3RT1065-6AP36

3RT1065-6AP36

Sales, Repair, Purchase

SIEMENS

Power contactor, AC-3e/AC-3 265 A, 132 kW / 400 V AC (50-60 Hz) / DC Uc: 220-240 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal More

Code: 3RT1065-6AP36

Total in stock: 5 pcs External stock 5 pcs
Variant does not exist

Rezervace termínu

Get a quote
SIEMENS

Power contactor, AC-3e/AC-3 265 A, 132 kW / 400 V AC (50-60 Hz) / DC Uc: 220-240 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal More

Code: 3RT1065-6AP36

Part Sales 1

Condition Code Warranty Availability Delivery
Express?
Price excl. VAT
New in sealed box (NC) 3RT1065-6AP36 NC 12/24 months In external stock 5 pcs
Within 2-4 days / Express
On request

Repair of the part

Name Code Delivery Warranty Price excl. VAT
Complete part repair 3RT1065-6AP36 O 3-6 weeks 24 months On request Enquire a repair

3RT1065-6AP36 – Power contactor

Power contactor.

Need to buy or repair this part?
We will check replacement part availability and the options for diagnosing and repairing your faulty unit.

Request a quote for purchase or repair
145 mmInstallation/ mounting/ dimensions / width
3Main circuit / number of poles for main current circuit
3Main circuit / number of NO contacts for main contacts

Application and selection

Compare the complete order number and specifications below with the original part and machine wiring. Check the design, interfaces, supply voltage or connection method as applicable to this product.

Technical specifications

ManufacturerSiemens
Order number3RT1065-6AP36
product brand nameSIRIUS
product designationPower contactor
product type designation3RT1
General technical data / size of contactorS10
General technical data / product extension / function module for communicationNo
General technical data / product extension / auxiliary switchYes
General technical data / power loss [W] for rated value of the current / at AC in hot operating state54 W
General technical data / power loss [W] for rated value of the current / at AC in hot operating state per pole18 W
General technical data / power loss [W] for rated value of the current / without load current share typical7.4 W
General technical data / type of calculation of power loss current-dependentquadratic
General technical data / insulation voltage / of main circuit with degree of pollution 3 rated value1 000 V
General technical data / insulation voltage / of auxiliary circuit with degree of pollution 3 rated value500 V
General technical data / surge voltage resistance / of main circuit rated value8 kV
General technical data / surge voltage resistance / of auxiliary circuit rated value6 kV
General technical data / maximum permissible voltage for protective separation between690 V
General technical data / shock resistance at rectangular impulse / at AC8,5 g / 5 ms, 4,2 g / 10 ms
General technical data / shock resistance at rectangular impulse / at DC8,5 g / 5 ms, 4,2 g / 10 ms
General technical data / shock resistance with sine pulse / at AC13,4 g / 5 ms, 6,5 g / 10 ms
General technical data / shock resistance with sine pulse / at DC13,4 g / 5 ms, 6,5 g / 10 ms
General technical data / mechanical service life (operating cycles) / of contactor typical10 000 000
General technical data / mechanical service life (operating cycles) / of the contactor with added electronically optimized5 000 000
General technical data / mechanical service life (operating cycles) / of the contactor with added auxiliary switch block typical10 000 000
General technical data / reference code according to IEC 81346-2Q
General technical data / Substance Prohibitance (day/month/year)05/01/2012
General technical data / SVHC substance nameLead CAS-No. 7439-92-1
General technical data / Net Weight6.162 kg
Ambient conditions / installation altitude at height above sea level maximum2 000 m
Ambient conditions / ambient temperature / during operation-25 ... +60 °C
Ambient conditions / ambient temperature / during storage-55 ... +80 °C
Ambient conditions / relative humidity minimum10 %
Ambient conditions / relative humidity at 55 °C according to IEC 60068-2-3095 %
Main circuit / number of poles for main current circuit3
Main circuit / number of NO contacts for main contacts3
Main circuit / number of NC contacts for main contacts0
Main circuit / operating voltage / at AC-3 rated value maximum1 000 V
Main circuit / operating voltage / at AC-3e rated value maximum1 000 V
Main circuit / operational current / at AC-1 at 400 V at ambient temperature 40 °C rated330 A
Main circuit / operational current / at AC-1 / up to 690 V at ambient temperature 40 °C rated330 A
Main circuit / operational current / at AC-1 / up to 690 V at ambient temperature 60 °C rated300 A
Main circuit / operational current / at AC-1 / up to 1000 V at ambient temperature 40 °C rated150 A
Main circuit / operational current / at AC-1 / up to 1000 V at ambient temperature 60 °C rated150 A
Main circuit / operational current / at AC-3 / at 400 V rated value265 A
Main circuit / operational current / at AC-3 / at 500 V rated value265 A
Main circuit / operational current / at AC-3 / at 690 V rated value265 A
Main circuit / operational current / at AC-3 / at 1000 V rated value95 A
Main circuit / operational current / at AC-3e / at 400 V rated value265 A
Main circuit / operational current / at AC-3e / at 500 V rated value265 A
Main circuit / operational current / at AC-3e / at 690 V rated value265 A
Main circuit / operational current / at AC-3e / at 1000 V rated value95 A
Main circuit / operational current / at AC-4 at 400 V rated value230 A
Main circuit / operational current / at AC-5a up to 690 V rated value290 A
Main circuit / operational current / at AC-5b up to 400 V rated value at AC-6a219 A
Main circuit / operational current / at AC-3e / up to 230 V for current peak value n=20 rated value265 A
Main circuit / operational current / at AC-3e / up to 400 V for current peak value n=20 rated value265 A
Main circuit / operational current / at AC-3e / up to 500 V for current peak value n=20 rated value265 A
Main circuit / operational current / at AC-3e / up to 690 V for current peak value n=20 rated value265 A
Main circuit / operational current / at AC-3e / up to 1000 V for current peak value n=20 rated95 A
Main circuit / operational current / at AC-6a / up to 230 V for current peak value n=30 rated value184 A
Main circuit / operational current / at AC-6a / up to 400 V for current peak value n=30 rated value184 A
Main circuit / operational current / at AC-6a / up to 500 V for current peak value n=30 rated value184 A
Main circuit / operational current / at AC-6a / up to 690 V for current peak value n=30 rated value184 A
Main circuit / operational current / at AC-6a / up to 1000 V for current peak value n=30 rated95 A
Main circuit / minimum cross-section in main circuit at maximum AC-1 rated185 mm²
Main circuit / AC-4 / at 400 V rated value117 A
Main circuit / AC-4 / at 690 V rated value105 A
Main circuit / operational current / at 1 current path at DC-1 / at 24 V rated value300 A
Main circuit / operational current / at 1 current path at DC-1 / at 60 V rated value300 A
Main circuit / operational current / at 1 current path at DC-1 / at 110 V rated value33 A
Main circuit / operational current / at 1 current path at DC-1 / at 220 V rated value3.8 A
Main circuit / operational current / at 1 current path at DC-1 / at 440 V rated value0.9 A
Main circuit / operational current / at 1 current path at DC-1 / at 600 V rated value0.6 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 24 V rated value300 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 60 V rated value300 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 110 V rated value300 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 220 V rated value300 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 440 V rated value4 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 600 V rated value2 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 24 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 60 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 110 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 220 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 440 V rated value11 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 600 V rated value5.2 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 24 V rated value300 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 60 V rated value11 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 110 V rated value3 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 220 V rated value0.6 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 440 V rated value0.18 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 600 V rated value0.125 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 24 V rated value300 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 60 V rated value300 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 110 V rated value300 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 220 V rated value2.5 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 440 V rated value0.65 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 600 V rated value0.37 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 24 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 60 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 110 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 220 V rated value300 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 440 V rated value1.4 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 600 V rated value0.75 A
Main circuit / operating power / at AC-3 / at 230 V rated value75 kW
Main circuit / operating power / at AC-3 / at 400 V rated value132 kW
Main circuit / operating power / at AC-3 / at 500 V rated value160 kW
Main circuit / operating power / at AC-3 / at 690 V rated value250 kW
Main circuit / operating power / at AC-3 / at 1000 V rated value132 kW
Main circuit / operating power / at AC-3e / at 230 V rated value75 kW
Main circuit / operating power / at AC-3e / at 400 V rated value132 kW
Main circuit / operating power / at AC-3e / at 500 V rated value160 kW
Main circuit / operating power / at AC-3e / at 690 V rated value250 kW
Main circuit / operating power / at AC-3e / at 1000 V rated value132 kW
Main circuit / 4 / at 400 V rated value66 kW
Main circuit / 4 / at 690 V rated value102 kW
Main circuit / operating apparent power at AC-6a / up to 230 V for current peak value n=20 rated value100 kVA
Main circuit / operating apparent power at AC-6a / up to 400 V for current peak value n=20 rated value180 kVA
Main circuit / operating apparent power at AC-6a / up to 500 V for current peak value n=20 rated value220 kVA
Main circuit / operating apparent power at AC-6a / up to 690 V for current peak value n=20 rated value310 kVA
Main circuit / operating apparent power at AC-6a / up to 1000 V for current peak value n=20 rated value160 kVA
Main circuit / operating apparent power at AC-6a / operating apparent power at AC-6a / up to 230 V for current peak value n=30 rated value70 kVA
Main circuit / operating apparent power at AC-6a / operating apparent power at AC-6a / up to 400 V for current peak value n=30 rated value120 kVA
Main circuit / operating apparent power at AC-6a / operating apparent power at AC-6a / up to 500 V for current peak value n=30 rated value150 kVA
Main circuit / operating apparent power at AC-6a / operating apparent power at AC-6a / up to 690 V for current peak value n=30 rated value220 kVA
Main circuit / operating apparent power at AC-6a / operating apparent power at AC-6a / up to 1000 V for current peak value n=30 rated value160 kVA
Main circuit / operating apparent power at AC-6a / 40 °C / limited to 1 s switching at zero current maximum4 880 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / operating apparent power at AC-6a / 40 °C / limited to 5 s switching at zero current maximum4 045 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / operating apparent power at AC-6a / 40 °C / limited to 10 s switching at zero current maximum2 785 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / operating apparent power at AC-6a / 40 °C / limited to 30 s switching at zero current maximum1 664 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / operating apparent power at AC-6a / 40 °C / limited to 60 s switching at zero current maximum1 276 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / operating apparent power at AC-6a / no-load switching frequency / at AC2 000 1/h
Main circuit / operating apparent power at AC-6a / no-load switching frequency / at DC2 000 1/h
Main circuit / operating apparent power at AC-6a / operating frequency / at AC-1 maximum800 1/h
Main circuit / operating apparent power at AC-6a / operating frequency / at AC-2 maximum250 1/h
Main circuit / operating apparent power at AC-6a / operating frequency / at AC-3 maximum at AC-3e500 1/h
Main circuit / operating apparent power at AC-6a / operating frequency / maximum500 1/h
Main circuit / operating apparent power at AC-6a / operating frequency / at AC-4 maximum130 1/h
Control circuit/ Control / type of voltage of the control supply voltageAC/DC
Control circuit/ Control / control supply voltage at AC / at 50 Hz rated value220 ... 240 V
Control circuit/ Control / control supply voltage at AC / at 60 Hz rated value220 ... 240 V
Control circuit/ Control / control supply voltage at DC rated value220 ... 240 V
Control circuit/ Control / magnet coil at DC / initial value0.8
Control circuit/ Control / magnet coil at DC / full-scale value1.1
Control circuit/ Control / magnet coil at AC / at 50 Hz0.8 ... 1.1
Control circuit/ Control / magnet coil at AC / at 60 Hz0.8 ... 1.1
Control circuit/ Control / design of the surge suppressorwith varistor
Control circuit/ Control / apparent pick-up power / at minimum rated control supply voltage at AC / at 50 Hz490 V·A
Control circuit/ Control / apparent pick-up power / at minimum rated control supply voltage at AC / at 60 Hz490 V·A
Control circuit/ Control / apparent pick-up power / at maximum rated control supply voltage at AC / at 60 Hz590 V·A
Control circuit/ Control / apparent pick-up power / at maximum rated control supply voltage at AC / at 50 Hz590 V·A
Control circuit/ Control / apparent pick-up power of magnet coil at AC / at 50 Hz590 V·A
Control circuit/ Control / apparent pick-up power of magnet coil at AC / at 60 Hz590 V·A
Control circuit/ Control / inductive power factor with closing power of the coil / at 50 Hz0.9
Control circuit/ Control / inductive power factor with closing power of the coil / at 60 Hz0.9
Control circuit/ Control / apparent holding power / at minimum rated control supply voltage at DC6.1 V·A
Control circuit/ Control / apparent holding power / at maximum rated control supply voltage at DC7.4 V·A
Control circuit/ Control / apparent holding power / at minimum rated control supply voltage at AC / at 50 Hz5.6 V·A
Control circuit/ Control / apparent holding power / at minimum rated control supply voltage at AC / at 60 Hz5.6 V·A
Control circuit/ Control / apparent holding power / at maximum rated control supply voltage at AC / at 50 Hz6.7 V·A
Control circuit/ Control / apparent holding power / at maximum rated control supply voltage at AC / at 60 Hz6.7 V·A
Control circuit/ Control / inductive power factor with the holding power of the coil / at 50 Hz0.9
Control circuit/ Control / inductive power factor with the holding power of the coil / at 60 Hz0.9
Control circuit/ Control / closing power of magnet coil at DC650 W
Control circuit/ Control / holding power of magnet coil at DC7.4 W
Control circuit/ Control / closing delay / at AC30 ... 95 ms
Control circuit/ Control / closing delay / at DC30 ... 95 ms
Control circuit/ Control / opening delay / at AC40 ... 80 ms
Control circuit/ Control / opening delay / at DC40 ... 80 ms
Control circuit/ Control / arcing time10 ... 15 ms
Control circuit/ Control / control version of the switch operating mechanismStandard A1 - A2
Auxiliary circuit / number of NC contacts for auxiliary contacts instantaneous2
Auxiliary circuit / number of NO contacts for auxiliary contacts instantaneous2
Auxiliary circuit / operational current at AC-12 maximum10 A
Auxiliary circuit / operational current at AC-15 / at 230 V rated value6 A
Auxiliary circuit / operational current at AC-15 / at 400 V rated value3 A
Auxiliary circuit / operational current at AC-15 / at 500 V rated value2 A
Auxiliary circuit / operational current at AC-15 / at 690 V rated value1 A
Auxiliary circuit / operational current at DC-12 / at 24 V rated value10 A
Auxiliary circuit / operational current at DC-12 / at 48 V rated value6 A
Auxiliary circuit / operational current at DC-12 / at 60 V rated value6 A
Auxiliary circuit / operational current at DC-12 / at 110 V rated value3 A
Auxiliary circuit / operational current at DC-12 / at 125 V rated value2 A
Auxiliary circuit / operational current at DC-12 / at 220 V rated value1 A
Auxiliary circuit / operational current at DC-12 / at 600 V rated value0.15 A
Auxiliary circuit / operational current at DC-13 / at 24 V rated value10 A
Auxiliary circuit / operational current at DC-13 / at 48 V rated value2 A
Auxiliary circuit / operational current at DC-13 / at 60 V rated value2 A
Auxiliary circuit / operational current at DC-13 / at 110 V rated value1 A
Auxiliary circuit / operational current at DC-13 / at 125 V rated value0.9 A
Auxiliary circuit / operational current at DC-13 / at 220 V rated value0.3 A
Auxiliary circuit / operational current at DC-13 / at 600 V rated value0.1 A
Auxiliary circuit / contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 480 V rated value240 A
UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 600 V rated value242 A
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 200/208 V rated value75 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 220/230 V rated value100 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 460/480 V rated value200 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 575/600 V rated value250 hp
UL/CSA ratings / contact rating of auxiliary contacts according to ULA600 / Q600
Short-circuit protection / design of the miniature circuit breaker for short-circuit protectionC characteristic: 10 A; 0.4 kA
Short-circuit protection / design of the fuse link / for short-circuit protection of the main circuit / with type of coordination 1 requiredgG: 500 A (690 V, 100 kA)
Short-circuit protection / design of the fuse link / for short-circuit protection of the main circuit / with type of coordination 2 requiredgG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415 V, 50 kA)
Short-circuit protection / design of the fuse link / for short-circuit protection of the auxiliary switch requiredgG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions / mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Installation/ mounting/ dimensions / fastening method side-by-side mountingYes
Installation/ mounting/ dimensions / fastening methodscrew fixing
Installation/ mounting/ dimensions / height210 mm
Installation/ mounting/ dimensions / width145 mm
Installation/ mounting/ dimensions / depth202 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards20 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side0 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards20 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards10 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side10 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / forwards20 mm
Installation/ mounting/ dimensions / required spacing / for live parts / upwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / downwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / at the side10 mm
Connections/ Terminals / type of electrical connection / for main current circuitConnection bar
Connections/ Terminals / type of electrical connection / for auxiliary and control circuitscrew-type terminals
Connections/ Terminals / type of electrical connection / at contactor for auxiliary contactsScrew-type terminals
Connections/ Terminals / type of electrical connection / of magnet coilscrew terminal
Connections/ Terminals / width of connection bar25 mm
Connections/ Terminals / thickness of connection bar6 mm
Connections/ Terminals / diameter of holes11 mm
Connections/ Terminals / number of holes1
Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for main contacts2/0 ... 500 kcmil
Connections/ Terminals / connectable conductor cross-section for main contacts / stranded70 ... 240 mm²
Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / solid or stranded0.5 ... 4 mm²
Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / finely stranded with core end processing0.5 ... 2.5 mm²
Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Connections/ Terminals / AWG number as coded connectable conductor cross18 ... 14
Safety related data / product function / mirror contact according to IEC 60947-4-1Yes
Safety related data / product function / positively driven operation according to IEC 60947-5-No
Safety related data / product function / suitable for safety functionYes
Safety related data / suitability for use safety-related switching OFFYes
Safety related data / service life maximum20 a
Safety related data / test wear-related service life necessaryYes
Safety related data / proportion of dangerous failures / with low demand rate according to SN 3192040 %
Safety related data / proportion of dangerous failures / with high demand rate according to SN 3192073 %
Safety related data / B10 value with high demand rate according to SN 319201 000 000
Safety related data / failure rate [FIT] with low demand rate according to SN100 FIT
Safety related data / device type according to ISO 13849-13
Safety related data / overdimensioning according to ISO 13849-2 necessaryYes
Safety related data / safety device type according to IEC 61508-2Type A
Safety related data / protection class IP on the front according to IEC 60529IP00; IP20 with box terminal/cover
Safety related data / touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front with box terminal/cover
Product descriptionpower contactor

Connections and conditions of use

  • General technical data / power loss [W] for rated value of the current / at AC in hot operating state: 54 W
  • General technical data / power loss [W] for rated value of the current / at AC in hot operating state per pole: 18 W
  • General technical data / power loss [W] for rated value of the current / without load current share typical: 7.4 W
  • General technical data / type of calculation of power loss current-dependent: quadratic
  • General technical data / insulation voltage / of main circuit with degree of pollution 3 rated value: 1 000 V
  • General technical data / insulation voltage / of auxiliary circuit with degree of pollution 3 rated value: 500 V
  • General technical data / surge voltage resistance / of main circuit rated value: 8 kV
  • General technical data / surge voltage resistance / of auxiliary circuit rated value: 6 kV

Scope of supply

We will confirm the exact version, package contents and related accessories before ordering. Package information in the technical table applies to the stated order number.

Frequently asked questions

Is the same product family enough to identify a replacement?

The complete order number is essential. If the type changes, compare the electrical and mechanical design, connections and requirements of the original application.

What information is needed to check connections and accessories?

Send a nameplate photo, the designations of related modules and connectors and, where needed, a wiring diagram. We will check the specific version for your application.

Can you assess a faulty part?

Yes. Send the complete order number and a description of the fault. We will check the diagnostic and professional repair options for your specific unit.

Why buy from FOXON

1

Replacement part availability

We will check current part availability and confirm the possible delivery date before you order.

2

New original and refurbished parts

We will specify the available version and condition of the particular unit in the quotation.

3

Parts with a warranty

We will confirm the warranty period according to the part condition and specific quotation.

4

Diagnostics and repairs

For a faulty unit, we will check the options for diagnostics and professional repair.

More than 3,500customers
We deliver tomore than 100 countries
Express delivery?We will check. Contact us now.

Part conditions available for sale

Part conditions and warranty
  • New, sealed (NC): Brand-new, unused part in unopened original packaging. 12-month warranty.
  • New, opened (NO): Brand-new and unused part, but the original packaging has been opened. 12-month warranty.
  • New, without packaging (NW): Brand-new and unused part, supplied without original packaging. 12-month warranty.
  • New (N): New and unused part, typically smaller components supplied in multi-packs in one original package. 12-month warranty.
  • Refurbished (R): Part has been removed from service, cleaned, inspected and tested to meet original functionality and quality. 12-month warranty.
  • Used, tested (T): Functional used part that has passed full testing. 6-month warranty.
  • Used (U): Functional used part. 3-month warranty.

Sales, repairs and buyback of automation parts

We supply replacement parts for industrial automation and assess faulty units for diagnostics and repair. We also buy surplus parts. Send the exact designation and required quantity.

More about parts sales, repairs and buyback

Need to buy or repair this part?

Send the complete order number, quantity and, for repairs, a description of the fault. We will prepare a quotation within 1 hour.

Request a quote for purchase or repair