from 27,83 EUR Incl. VAT
6EP1436-3BA00
- SIEMENS
- SITOP POWER SUPPLIES
- 6EP1436-3BA00
6EP1436-3BA00
SITOP modular 20 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/20 A More
Code: 6EP1436-3BA00
SITOP modular 20 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/20 A More
Code: 6EP1436-3BA00
Part Sales 3
| Condition | Code | Warranty | Availability |
Delivery Express? | Price excl. VAT | |
|---|---|---|---|---|---|---|
| New in sealed box (NC) | 6EP1436-3BA00 NC | 12/24 months | In external stock 7 pcs |
Within 2-4 days / Express
|
On request
|
|
| Refurbished (R) | 6EP1436-3BA00 R | 12/24 months | In external stock 19 pcs |
Within 2-4 days / Express
|
On request
|
|
| Used (U) | 6EP1436-3BA00 U | 3 months | In external stock 6 pcs |
Within 2-4 days / Express
|
On request
|
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6EP1436-3BA00 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6EP1436-3BA00 – modular
SITOP modular/3AC/24VDC/20A SITOP modular 20 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/20 A
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Application and selection
Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6EP1436-3BA00 |
| General information / product type designation | modular |
| General information / product designation | Power supply SITOP modular |
| General information / type of current supply | 24 V/20 A |
| input / type of the power supply network | 3-phase AC |
| input / phase number | 3 |
| input / voltage curve at input | AC |
| input / supply voltage at AC / minimum rated value | 400 V |
| input / supply voltage at AC / maximum rated value | 500 V |
| input / supply voltage at AC / initial value | 320 V |
| input / supply voltage at AC / full-scale value | 550 V |
| input / supply voltage at AC | Starting from Vin > 340 V |
| input / supply voltage / at 50 Hz | 400 V |
| input / supply voltage / at 60 Hz | 500 V |
| input / line frequency | 50/60 Hz |
| input / wide range input | Yes |
| input / overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
| input / buffering time for rated value of the output current in the event of | 6 ms |
| input / operating condition of the mains buffering | at Vin = 400 V |
| input / input current / at rated input voltage 400 V | 1.1 A |
| input / input current / at rated input voltage 500 V | 0.9 A |
| input / current limitation of inrush current at 25 °C maximum | 35 A |
| input / I2t value maximum | 0.7 A²·s |
| input / fuse protection type | none |
| input / fuse protection type in the feeder | Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) |
| output / voltage curve at output | Controlled, isolated DC voltage |
| output / product function output voltage controlled | Yes |
| output / product function output voltage stabilized | Yes |
| output / output voltage at DC rated value | 24 V |
| output / output voltage / at output 1 at DC rated value | 24 V |
| output / output voltage / at output 1 at DC | 24 V |
| output / output voltage adjustable | Yes; via potentiometer |
| output / adjustable output voltage | 24 ... 28.8 V; max. 480 W |
| output / relative overall tolerance of the voltage | 3 % |
| output / relative control precision of the output voltage / on slow fluctuation of input voltage | 0.1 % |
| output / relative control precision of the output voltage / on slow fluctuation of ohm loading | 0.2 % |
| output / residual ripple / maximum | 100 mV |
| output / voltage peak / maximum | 200 mV |
| output / display version for normal operation | Green LED for 24 V OK |
| output / type of signal at output | via signaling module (6EP1961-3BA10) |
| output / behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
| output / response delay maximum | 2.5 s |
| output / voltage increase time of the output voltage / maximum | 500 ms |
| output / output current / rated value | 20 A |
| output / output current / rated range | 0 ... 20 A; +60 ... +70 °C: Derating 2%/K |
| output / supplied active power typical | 480 W |
| output / short-term overload current / at short-circuit during operation typical | 60 A |
| output / duration of overloading capability for excess current / at short-circuit during operation | 25 ms |
| output / constant overload current / on short-circuiting during the start-up typical | 23 A |
| output / bridging of equipment | Yes; switchable characteristic |
| output / number of parallel-switched equipment resources for increasing | 2 |
| efficiency / efficiency in percent | 90 % |
| efficiency / power loss [W] / at rated output voltage for rated value of the output | 53 W |
| closed-loop control / relative control precision of the output voltage with rapid | 1 % |
| closed-loop control / relative control precision of the output voltage load step of | 2 % |
| closed-loop control / setting time / load step 50 to 100% typical | 4 ms |
| closed-loop control / setting time / load step 100 to 50% typical | 4 ms |
| closed-loop control / setting time / maximum | 10 ms |
| protection and monitoring / design of the overvoltage protection | < 35 V |
| protection and monitoring / property of the output short-circuit proof | Yes |
| protection and monitoring / design of short-circuit protection | Alternatively, constant current characteristic approx. 23 A or latching shutdown |
| protection and monitoring / typical | 23 A |
| protection and monitoring / enduring short circuit current RMS value / typical | 23 A |
| protection and monitoring / display version for overload and short circuit | LED yellow for "overload", LED red for "latching shutdown" |
| safety / galvanic isolation between input and output | Yes |
| safety / galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| safety / operating resource protection class | Class I |
| safety / leakage current / maximum | 3.5 mA |
| safety / protection class IP | IP20 |
| EMC / standard / for emitted interference | EN 55022 Class B |
| EMC / standard / for mains harmonics limitation | EN 61000-3-2 |
| EMC / standard / for interference immunity | EN 61000-6-2 |
| ambient conditions / ambient temperature / during operation | 0 ... 70 °C; with natural convection |
| ambient conditions / ambient temperature / during transport | -40 ... +85 °C |
| ambient conditions / ambient temperature / during storage | -40 ... +85 °C |
| ambient conditions / environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| connection method / type of electrical connection | screw terminal |
| connection method / at input | L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded |
| connection method / at output | +, -: 2 screw terminals each for 0.33 ... 4 mm² |
| connection method / for auxiliary contacts | - |
| mechanical data / width × height × depth of the enclosure | 160 × 125 × 125 mm |
| mechanical data / installation width × mounting height | 160 mm × 225 mm |
| mechanical data / required spacing / top | 50 mm |
| mechanical data / required spacing / bottom | 50 mm |
| mechanical data / required spacing / left | 0 mm |
| mechanical data / required spacing / right | 0 mm |
| mechanical data / fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| mechanical data / required spacing / DIN-rail mounting | Yes |
| mechanical data / required spacing / S7 rail mounting | No |
| mechanical data / required spacing / wall mounting | No |
| mechanical data / housing can be lined up | Yes |
| mechanical data / net weight | 2 kg |
| accessories / electrical accessories | Buffer module, signaling module |
| Output voltage | 24 V DC |
Connections and conditions of use
- output / type of signal at output: via signaling module (6EP1961-3BA10)
- connection method / type of electrical connection: screw terminal
- connection method / at input: L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded
- connection method / at output: +, -: 2 screw terminals each for 0.33 ... 4 mm²
- connection method / for auxiliary contacts: -
Scope of supply
We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.
Frequently asked questions
Is the same product family enough to identify a replacement?
The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.
What information is needed to check connections and accessories?
Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.
Can you assess a faulty part?
Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.
Why buy from FOXON
Replacement part availability
We will check current part availability and confirm the possible delivery date before you order.
New original and refurbished parts
We will specify the available version and condition of the particular unit in the quotation.
Parts with a warranty
We will confirm the warranty period according to the part condition and specific quotation.
Diagnostics and repairs
For a faulty unit, we will check the options for diagnostics and professional repair.
Part conditions available for sale
Part conditions and warranty
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Sales, repairs and buyback of automation parts
We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.
Need to buy or repair this part?
Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.