6SL4113-2CA23-2AF0
- SIEMENS
- SINAMICS
- SINAMICS filters
- 6SL4113-2CA23-2AF0
6SL4113-2CA23-2AF0
SINAMICS G220 Clean Power 380-500 V 3AC + 10/-20% 47-63 Hz power low overload: 30 kW 150% 3 s, 110% 57 s power high overload: 22 kW 200% 3 s, 150% 57 s 460x 200x 245 (HxWxD) frame size: FSD2 degree of protection IP20 / UL open type safety SIL3 with integrated braking chopper basic version radio interference suppression filter category C2 . PROFINET PN, Modbus TCP
More
Code: 6SL4113-2CA23-2AF0
SINAMICS G220 Clean Power 380-500 V 3AC + 10/-20% 47-63 Hz power low overload: 30 kW 150% 3 s, 110% 57 s power high overload: 22 kW 200% 3 s, 150% 57 s 460x 200x 245 (HxWxD) frame size: FSD2 degree of protection IP20 / UL open type safety SIL3 with integrated braking chopper basic version radio interference suppression filter category C2 . PROFINET PN, Modbus TCP
More
Code: 6SL4113-2CA23-2AF0
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6SL4113-2CA23-2AF0 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6SL4113-2CA23-2AF0 – SINAMICS G220 Clean Power
Siemens 6SL4113-2CA23-2AF0: SINAMICS G220 Clean Power.
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6SL4113-2CA23-2AF0 |
| Input / Number of phases | 3 AC |
| Input / Line voltage | 380...415V / 440...500V (--20+10 %) |
| Input / Line frequency | 50/60 Hz (47 ... 63 Hz) |
| Rated data / Input / Voltage range (voltage class) | 380 … 415 V 440 … 500 V (400V IEC) (480V NEC) |
| Input / Rated current | 53.0 A / 44.0 A |
| Output / Number of phases | 3 AC |
| Rated data / Output / Voltage range (voltage class) | 380 … 415 V 440 … 500 V (400V IEC) (480V NEC) |
| Output / Rated power (LO) | 30.00 kW / 40.00 hp |
| Output / Rated power (HO) | 22.00 kW 30.00 hp |
| Output / Rated current (LO) | 63.0 A / 52.0 A |
| Output / Rated current (HO) | 46.0 A 40.0 A |
| Output / Rated current (IN) | 64.7 A / 53.4 A |
| Rated data / Output / Pulse frequency (factory setting) | 4 kHz |
| Efficiency η | 0.97 |
| Communication / Operator element version | Integrated SDI standard for monitoring and diagnostics |
| Communication / Interface design | RJ45 with 100 MBit/s Ethernet |
| Communication / Display design | 1.4" graphic display |
| Communication / Screen resolution | 128 x 160 Pixel |
| Inputs / outputs / Standard digital inputs / Number | 6 (additionally 2 AI configurable as 2 DI) |
| Inputs / outputs / Standard digital inputs / Number as rapid input | 1 (DI5) |
| Inputs / outputs / Fail-safe digital inputs / Number | 1 (additionally 4 DI configurable as 2 FDI) |
| Inputs / outputs / Digital outputs / Number as relay changeover contact | 2 |
| Inputs / outputs / Digital outputs / Number as transistor | 1 |
| Inputs / outputs / Analog inputs / Number | 2 (Differential input) |
| Inputs / outputs / Analog inputs / Voltage bipolar | -10 … 10 V |
| Inputs / outputs / Analog inputs / Voltage unipolar | 0 … 10 V |
| Ambient conditions / Cooling | Air cooling using an integrated fan |
| Ambient conditions / Cooling air requirement | 0.050 m³/s |
| Ambient conditions / Installation altitude (without derating) | 1,000 m |
| Ambient conditions / Max. ambient temperature with derating | 60 °C |
| Ambient conditions / Ambient temperature with high overload (without derating) | 50 °C |
| Ambient conditions / Ambient temperature with low overload (without derating) | 45 °C |
| Connections / Signal cable / Conductor cross-section | 0.20 ... 2.50 mm² (24 ... 12 AWG) |
| Connections / Motor end / Conductor cross-section | 10.00 ... 50.00 mm² (8 ... 1/0 AWG) |
| Connections / DC link / Conductor cross-section | 10.00 ... 50.00 mm² (8 ... 1/0 AWG) |
| Degree of protection | IP20 / UL open type |
| Frame size | FSD2 |
| Net weight | 24.8 kg |
| Dimensions / Width | 200 mm |
| Dimensions / Height | 460 mm |
| Dimensions / Depth | 245 mm |
Calculated values may differ from nameplate ratings.
Part variants and further information
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Buy parts and arrange repairs with FOXON
We supply new original and refurbished parts with a warranty. We confirm current availability and the possible delivery date before you place an order. For faulty parts, we check the options for diagnostics and professional repair.
Need to buy or repair this part?
Send the full order number, required quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.