Ethernet IO remote digital inputs outputs 230V: 1xDI, 1xDO relay, Modbus TCP, REST, MQTT, OPC UA
- Remote inputs outputs
- Digital IO modules 230V
- Ethernet IO remote digital inputs outputs 230V: 1xDI, 1xDO relay, Modbus TCP, REST, MQTT, OPC UA
Ethernet IO remote digital inputs outputs 230V: 1xDI, 1xDO relay, Modbus TCP, REST, MQTT, OPC UA
Industrial module for remote control and monitoring of digital signals 1x DI 230V a 1x DO 230V via TCP/IP Ethernet, OPC UA, Modbus TCP, MQTT, REST or Web server. Alarm system with email notification, automatic control of outputs according to input, power supply 230 VAC, DIN mounting. More
Manufacturer: W&T Code: 57732
Industrial module for remote control and monitoring of digital signals 1x DI 230V a 1x DO 230V via TCP/IP Ethernet, OPC UA, Modbus TCP, MQTT, REST or Web server. Alarm system with email notification, automatic control of outputs according to input, power supply 230 VAC, DIN mounting. More
Manufacturer: W&T Code: 57732
The industrial module with digital inputs and outputs is used for simple remote data acquisition, half-mile counting, signal monitoring, long-distance signal transmission or remote control of various devices. A great advantage is the support of OPC UA and MQTT communication protocols, thanks to which you can control and read inputs and outputs directly from software programs such as OPC Server, SCADA HMI, MES, ERP, cloud applications, etc.
Application areas:
- Remote reading and writing of digital inputs via OPC UA/DA protocol, directly from OPC client, e.g. KEPServerEx Kepware, OPC Router, etc.
- Remote reading and writing of digital outputs via MQTT protocols and REST interface, e.g. OPC Router, cloud systems, etc.
- Wherever it is necessary to read signals and process them directly in the target application, i.e. not to send them first to the PLC and from there to the target application
- When collecting production and process data from the machine, where for some reason it is not possible to read data from the PLC (machine is still under warranty, PLC program is not available, etc.)
- When there is a need to transfer IO data over long distances over Ethernet, because two devices can be interconnected and synchronized with each other
This module includes:
- 1x switching input:
- Digital input, 230V
- 32-bit event counter
- 1x switching output:
- Potential-free output for 230V mains voltage
- Switching currents up to max. 16A
A great advantage is the multitude of communication interfaces and other functions, where configuration is simply set up in the web interface:
- web interface
- control of outputs via web interface
- customised for smartphone
- HTTP or HTTPS
- current Industry 4.0 protocols
- OPC UA, REST and MQTT
- Modbus TCP
- SNMP V1 V2 V3
- Alarm and reporting functions
- Email for sending an alarm or as a status report
- Output switching in alarm situations
- Switching outputs on another web IO
- Up to 30 actions can be configured
- 5 year guarantee
Connections, displays and control elements:
- Digital output:
- 1 x potential-free contact, max. 16A
- Digital input:
- 1 x digital in,
- max. input voltage 250V AC
- Switching threshold 80V
- Integrated 32-bit event counter
- Network:
- 10/100BaseT autosensing
- Power supply:
- 230V AC (approx. 15mA@230V)
- Galvanic isolation:
- Digital output - network: min. 1000 V
- Digital input - network: min 2000 V
- Digital input - output: min. 1000 V
- Adapters:
- 1 x 6x screw terminal for supply and IOs
- 1 x RJ45 for network
- Displays:
- Status LEDs for network
- 2 LEDs for digital states
Data transmission:
- Protocols:
- HTTP and HTTPS
- TCP and UDP sockets, client and server
- MQTT - Publish and Subscribe
- REST
- SNMP V1 V2 V3 including traps
- SMTP e-mail sending
- OPC server
- Modbus TCP
- Inventory keeping, group management
- Response times:
- Data and switching traffic: typically 12 ms
Housing and other data:
- Housing:
- Plastic housing for top hat rail installation
- 90x45x56mm (lxwxh)
- Enclosure rating:
- IP20
- Weight:
- approx. 140 g
- Storage temperature:
- -25°C - 70°C
- Operating temperature:
- 0°C - 40°C
- Permissible relative humidity:
- 5..95% RH (non-condensing)
- Scope of delivery:
- 1 x Web-IO 4.0 Digital, 1x230V In, 1xRelay Out
- 1 x Quick Guide
- Power supply and other accessories can be ordered separately
VIDEO: Easily Collect Machine Data via OPC UA & MQTT
At the beginning of 2024 we introduced a new product from the German manufacturer of industrial modules W&T to the Czech market. Check out our short videos to see how easy it is to set up and use W&T sensors and digital and analogue inputs and outputs for data acquisition using OPC UA and MQTT communications.