from 321,86 EUR Incl. VAT
6SL3210-1KE11-8UF2
- SIEMENS
- SINAMICS
- SINAMICS G120C
- 6SL3210-1KE11-8UF2
6SL3210-1KE11-8UF2
SINAMICS G120C rated power 3AC380-480V +10/-20% 47-63Hz low overload: 0,55kW at 150% 3s, 110% 57s, 100% 240s high overload: 0,37kW at 200% 3s, 150% 57s, 100% 240s unfiltered external 24V I/O interface: 6DI, 2DO,1AI,1AO, 1Mot_t Safe Torque Off integrated Fieldbus: PROFINET-PN Protection: IP20/ UL OPEN TYPE Size: FSAA 173X73X160(HXWXD) More
Code: 6SL3210-1KE11-8UF2
SINAMICS G120C rated power 3AC380-480V +10/-20% 47-63Hz low overload: 0,55kW at 150% 3s, 110% 57s, 100% 240s high overload: 0,37kW at 200% 3s, 150% 57s, 100% 240s unfiltered external 24V I/O interface: 6DI, 2DO,1AI,1AO, 1Mot_t Safe Torque Off integrated Fieldbus: PROFINET-PN Protection: IP20/ UL OPEN TYPE Size: FSAA 173X73X160(HXWXD) More
Code: 6SL3210-1KE11-8UF2
Part Sales 2
| Condition | Code | Warranty | Availability |
Delivery Express? | Price excl. VAT | |
|---|---|---|---|---|---|---|
| New in sealed box (NC) | 6SL3210-1KE11-8UF2 NC | 12/24 months | In external stock 20 pcs |
Within 2-4 days / Express
|
On request
|
|
| Refurbished (R) | 6SL3210-1KE11-8UF2 R | 12/24 months | In external stock 2 pcs |
Within 2-4 days / Express
|
On request
|
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6SL3210-1KE11-8UF2 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6SL3210-1KE11-8UF2 – SINAMICS G120C
Siemens 6SL3210-1KE11-8UF2: SINAMICS G120C.
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6SL3210-1KE11-8UF2 |
| Input / Number of phases | 3 AC |
| Input / Line voltage | 380 ... 480 V +10 % -20 % |
| Input / Line frequency | 47 ... 63 Hz |
| Input / Rated current (LO) | 2.30 A |
| Input / Rated current (HO) | 1.90 A |
| Output / Number of phases | 3 AC |
| Output / Rated voltage | 400V IEC / 480V NEC 1) |
| Output / Rated power (LO) | 0.55 kW / 0.75 hp |
| Output / Rated power (HO) | 0.37 kW / 0.50 hp |
| Output / Rated current (LO) | 1.70 A |
| Output / Rated current (HO) | 1.30 A |
| Output / Rated current (IN) | 1.80 A |
| Output / Max. output current | 2.60 A |
| Output / Pulse frequency | 4 kHz |
| Efficiency η | 0.97 |
| Power loss | 33.5 W |
| Filter class (integrated) | Unfiltered |
| Communication / Communication | PROFINET, EtherNet/IP |
| Inputs / outputs / Standard digital inputs / Number | 6 |
| Inputs / outputs / Fail-safe digital inputs / Number | 1 |
| Inputs / outputs / Digital outputs / Number as relay changeover contact | 1 |
| Inputs / outputs / Digital outputs / Number as transistor | 1 |
| Inputs / outputs / Analog / digital inputs / Number | 1 (Differential input) |
| Inputs / outputs / Analog outputs / Number | 1 (Non-isolated output) |
| Ambient conditions / Cooling | Air cooling using an integrated fan |
| Ambient conditions / Cooling air requirement | 0.005 m³/s |
| Ambient conditions / Installation altitude | 1,000 m |
| Ambient conditions / Ambient temperature / Operation | -10 ... 40 °C |
| Ambient conditions / Ambient temperature / Storage | -25 ... 55 °C |
| Connections / Signal cable / Conductor cross-section | 0.15 ... 1.50 mm² (AWG 24 ... AWG 16) |
| Connections / Line side / Version | Plug-in screw terminals |
| Connections / Line side / Conductor cross-section | 1.00 ... 2.50 mm² (AWG 18 ... AWG 14) |
| Connections / Motor end / Version | Plug-in screw terminals |
| Connections / Motor end / Conductor cross-section | 1.00 ... 2.50 mm² (AWG 18 ... AWG 14) |
| Connections / DC link (for braking resistor) / Version | Plug-in screw terminals |
| Connections / DC link (for braking resistor) / Conductor cross-section | 1.00 ... 2.50 mm² (AWG 18 ... AWG 14) |
| Connections / Max. motor cable length / Shielded | 150 m |
| Connections / Max. motor cable length / Unshielded | 150 m |
| Degree of protection | IP20 / UL open type |
| Frame size | FSAA |
| Net weight | 1.40 kg |
| Dimensions / Width | 73 mm |
| Dimensions / Height | 173 mm |
| Dimensions / Depth | 160 mm |
1) The output current and HP ratings are valid for the voltage range 440V-480V 28.1 W (2.4 %) 27.9 W (2.4 %) 30.3 W (2.6 %) 31.7 W (2.7 %) 33.5 W (2.8 %) 29.7 W (2.5 %)28.9 W (2.5 %) 28.3 W (2.4 %) f90%50% 25% 50% I 100%
Calculated values may differ from nameplate ratings.
Part variants and further information
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Buy parts and arrange repairs with FOXON
We supply new original and refurbished parts with a warranty. We confirm current availability and the possible delivery date before you place an order. For faulty parts, we check the options for diagnostics and professional repair.
Need to buy or repair this part?
Send the full order number, required quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.