6AG1961-3BA21-4AX0
- SIEMENS
- SIMATIC ET 200 / DP
- 6AG1961-3BA21-4AX0
6AG1961-3BA21-4AX0
SIPLUS PS E202U redundancy module based on 6EP1961-3BA21 with conformal coating, 0…+60 °C, input/output: 24 V DC/40 A suitable for decoupling two SITOP power supplies with max. 20 A output current each
More
Code: 6AG1961-3BA21-4AX0
SIPLUS PS E202U redundancy module based on 6EP1961-3BA21 with conformal coating, 0…+60 °C, input/output: 24 V DC/40 A suitable for decoupling two SITOP power supplies with max. 20 A output current each
More
Code: 6AG1961-3BA21-4AX0
Repair of the part
| Name | Code | Delivery | Warranty | Price excl. VAT | |
|---|---|---|---|---|---|
| Complete part repair | 6AG1961-3BA21-4AX0 O | 3-6 weeks | 24 months | On request | Enquire a repair |
6AG1961-3BA21-4AX0 – PSE202U
Siemens 6AG1961-3BA21-4AX0: SIPLUS PSE202U REDUNDANZMODUL SIPLUS PS E202U redundancy module based on 6EP1961-3BA21 with conformal coating, 0…+60 °C, input/output: 24 V DC/40 A suitable for decoupling two SITOP power supplies with max. 20 A output current each.
Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.
Technical specifications
| Manufacturer | Siemens |
|---|---|
| Order number | 6AG1961-3BA21-4AX0 |
| Product type | PSE202U |
| Product designation | Redundancy module |
| Input / supply voltage at DC | 24 V |
| Input / input voltage at DC | 24 ... 28.8 V |
| Output / product function output voltage controlled | Yes |
| Output / output voltage at DC rated value | 24 V |
| Output / formula for output voltage | Vin - approx. 0.5 V |
| Output / output voltage / at output 1 at DC rated value | 24 V |
| Output / output voltage / at output 1 at DC | 24 V |
| Output / output voltage adjustable | No |
| Output / output current / rated value | 40 A |
| Output / output current / rated range | 40 A; max. aggregate current 40 A; +60 ... +70 °C: derating 3%/K |
| Efficiency / power loss [W] / at rated output voltage for rated value of the output | 34 W |
| Efficiency / power loss [W] / during no-load operation maximum | 1.5 W |
| Safety / galvanic isolation between input and output | No |
| Safety / galvanic isolation | relay contact: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| Safety / protection class IP | IP20 |
| Ambient temperature / in horizontal mounting position during operation | 0 ... 60 °C; with natural convection |
| Width × height × depth of the enclosure | 70 × 125 × 120 mm |
| Net weight | 0.5 kg |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Part variants and further information
- New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
- New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
- New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
- New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
- Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
- Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
- Used (U): Functional used part. 3-month warranty.


Buy parts and arrange repairs with FOXON
We supply new original and refurbished parts with a warranty. We confirm current availability and the possible delivery date before you place an order. For faulty parts, we check the options for diagnostics and professional repair.
Need to buy or repair this part?
Send the full order number, required quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.
Request a quote for purchase or repairHighlighted items are mandatory.