6AG1331-7NF10-2AB0

6AG1331-7NF10-2AB0

Sales, Repair, Purchase

SIEMENS

SIPLUS S7-300 SM 331 8AI 40-pole based on 6ES7331-7NF10-0AB0 with conformal coating, -25…+60 °C, analog input isolated, 8 AI; +/-5/10V, 1-5 V, +/-20 mA, 0/4 to 20 mA, 16-bit, single rooting (60 V COM.), 4-channel operation: 10 ms, 8-channel operation: 23-95 ms, 1x 40-pole More

Code: 6AG1331-7NF10-2AB0

Variant does not exist

Rezervace termínu

Get a quote
SIEMENS

SIPLUS S7-300 SM 331 8AI 40-pole based on 6ES7331-7NF10-0AB0 with conformal coating, -25…+60 °C, analog input isolated, 8 AI; +/-5/10V, 1-5 V, +/-20 mA, 0/4 to 20 mA, 16-bit, single rooting (60 V COM.), 4-channel operation: 10 ms, 8-channel operation: 23-95 ms, 1x 40-pole More

Code: 6AG1331-7NF10-2AB0

Repair of the part

Name Code Delivery Warranty Price excl. VAT
Complete part repair 6AG1331-7NF10-2AB0 O 3-6 weeks 24 months On request Enquire a repair

6AG1331-7NF10-2AB0 – SM 331

SIPLUS S7-300 SM 331 8 AI 40-pole based on 6ES7331-7NF10- 0AB0 with conformal coating, -25…+60 °C, analog input isolated, 8 AI; +/-5/10V, 1- 5 V, +/-20 mA, 0/4 to 20 mA, 16 bit, single-point grounding (60 V common), 4- channel operation: 10 ms, 8-channel operation: 23-95 ms, 1x 40-pole

Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.

Request a quote for purchase or repair
24 VSupply voltage / Load voltage L+ / Rated value (DC)
YesSupply voltage / Load voltage L+ / Reverse polarity protection
8Analog inputs / Number of analog inputs

Application and selection

Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.

Technical specifications

ManufacturerSiemens
Order number6AG1331-7NF10-2AB0
General information / based on6ES7331-7NF10-0AB0
General information / Product function / Isochronous modeNo
Supply voltage / Load voltage L+ / Rated value (DC)24 V
Supply voltage / Load voltage L+ / Reverse polarity protectionYes
Input current / from load voltage L+ (without load), max.200 mA
Input current / from backplane bus 5 V DC, max.100 mA
Power loss / Power loss, typ.3 W
Analog inputs / Number of analog inputs8
Analog inputs / permissible input voltage for voltage input (destruction limit),75 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)
Analog inputs / permissible input current for current input (destruction limit),40 mA
Analog inputs / Input ranges / VoltageYes
Analog inputs / Input ranges / CurrentYes
Analog inputs / Input ranges / ThermocoupleNo
Analog inputs / Input ranges / Resistance thermometerNo
Analog inputs / Input ranges / ResistanceNo
Analog inputs / Input ranges (rated values), voltages / 0 to +10 VNo
Analog inputs / Input ranges (rated values), voltages / 1 V to 5 VYes
Analog inputs / Input ranges (rated values), voltages / Input resistance (1 V to 5 V)10 MΩ
Analog inputs / Input ranges (rated values), voltages / 1 V to 10 VNo
Analog inputs / Input ranges (rated values), voltages / -1 V to +1 VNo
Analog inputs / Input ranges (rated values), voltages / -10 V to +10 VYes
Analog inputs / Input ranges (rated values), voltages / Input resistance (-10 V to +10 V)10 MΩ
Analog inputs / Input ranges (rated values), voltages / -2.5 V to +2.5 VNo
Analog inputs / Input ranges (rated values), voltages / -250 mV to +250 mVNo
Analog inputs / Input ranges (rated values), voltages / -5 V to +5 VYes
Analog inputs / Input ranges (rated values), voltages / Input resistance (-5 V to +5 V)10 MΩ
Analog inputs / Input ranges (rated values), voltages / -50 mV to +50 mVNo
Analog inputs / Input ranges (rated values), voltages / -500 mV to +500 mVNo
Analog inputs / Input ranges (rated values), voltages / -80 mV to +80 mVNo
Analog inputs / Input ranges (rated values), currents / 0 to 20 mAYes
Analog inputs / Input ranges (rated values), currents / Input resistance (0 to 20 mA)250 Ω
Analog inputs / Input ranges (rated values), currents / -20 mA to +20 mAYes
Analog inputs / Input ranges (rated values), currents / Input resistance (-20 mA to +20 mA)250 Ω
Analog inputs / Input ranges (rated values), currents / -3.2 mA to +3.2 mANo
Analog inputs / Input ranges (rated values), currents / 4 mA to 20 mAYes
Analog inputs / Input ranges (rated values), currents / Input resistance (4 mA to 20 mA)250 Ω
Analog inputs / Input ranges (rated values), thermocouples / Type BNo
Analog inputs / Input ranges (rated values), thermocouples / Type CNo
Analog inputs / Input ranges (rated values), thermocouples / Type ENo
Analog inputs / Input ranges (rated values), thermocouples / Type JNo
Analog inputs / Input ranges (rated values), thermocouples / Type KNo
Analog inputs / Input ranges (rated values), thermocouples / Type LNo
Analog inputs / Input ranges (rated values), thermocouples / Type NNo
Analog inputs / Input ranges (rated values), thermocouples / Type RNo
Analog inputs / Input ranges (rated values), thermocouples / Type SNo
Analog inputs / Input ranges (rated values), thermocouples / Type TNo
Analog inputs / Input ranges (rated values), thermocouples / Type UNo
Analog inputs / Input ranges (rated values), thermocouples / Type TXK/TXK(L) to GOSTNo
Analog inputs / Input ranges (rated values), resistance thermometer / Cu 10No
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 100No
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 1000No
Analog inputs / Input ranges (rated values), resistance thermometer / LG-Ni 1000No
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 120No
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 200No
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 500No
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 100No
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 1000No
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 200No
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 500No
Analog inputs / Input ranges (rated values), resistors / 0 to 150 ohmsNo
Analog inputs / Input ranges (rated values), resistors / 0 to 300 ohmsNo
Analog inputs / Input ranges (rated values), resistors / 0 to 600 ohmsNo
Analog inputs / Input ranges (rated values), resistors / 0 to 6000 ohmsNo
Analog inputs / Cable length / shielded, max.200 m
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.16 bit; Unipolar: 15/15/15/15 bit; bipolar: 15 bit + sign/15 bit + sign/15 bit + sign/15 bit + sign
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Integration time, parameterizableYes; 23 / 72 / 83 / 95 ms
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Basic conversion time (ms)10 ms (4-channel mode); 95/83/72/23 ms (8-channel mode)
Analog value generation for the inputs / Integration and conversion time/resolution per channel / Interference voltage suppression for interference400 / 60 / 50 Hz, combinations of 400, 60, 50 Hz
Encoder / Connection of signal encoders / for voltage measurementYes
Encoder / Connection of signal encoders / for current measurement as 2-wire transducerYes; with external transmitter, current supply; possible with separate supply for transmitter
Encoder / Connection of signal encoders / for current measurement as 4-wire transducerYes
Errors/accuracies / Operational error limit in overall temperature range / Voltage, relative to input range, (+/-)0.1 %; @ 0 ... +60 °C; ±0.2% @ -25 ... +60 °C
Errors/accuracies / Operational error limit in overall temperature range / Current, relative to input range, (+/-)0.1 %; @ 0 ... +60 °C; ±0.2% @ -25 ... +60 °C
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Voltage, relative to input range, (+/-)0.05 %
Errors/accuracies / Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-)0.05 %
Interrupts/diagnostics/status information / Diagnostics functionYes; Parameterizable
Interrupts/diagnostics/status information / Alarms / Diagnostic alarmYes; Parameterizable
Interrupts/diagnostics/status information / Alarms / Limit value alarmYes; Parameterizable all channels (end of cycle interrupt is also supported across modules)
Interrupts/diagnostics/status information / Alarms / Hardware interruptYes; Parameterizable, channels 0 to 7 (on exceeding limit value), at end of cycle
Interrupts/diagnostics/status information / Diagnoses / Diagnostic information readableYes
Interrupts/diagnostics/status information / Diagnostics indication LED / Group error SF (red)Yes
Potential separation / Potential separation analog inputs / between the channelsNo
Potential separation / Potential separation analog inputs / between the channels, in groups of2
Potential separation / Potential separation analog inputs / between the channels and backplane busYes
Potential separation / Potential separation analog inputs / between the channels and the power supply of theYes
Isolation / Isolation tested with500 V AC
Ambient conditions / Ambient temperature during operation / min.-25 °C; = Tmin
Ambient conditions / Ambient temperature during operation / max.60 °C; = Tmax
Ambient conditions / Ambient temperature during storage/transportation / min.-40 °C
Ambient conditions / Ambient temperature during storage/transportation / max.70 °C
Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max.5 000 m
Ambient conditions / Altitude during operation relating to sea level / Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Ambient conditions / Relative humidity / With condensation, tested in accordance with IEC 60068-100 %; RH incl. condensation/frost (no commissioning under condensation
Ambient conditions / Relative humidity / 2-38, max.conditions)
Ambient conditions / Resistance / Use in stationary industrial systems / to biologically active substances according to ENYes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna);
Ambient conditions / Resistance / Use in stationary industrial systems / 60721-3-3Class 3B3 on request
Ambient conditions / Resistance / Use in stationary industrial systems / to chemically active substances according to ENYes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
Ambient conditions / Resistance / Use in stationary industrial systems / to mechanically active substances according to ENYes; Class 3S4 incl. sand, dust, *
Ambient conditions / Resistance / Use on ships/at sea / to biologically active substances according to ENYes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on
Ambient conditions / Resistance / Use on ships/at sea / 60721-3-6request
Ambient conditions / Resistance / Use on ships/at sea / to chemically active substances according to ENYes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
Ambient conditions / Resistance / Use on ships/at sea / to mechanically active substances according to ENYes; Class 6S3 incl. sand, dust; *
Ambient conditions / Resistance / Usage in industrial process technology / Against chemically active substances acc. to ENYes; Class 3 (excluding trichlorethylene)
Ambient conditions / Resistance / Usage in industrial process technology / Environmental conditions for process, measuringYes; Level GX group A/B (excluding trichlorethylene; harmful gas
Ambient conditions / Resistance / Usage in industrial process technology / and control systems acc. to ANSI/ISA-71.04concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Ambient conditions / Resistance / Remark / conditions acc. to EN 60721, EN 60654-4 andduring operation!
Connection method / required front connector40-pin
Dimensions / Width40 mm
Dimensions / Height125 mm
Dimensions / Depth120 mm
Weights / Weight, approx.272 g
Product type designationSM 331
Number of poles40

Supported signals and ranges

  • Supply voltage / Load voltage L+ / Rated value (DC): 24 V
  • Supply voltage / Load voltage L+ / Reverse polarity protection: Yes
  • Input current / from load voltage L+ (without load), max.: 200 mA
  • Analog inputs / permissible input voltage for voltage input (destruction limit),: 75 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)
  • Analog inputs / Input ranges / Voltage: Yes
  • Analog inputs / Input ranges / Current: Yes
  • Analog inputs / Input ranges / Thermocouple: No
  • Analog inputs / Input ranges / Resistance thermometer: No

Scope of supply

We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.

Frequently asked questions

Is the same product family enough to identify a replacement?

The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.

What information is needed to check connections and accessories?

Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.

Can you assess a faulty part?

Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.

Why buy from FOXON

1

Replacement part availability

We will check current part availability and confirm the possible delivery date before you order.

2

New original and refurbished parts

We will specify the available version and condition of the particular unit in the quotation.

3

Parts with a warranty

We will confirm the warranty period according to the part condition and specific quotation.

4

Diagnostics and repairs

For a faulty unit, we will check the options for diagnostics and professional repair.

More than 3,500customers
We deliver tomore than 100 countries
Express delivery?We will check. Contact us now.

Part conditions available for sale

Part conditions and warranty
  • New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
  • New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
  • New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
  • New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
  • Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
  • Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
  • Used (U): Functional used part. 3-month warranty.

Sales, repairs and buyback of automation parts

We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.

More about parts sales, repairs and buyback

Need to buy or repair this part?

Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.

Request a quote for purchase or repair