MEAN WELL XDR-480E-24 - DIN rail power supply, 24 V DC, 20 A, 480 W

MEAN WELL XDR-480E-24 - DIN rail power supply, 24 V DC, 20 A, 480 W
MEAN WELL XDR-480E-24 - DIN rail power supply, 24 V DC, 20 A, 480 W

MEAN WELL XDR-480E-24 - DIN rail power supply, 24 V DC, 20 A, 480 W


MEAN WELL

Industrial switching power supply for DIN rail mounting. Output 24 V DC, 20 A, 480 W, adjustable from 24 to 29 V DC. Input 85 to 264 V AC / 120 to 370 V DC, 48 mm wide, active PFC and DC OK contact. More

Code: XDR-480E-24

Rezervace termínu

Get a quote
MEAN WELL

Industrial switching power supply for DIN rail mounting. Output 24 V DC, 20 A, 480 W, adjustable from 24 to 29 V DC. Input 85 to 264 V AC / 120 to 370 V DC, 48 mm wide, active PFC and DC OK contact. More

Code: XDR-480E-24

MEAN WELL · XDR-E

XDR-480E-24 - 480 W for industrial automation

MEAN WELL XDR-480E-24 converts mains voltage to a regulated 24 V DC output with a current of up to 20 A. Its slim 48 mm design saves space in the control cabinet. The power supply features active PFC, fanless cooling and a DC OK relay contact for monitoring the output voltage.

Looking to buy or repair this power supply?
We will check the availability of a new power supply and the options for diagnosing and professionally repairing a faulty unit. Price on request.

Request a purchase or repair quote
24 V DC / 20 ARated power 480 W
48 mm wideTS-35 DIN rail mounting
DC OK contactOutput voltage monitoring

XDR-480E-24 applications

The power supply is designed for industrial control systems, factory automation and electromechanical equipment. In a control cabinet, it provides a 24 V DC supply rail for devices with the appropriate voltage rating and a combined demand within its power limits.

When selecting a power supply, consider the continuous load, the starting currents of connected devices and the temperature inside the cabinet. The adjustable 24 to 29 V DC output helps match the voltage to the application; the 480 W power limit still applies when the voltage is increased.

MEAN WELL XDR-480E-24 technical specifications

Manufacturer / part numberMEAN WELL / XDR-480E-24
DesignAC/DC switching power supply for DIN rail mounting
Rated output voltage24 V DC
Rated output current20 A; operating range 0 to 20 A
Rated output power480 W
Output voltage adjustment24 to 29 V DC; total power must not exceed 480 W
AC input voltage85 to 264 V AC, 47 to 63 Hz; load derating is required below 100 V AC
DC input voltage120 to 370 V DC
Typical efficiency95.5 % at 230 V AC, rated load and an ambient temperature of 25 °C
No-load power consumptionTypically 1 W at 115 / 230 V AC
Active PFCTypical power factor >0.95 at 230 V AC and >0.98 at 115 V AC, at full load
Ripple and noiseMax. 120 mV peak-to-peak; measured with a 20 MHz bandwidth and the specified measurement setup
Output voltage tolerance±1.0 %, including setting tolerance, line regulation and load regulation
Hold-up timeTypically 15 ms at 115 / 230 V AC and full load
ProtectionShort circuit, overload, output overvoltage and overheating
DC OK contactClosed when the output voltage is correct; max. 30 V DC / 1 A or 30 V AC / 0.5 A, resistive load
Operating temperature-40 to +70 °C; full power from -30 to +50 °C; maximum 80 % at -40 °C and 75 % at +70 °C
Operating humidity20 to 95 % relative humidity, non-condensing
CoolingNatural air convection, without a fan
MountingTS-35/7.5 or TS-35/15 DIN rail, vertical orientation
Dimensions (W × H × D)48 × 125.2 × 125 mm
Catalogue weight890 g
Parallel operation and current sharingUp to 4 units; PLINK activation; current limit 20 A × number of units × 0.9
AC input currentTypically 6 A at 115 V AC; 3 A at 230 V AC

Power and operating conditions: Load derating is required at input voltages below 100 V AC and ambient temperatures above +50 °C. Above an altitude of 2,000 m, the permissible ambient temperature is reduced by 3.5 °C for every additional 1,000 m.

DC OK monitoring, protection and installation

The potential-free DC OK contact is closed when the output voltage is correct and opens when the power supply is switched off or the output fails. Use an external circuit for signalling and observe the contact ratings.

Overload protection operates at 105 to 130 % of rated power. The power supply limits the current; if the output drops below 30 % of rated voltage, it switches to repeated restart attempts. Normal operation resumes automatically once the fault is removed. Overtemperature protection shuts down the output and restores it after cooling.

For vertical mounting and continuous full-load operation, leave the recommended clearances of 40 mm above the power supply, 20 mm below it and 5 mm on each side. Next to equipment that generates heat, leave the recommended side clearance of 15 mm. Keep the ventilation openings unobstructed.

Parallel operation and current sharing

XDR-480E-24 supports parallel operation of up to 4 power supplies in droop mode. Enable the function by locally bridging pins 3 and 4 (PLINK) on each power supply; it is disabled by default. The difference between the set output voltages must be less than 0.1 V.

Total output current must not exceed 20 A × number of power supplies × 0.9. The minimum load must exceed 7 % of the sum of the rated currents of all connected power supplies. Use short wiring with an adequate conductor cross-section.

In parallel mode, output voltage falls by approximately 4 % as load increases; the example for this model shows a drop from 24 V at no load to approximately 23 V at rated current. At low loads, only one power supply may operate while the others enter standby; their DC OK LEDs and relays are then inactive. After an overload or short circuit in parallel operation, power must be switched off and on again to restore operation.

Scope of delivery

MEAN WELL XDR-480E-24 power supply. We will confirm the exact scope of delivery in the quotation. Select the DIN rail, supply wiring and other cabinet equipment separately to suit the installation.

Frequently asked questions

Can it replace another 24 V / 20 A power supply?

Matching voltage and current ratings are the starting point. Before replacement, also check the input supply, dimensions, terminals, required signalling and starting current of the connected equipment. Send us the original power supply designation and load details.

Can the power supply operate at 29 V and deliver 20 A?

When the output voltage is increased, the current must be reduced so that output power does not exceed 480 W. The rated 20 A applies to a 24 V DC output.

Does the power supply deliver full power at +70 °C?

No. With vertical mounting, full power is available from -30 to +50 °C. At +70 °C, the maximum permissible load is 75 %, or 360 W. Load must also be reduced at -40 °C, to a maximum of 80 %.

Can several XDR-480E-24 power supplies be connected together?

Yes, up to 4 units in droop mode. Observe PLINK activation, voltage settings, the current limit and the minimum load described in the parallel-operation section. Connecting the outputs without the required settings is not sufficient.

Does the power supply provide backup during a mains failure?

Battery backup requires a separate backup system. The typical 15 ms hold-up time at full load only bridges a very brief dip or loss of the input supply.

Can I request diagnosis and repair of a faulty power supply?

Yes. Send us a photograph of the nameplate and a description of the fault. We will check diagnosis and repair options and compare them with supplying a new power supply.

Available product conditions

You can request a new original XDR-480E-24 power supply. If you require a different product condition or a replacement for an existing power supply, include this in your enquiry. We will confirm availability, condition, price and delivery time in a specific quotation.

Sales, repairs and purchase of surplus automation parts

FOXON supplies industrial automation parts in Czechia and internationally and provides diagnosis and repair of faulty parts. For each specific power supply, we first assess the appropriate approach.

Sales, repairs and purchase of surplus parts at FOXON.cz

Request a quote for the XDR-480E-24

Send us the quantity, required delivery date and parameters of the load to be powered. For diagnosis or repair enquiries, include a photograph of the nameplate and a description of the fault.

Request a purchase or repair quote
Manufacturer / part numberMEAN WELL / XDR-480E-24
DesignAC/DC switching power supply for DIN rail mounting
Rated output voltage24 V DC
Rated output current20 A; operating range 0 to 20 A
Rated output power480 W
Output voltage adjustment24 to 29 V DC; total power must not exceed 480 W
AC input voltage85 to 264 V AC, 47 to 63 Hz; load derating is required below 100 V AC
DC input voltage120 to 370 V DC
Typical efficiency95.5 % at 230 V AC, rated load and an ambient temperature of 25 °C
No-load power consumptionTypically 1 W at 115 / 230 V AC
Active PFCTypical power factor >0.95 at 230 V AC and >0.98 at 115 V AC, at full load
Ripple and noiseMax. 120 mV peak-to-peak; measured with a 20 MHz bandwidth and the specified measurement setup
Output voltage tolerance±1.0 %, including setting tolerance, line regulation and load regulation
Hold-up timeTypically 15 ms at 115 / 230 V AC and full load
ProtectionShort circuit, overload, output overvoltage and overheating
DC OK contactClosed when the output voltage is correct; max. 30 V DC / 1 A or 30 V AC / 0.5 A, resistive load
Operating temperature-40 to +70 °C; full power from -30 to +50 °C; maximum 80 % at -40 °C and 75 % at +70 °C
Operating humidity20 to 95 % relative humidity, non-condensing
CoolingNatural air convection, without a fan
MountingTS-35/7.5 or TS-35/15 DIN rail, vertical orientation
Dimensions (W × H × D)48 × 125.2 × 125 mm
Catalogue weight890 g
Parallel operation and current sharingUp to 4 units; PLINK activation; current limit 20 A × number of units × 0.9
AC input currentTypically 6 A at 115 V AC; 3 A at 230 V AC