SIMATIC S7-300, counter module fm 350-2, 8 channels, 20 kHz, 24V encoder for counting, measuring frequencies, speed measurement, period duration measurement and proportioning incl. config. package and electronic docu on CD More
Code: 6ES7350-2AH00-0AE0
SIMATIC S7-300, counter module fm 350-2, 8 channels, 20 kHz, 24V encoder for counting, measuring frequencies, speed measurement, period duration measurement and proportioning incl. config. package and electronic docu on CD More
Code: 6ES7350-2AH00-0AE0
Part Sales 4
| Condition | Code | Warranty | Availability |
Delivery Express? | Price excl. VAT | |
|---|---|---|---|---|---|---|
| New in open box (NO) | 6ES7350-2AH00-0AE0 NO | 12/24 months | In external stock 1 pcs |
Within 2-4 days / Express
|
On request
|
|
| Refurbished (R) | 6ES7350-2AH00-0AE0 R | 12/24 months | In external stock 5 pcs |
Within 2-4 days / Express
|
On request
|
|
| Used and tested (T) | 6ES7350-2AH00-0AE0 T | 6 months | In stock FOXON 4 pcs |
141 EUR
|
||
| Used (U) | 6ES7350-2AH00-0AE0 U | 3 months | In external stock 1 pcs |
Within 2-4 days / Express
|
On request
|
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6ES7350-2AH00-0AE0 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6ES7350-2AH00-0AE0 – FM 350-2
Siemens SIMATIC S7-300 FM 350-2.
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Application and selection
Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6ES7350-2AH00-0AE0 |
| Product type designation | FM 350-2 |
| Voltages and currents / Aux. voltage 1L+, load voltage 2 L+ / Rated value (DC) | 24 V |
| Voltages and currents / Aux. voltage 1L+, load voltage 2 L+ / permissible range, lower limit (DC) | 20.4 V |
| Voltages and currents / Aux. voltage 1L+, load voltage 2 L+ / permissible range, upper limit (DC) | 28.8 V |
| Current consumption / from load voltage L+ (without load), max. | 150 mA |
| Current consumption / from backplane bus DC 5 V, max. | 100 mA |
| Current consumption / Power loss, typ. | 10 W |
| Connection point / required front connectors | 1 x 40-pin |
| Digital inputs / Number of digital inputs | 8 |
| Digital inputs / Functions | 1 each for gate start/ gate stop |
| Digital inputs / Cable length / Cable length, shielded, max. | 100 m |
| Digital inputs / Input voltage / for signal "0" | 3 to 5 V |
| Digital inputs / Input voltage / for signal "1" | 11 to 30.2 V |
| Digital inputs / Input current / for signal "0", max. (permissible quiescent current) | 2 mA |
| Digital inputs / Input current / for signal "1", typ. | 9 mA |
| Digital inputs / Input delay (for rated value of input voltage) / for standard inputs / at "0" to "1", max. | 50 µs |
| Digital outputs / Number of digital outputs | 8 |
| Digital outputs / Cable length, shielded, max. | 600 m |
| Digital outputs / Cable length unshielded, max. | 100 m |
| Digital outputs / Short-circuit protection of the output | Yes |
| Digital outputs / Limitation of inductive shutdown voltage to | L+ (-40 V) |
| Digital outputs / Output voltage / for signal "1", min. | L+ (-0,8 V) |
| Digital outputs / Output current / for signal "1" rated value | 0.5 A |
| Digital outputs / Output current / for signal "0" residual current, max. | 0.5 mA |
| Digital outputs / Output delay with resistive load / "0" to "1", max. | 300 µs |
| Digital outputs / Switching frequency / with resistive load, max. | 500 Hz |
| Digital outputs / Switching frequency / with inductive load, max. | 0.5 Hz |
| Digital outputs / Aggregate current of the outputs (per group) / horizontal installation / up to 40 °C, max. | 4 A |
| Digital outputs / Aggregate current of the outputs (per group) / horizontal installation / up to 60 °C, max. | 2 A |
| Digital outputs / Aggregate current of the outputs (per group) / all other mounting positions / up to 40 °C, max. | 2 A |
| Encoder supply / Output voltage | NAMUR-encoder supply: 8.2 V +/-2% |
| Encoder supply / Output current, rated value | 200 mA |
| Encoder supply / Short-circuit protection | Yes |
| Encoder / Connectable encoders / Incremental encoder (asymmetrical) | Yes |
| Encoder / Connectable encoders / 24 V initiator | Yes |
| Encoder / Connectable encoders / 24 V directional element | Yes |
| Encoder / Connectable encoders / NAMUR encoder | Yes |
| Encoder / Connectable encoders / 2-wire BEROS | Yes |
| Encoder / NAMUR encoder / Number of NAMUR inputs | 8 |
| Encoder / NAMUR encoder / Input signal | to DIN 19 234 |
| Encoder / NAMUR encoder / Input current, for signal "0", max. | 1.2 mA |
| Encoder / NAMUR encoder / Input current, for signal "1", min. | 2.1 mA |
| Encoder / NAMUR encoder / Input delay, max. | 50 µs |
| Encoder / NAMUR encoder / Input frequency, max. | 20 kHz |
| Encoder / NAMUR encoder / Cable length, shielded, max. | 100 m |
| Counters / Counter input 24 V / Number | 8; 32 bit or +/-31 bit |
| Counters / Counter input 24 V / Input voltage, for signal "0" | 3 to 5 V |
| Counters / Counter input 24 V / Input voltage, for signal "1" | 11 V to 30.2 V |
| Counters / Counter input 24 V / Input current, for signal "0", max.. (permissible idle current) | 2 mA |
| Counters / Counter input 24 V / Input current, for signal "1", typ. | 9 mA |
| Counters / Counter input 24 V / Input delay, max., | 50 µs |
| Counter frequency, max. | 20 kHz; 24 V incremental encoder: 10 kHz,; 24 V directional element: 20 kHz,; 24 V initiator: 20 kHz,; NAMUR sensor: 20 kHz |
| Cable length, max. | 100 m |
| Status information/ alarms/diagnostics / Alarms / Diagnostic alarm | Yes; parameterizable |
| Status information/ alarms/diagnostics / Alarms / Process alarm | Yes; parameterizable |
| Status information/ alarms/diagnostics / Diagnoses / Diagnostic functions | Yes; Diagnostic information readable |
| Isolation / Isolation, digital outputs / between the channels and the backplane bus | Yes; and shielding |
| Isolation / Galvanic isolation, digital inputs / between the channels and the backplane bus | Yes; and shielding |
| Isolation / Galvanic isolation, digital inputs / between the channels and the backplane bus (NAMUR) | Yes, against backplane bus and shielding |
| Isolation / Isolation counter / between the channels and the backplane bus | Yes; and shielding |
| Dimensions and weight / Width | 80 mm |
| Dimensions and weight / Height | 125 mm |
| Dimensions and weight / Depth | 120 mm |
| Weights / Weight, approx. | 460 g |
Connections and conditions of use
- Connection point / required front connectors: 1 x 40-pin
- Digital inputs / Input voltage / for signal "0": 3 to 5 V
- Digital inputs / Input voltage / for signal "1": 11 to 30.2 V
- Digital inputs / Input current / for signal "0", max. (permissible quiescent current): 2 mA
- Digital inputs / Input current / for signal "1", typ.: 9 mA
- Digital outputs / Output voltage / for signal "1", min.: L+ (-0,8 V)
- Digital outputs / Output current / for signal "1" rated value: 0.5 A
- Digital outputs / Output current / for signal "0" residual current, max.: 0.5 mA
Scope of supply
We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.
Frequently asked questions
Is the same product family enough to identify a replacement?
The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.
What information is needed to check connections and accessories?
Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.
Can you assess a faulty part?
Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.
Why buy from FOXON
Replacement part availability
We will check current part availability and confirm the possible delivery date before you order.
New original and refurbished parts
We will specify the available version and condition of the particular unit in the quotation.
Parts with a warranty
We will confirm the warranty period according to the part condition and specific quotation.
Diagnostics and repairs
For a faulty unit, we will check the options for diagnostics and professional repair.
Part conditions available for sale
Part conditions and warranty
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Sales, repairs and buyback of automation parts
We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.
Need to buy or repair this part?
Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.