6EP1333-1AL12

6EP1333-1AL12

Sales, Repair, Purchase

SIEMENS

SITOP power 5 A, special line stabilized power supply input: 120/230 V AC output: 24 V DC/5 A More

Code: 6EP1333-1AL12

Total in stock: 2 pcs External stock 2 pcs
Variant does not exist

Rezervace termínu

Get a quote
SIEMENS

SITOP power 5 A, special line stabilized power supply input: 120/230 V AC output: 24 V DC/5 A More

Code: 6EP1333-1AL12

Part Sales 2

Condition Code Warranty Availability Delivery
Express?
Price excl. VAT
Refurbished (R) 6EP1333-1AL12 R 12/24 months In stock
On request
Used (U) 6EP1333-1AL12 U 3 months In external stock 2 pcs
Within 2-4 days / Express
On request

Repair of the part

Name Code Delivery Warranty Price excl. VAT
Complete part repair 6EP1333-1AL12 O 3-6 weeks 24 months On request Enquire a repair

6EP1333-1AL12 – Siemens 6EP1333-1AL12

SITOP POWER/1AC/24VDC/5A/FLAT DESIGN SITOP power 5 A, special line stabilized power supply input: 120/230 V AC output: 24 V DC/5 A

Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.

Request a quote for purchase or repair
Set by means of selector switch on the deviceinput / supply voltage at AC
120 V/230 Vinput / supply voltage
85 ... 132 Vinput / input voltage 1 at AC

Application and selection

Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.

Technical specifications

ManufacturerSiemens
Order number6EP1333-1AL12
General information / product designationPower supply SITOP power
General information / type of current supply24 V/5 A
input / type of the power supply network1-phase AC
input / phase number1
input / voltage curve at inputAC
input / supply voltage at ACSet by means of selector switch on the device
input / supply voltage120 V/230 V
input / input voltage 1 at AC85 ... 132 V
input / input voltage 2 at AC170 ... 264 V
input / supply voltage / at 50 Hz230 V
input / supply voltage / at 60 Hz120 V
input / line frequency50/60 Hz
input / wide range inputNo
input / overvoltage overload capability2.3 × Vin rated, 1.3 ms
input / buffering time for rated value of the output current in the event of20 ms
input / operating condition of the mains bufferingat Vin = 93/187 V
input / input current / at rated input voltage 120 V2.2 A
input / input current / at rated input voltage 230 V1.2 A
input / current limitation of inrush current at 25 °C maximum32 A
input / duration of inrush current limiting at 25 °C / maximum3 ms
input / I2t value maximum0.8 A²·s
input / fuse protection typeT 3,15 A/250 V (not accessible)
input / fuse protection type in the feederRecommended miniature circuit breaker: from 6 A characteristic C
output / voltage curve at outputControlled, isolated DC voltage
output / product function output voltage controlledYes
output / product function output voltage stabilizedYes
output / output voltage at DC rated value24 V
output / output voltage / at output 1 at DC rated value24 V
output / output voltage / at output 1 at DC24 V
output / output voltage adjustableYes; via potentiometer
output / adjustable output voltage22 ... 29 V
output / relative overall tolerance of the voltage1 %
output / relative control precision of the output voltage / on slow fluctuation of input voltage0.1 %
output / relative control precision of the output voltage / on slow fluctuation of ohm loading0.5 %
output / residual ripple / maximum150 mV
output / residual ripple / typical40 mV
output / voltage peak / maximum240 mV
output / voltage peak / typical100 mV
output / display version for normal operationGreen LED for 24 V OK
output / behavior of the output voltage when switching onNo overshoot of Vout (soft start)
output / response delay maximum2 s
output / voltage increase time of the output voltage / typical40 ms
output / output current / rated value5 A
output / output current / rated range0 ... 5 A
output / supplied active power typical120 W
output / short-term overload current / on short-circuiting during the start-up typical20 A
output / short-term overload current / at short-circuit during operation typical20 A
output / duration of overloading capability for excess current / on short-circuiting during the start-up500 ms
output / duration of overloading capability for excess current / at short-circuit during operation500 ms
output / bridging of equipmentYes
output / number of parallel-switched equipment resources for increasing2
efficiency / efficiency in percent88 %
efficiency / power loss [W] / at rated output voltage for rated value of the output17 W
closed-loop control / relative control precision of the output voltage with rapid0.3 %
closed-loop control / relative control precision of the output voltage load step of0.5 %
closed-loop control / setting time / load step 50 to 100% typical0.1 ms
closed-loop control / setting time / load step 100 to 50% typical0.1 ms
protection and monitoring / design of the overvoltage protectionAdditional control loop, shutdown at approx. 33 V, automatic restart
protection and monitoring / property of the output short-circuit proofYes
protection and monitoring / design of short-circuit protectionElectronic shutdown, automatic restart
protection and monitoring / response value current limitation5.5 ... 6.5 A
protection and monitoring / enduring short circuit current RMS value / maximum5 A
safety / galvanic isolation between input and outputYes
safety / galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
safety / operating resource protection classClass I
safety / leakage current / maximum3.5 mA
safety / leakage current / typical0.26 mA
safety / protection class IPIP20
EMC / standard / for emitted interferenceEN 55022 Class B
EMC / standard / for mains harmonics limitation-
EMC / standard / for interference immunityEN 61000-6-2
ambient conditions / ambient temperature / during operation0 ... 60 °C; with natural convection
ambient conditions / ambient temperature / during transport-40 ... +85 °C
ambient conditions / ambient temperature / during storage-40 ... +85 °C
ambient conditions / environmental category according to IEC 60721Climate class 3K3, 5 ... 95% no condensation
connection method / type of electrical connectionscrew terminal
connection method / at inputL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
connection method / at outputL+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
connection method / for auxiliary contacts-
mechanical data / width × height × depth of the enclosure160 × 130 × 60 mm
mechanical data / installation width × mounting height160 mm × 230 mm
mechanical data / required spacing / top50 mm
mechanical data / required spacing / bottom50 mm
mechanical data / required spacing / left0 mm
mechanical data / required spacing / right0 mm
mechanical data / fastening methodSnaps onto DIN rail EN 60715 35x7.5/15
mechanical data / required spacing / DIN-rail mountingYes
mechanical data / required spacing / S7 rail mountingNo
mechanical data / required spacing / wall mountingNo
mechanical data / housing can be lined upYes
mechanical data / net weight0.6 kg
Output voltage24 V DC

Connections and conditions of use

  • connection method / type of electrical connection: screw terminal
  • connection method / at input: L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
  • connection method / at output: L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
  • connection method / for auxiliary contacts: -

Scope of supply

We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.

Frequently asked questions

Is the same product family enough to identify a replacement?

The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.

What information is needed to check connections and accessories?

Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.

Can you assess a faulty part?

Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.

Why buy from FOXON

1

Replacement part availability

We will check current part availability and confirm the possible delivery date before you order.

2

New original and refurbished parts

We will specify the available version and condition of the particular unit in the quotation.

3

Parts with a warranty

We will confirm the warranty period according to the part condition and specific quotation.

4

Diagnostics and repairs

For a faulty unit, we will check the options for diagnostics and professional repair.

More than 3,500customers
We deliver tomore than 100 countries
Express delivery?We will check. Contact us now.

Part conditions available for sale

Part conditions and warranty
  • New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
  • New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
  • New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
  • New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
  • Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
  • Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
  • Used (U): Functional used part. 3-month warranty.

Sales, repairs and buyback of automation parts

We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.

More about parts sales, repairs and buyback

Need to buy or repair this part?

Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.

Request a quote for purchase or repair