6AG2552-1AA00-4AB0
- SIEMENS
- SIMATIC ET 200 / DP
- 6AG2552-1AA00-4AB0
6AG2552-1AA00-4AB0
SIPLUS S7-1500 TM timer DIDQ 16x 24 V rail based on 6ES7552-1AA00-0AB0 with conformal coating, -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes), time-controlled digital inputs and outputs max. 8 DI, 16 DQ of which max. 16 with time stamp, count, PWM, oversampling More
Code: 6AG2552-1AA00-4AB0
SIPLUS S7-1500 TM timer DIDQ 16x 24 V rail based on 6ES7552-1AA00-0AB0 with conformal coating, -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes), time-controlled digital inputs and outputs max. 8 DI, 16 DQ of which max. 16 with time stamp, count, PWM, oversampling More
Code: 6AG2552-1AA00-4AB0
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6AG2552-1AA00-4AB0 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6AG2552-1AA00-4AB0 – TM Timer DIDQ 16x24V
Siemens 6AG2552-1AA00-4AB0: SIPLUS S7-1500 TM timer DIDQ 16x 24 V rail based on 6ES7552-1AA00-0AB0 with conformal coating, -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes), time-controlled digital inputs and outputs max. 8 DI, 16 DQ of which max. 16 with time stamp, count, PWM, oversampling.
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6AG2552-1AA00-4AB0 |
| Product type | TM Timer DIDQ 16x24V |
| Supply voltage / Load voltage 1L+ / Rated value (DC) | 24 V |
| Supply voltage / Load voltage 2L+ / Rated value (DC) | 24 V |
| Input current / from load voltage 1L+ (without load), max. | 40 mA; without load |
| Input current / from load voltage 2L+ (without load), max. | 30 mA; without load |
| Encoder supply / 24 V encoder supply / Output current, max. | 1.2 A; Total current of all encoders / channels, max. 0.5 A per output |
| Power loss / Power loss, typ. | 5 W |
| Digital inputs / Number of digital inputs | 8; max. depending on parameterization |
| Digital inputs / Input voltage / Rated value (DC) | 24 V |
| Digital inputs / Input current / for signal "1", typ. | 2.5 mA |
| Digital inputs / Input delay (for rated value of input voltage) / Minimum pulse width for program reactions for standard inputs | 3 µs; for parameterization "none" |
| Digital inputs / Input delay (for rated value of input voltage) / parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 ms |
| Digital inputs / Cable length / shielded, max. | 1 000 m; Depending on sensor, cable quality and rate of change |
| Digital inputs / Cable length / unshielded, max. | 600 m; Depending on sensor, cable quality and rate of change |
| Digital outputs / Number of digital outputs | 16; max. depending on parameterization |
| Digital outputs / Output current / for signal "1" rated value | 0.5 A; 0.1 A with High Speed output, observe derating |
| Digital outputs / Output current / for signal "1" permissible range, max. | 0.6 A; 0.12 A with High Speed output, observe derating |
| Digital outputs / Cable length / shielded, max. | 1 000 m; depending on load and cable quality |
| Digital outputs / Cable length / unshielded, max. | 600 m; depending on load and cable quality |
| Encoder / Encoder signals, incremental encoder (asymmetrical) / Cable length, shielded, max. | 600 m; Depending on input frequency, encoder and cable quality; max. 200 m at 50 kHz |
| Ambient temperature during operation / horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| Ambient temperature during operation / horizontal installation, max. | 70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155) |
| Ambient temperature during operation / vertical installation, min. | -40 °C; = Tmin |
| Ambient temperature during operation / vertical installation, max. | 40 °C; = Tmax; Note derating |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights / Weight, approx. | 320 g |
Part variants and further information
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Buy parts and arrange repairs with FOXON
We supply new original and refurbished parts with a warranty. We confirm current availability and the possible delivery date before you place an order. For faulty parts, we check the options for diagnostics and professional repair.
Need to buy or repair this part?
Send the full order number, required quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.