuit / design of the fuse link / for short-circuit protection of the auxiliary switch | fuse gL/gG: 10 A |
| Short circuit / operational current of upstream fuse rated value | 100 A |
| according UL / operational current at AC according to UL 508/UL 60947-4-1 | 100 A |
| according UL / operating voltage at AC at 50/60 Hz according to UL 508/UL | 600 V |
| according UL / active power [hp] at AC at 480 V according to UL 508/UL | 60 |
| according UL / active power [hp] at AC at 600 V according to UL 508/UL | 75 |
| according UL / short-time withstand current (SCCR) at 600 V according to | 10 kA |
| according UL / continuous current of upstream fuse according to UL rated | 200 A |
| according UL / type of fuse according to UL | RK5 |
| Connections / section solid maximum / | 1 |
| Connections / section solid maximum / | 12 |
| Connections / conductor / solid | 1x (4...50mm²) |
| Connections / conductor / finely stranded with core end processing | 1x (4...35mm²) |
| Connections / conductor / stranded | 1x (4...50mm²) |
| Connections / contacts / solid | lateral auxiliary switch 2x (0,75 ... 2,5mm²), 1x 4mm²; front auxiliary switch 1x (0,75 ... 2,5mm²) |
| Connections / contacts / finely stranded with core end processing | lateral auxiliary switch 2x (0,75 ... 1,5mm²), 1x 2,5mm²; front auxiliary switch 1x 2,5mm² |
| Connections / contacts / stranded | lateral auxiliary switch 2x (0,75 ... 2,5mm²), 1x 4mm²; front auxiliary switch 1x (0,75 ... 2,5mm²) |
| Connections / type of electrical connection / for main current circuit | box terminal |
| Connections / type of electrical connection / for auxiliary contacts | connection terminals |
| Mechanical Design / height | 107 mm |
| Mechanical Design / width | 90 mm |
| Mechanical Design / depth | 112.5 mm |
| Mechanical Design / type of device | fixed mounting |
| Mechanical Design / fastening method | Built-in unit fixed-mounted version |
| Mechanical Design / fastening method / 4-hole front mounting | Yes |
| Mechanical Design / fastening method / front mounting with central attachment | No |
| Mechanical Design / fastening method / rail mounting | No |
| Mechanical Design / Net Weight | 486 g |
| Environmental conditions / ambient temperature during operation / minimum | -25 °C |
| Environmental conditions / ambient temperature during operation / maximum | 55 °C |
| Environmental conditions / ambient temperature during storage / minimum | -25 °C |
| Environmental conditions / ambient temperature during storage / maximum | 55 °C |
| Product description | SENTRON |
Connections and conditions of use
- Voltage / insulation voltage rated value: 690 V
- Voltage / surge voltage resistance rated value: 6 kV
- Voltage / operating voltage / at AC rated value: 690 V
- Voltage / operating frequency rated value / minimum: 50 Hz
- Voltage / operating frequency rated value / maximum: 60 Hz
- Dissipation / power loss [W] for rated value of the current at AC in hot: 2.77 W
- Main circuit / operational current / at AC-21 at 690 V rated value: 100 A
- Main circuit / operational current / at AC-21 A at 240 V rated value: 100 A
Scope of supply
We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.
Frequently asked questions
Is the same product family enough to identify a replacement?
The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.
What information is needed to check connections and accessories?
Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.
Can you assess a faulty part?
Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.
Why buy from FOXON
Replacement part availability
We will check current part availability and confirm the possible delivery date before you order.
New original and refurbished parts
We will specify the available version and condition of the particular unit in the quotation.
Parts with a warranty
We will confirm the warranty period according to the part condition and specific quotation.
Diagnostics and repairs
For a faulty unit, we will check the options for diagnostics and professional repair.
Part conditions available for sale
Part conditions and warranty
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Sales, repairs and buyback of automation parts
We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.
Need to buy or repair this part?
Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.