- UPS and power supplies
- Power supplies
- Power supply TRIO 1 phase 12VDC, 10A, 120W
Power supply TRIO 1 phase 12VDC, 10A, 120W
Power supply 12VDC with DIN rail mounting is robust, compact and efficient source, specialized on industrial automation systems. Input: 1x phase, output 12V DC, 10A. More
Code: 2866488
Power supply 12VDC with DIN rail mounting is robust, compact and efficient source, specialized on industrial automation systems. Input: 1x phase, output 12V DC, 10A. More
Code: 2866488
TRIO POWER power supplies with standard functionality
TRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.
The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.
- Use the third negative terminal block as a grounding terminal block and minimize installation costs
- Rugged design with metal housing and wide temperature range from -25 to +70°C
- Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to 300 V AC
- Compensation of voltage drops by means of output voltage that can be adjusted on the front
Dimensions
| Width | 40 mm |
| Height | 130 mm |
| Depth | 115 mm |
Ambient conditions
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 55° C derating : 2.5%/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
| Input voltage range | 85 V AC ... 264 V AC (derating < 90 V AC: 2.5 % per Kelvin) |
| Dielectric strength maximum | 300 V AC |
| AC frequency range | 45 Hz ... 65 Hz |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 1.7 A (120 V AC) |
| 0.9 A (230 V AC) | |
| Nominal power consumption | 218.7 VA |
| Inrush current | < 15 A |
| Mains buffering time | > 20 ms (120 V AC) |
| > 86 ms (230 V AC) | |
| Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
| Power factor (cos phi) | 0.63 |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 12 V DC ±1 % |
| Setting range of the output voltage (USet) | 10 V DC ... 18 V DC (> 12 V DC, constant capacity restricted) |
| Nominal output current (IN) | 10 A (-25 °C ... 55 °C) |
| Derating | 55 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback voltage resistance | 25 V DC |
| Protection against overvoltage at the output (OVP) | < 25 V DC |
| Max. capacitive load | unlimited |
| Active current limitation | Approx. 12 A (in the event of a short-circuit) |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 2 % (change in load, dynamic 10 % ... 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 20 mVPP |
| Output power | 120 W |
| Typical response time | < 1 s |
| Peak switching voltages nominal load | < 70 mVPP |
| Maximum power dissipation in no-load condition | 1.1 W |
| Power loss nominal load max. | 18 W |
General
| Net weight | 0.6 kg |
| Operating voltage display | Green LED |
| Efficiency | > 86 % (for 230 V AC and nominal values) |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage input / PE | 2 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage output / PE | 500 V DC (type test) |
| Protection class | I (with PE connection) |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | |
| > 1871000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Connection data, input
| Connection method | Screw connection |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 9 mm |
| Screw thread | M2,5 |
Connection data, output
| Connection method | Screw connection |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 9 mm |
| Screw thread | M2,5 |
EMC data
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Electrostatic discharge | EN 61000-4-2 |
| Contact discharge | 6 kV (Test Level 3) |
| Discharge in air | 8 kV (Test Level 3) |
| Electromagnetic HF field | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Frequency range | 1 GHz ... 2 GHz |
| Test field strength | 10 V/m |
| Frequency range | 2 GHz ... 3 GHz |
| Test field strength | 10 V/m |
| Comments | Criterion A |
| Fast transients (burst) | EN 61000-4-4 |
| Input | 4 kV (Test Level 4 - asymmetrical) |
| Output | 4 kV (Test Level 4 - asymmetrical) |
| Signal | 2 kV (Test Level 3 - asymmetrical) |
| Comments | Criterion A |
| Surge voltage load (surge) | EN 61000-4-5 |
| Input | 2 kV (Test Level 3 - symmetrical) |
| 4 kV (Test Level 4 - asymmetrical) | |
| Output | 1 kV (Test Level 2 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) | |
| Comments | Criterion A |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Voltage dips | EN 61000-4-11 |

Review: How the NODKA UPS Supercapacitor Works – a Test by Jaroslav Blažek
In his review, Jaroslav Blažek (blaja.cz) focused on the UPS Supercapacitor from the manufacturer NODKA. Did it protect a connected device during a power outage as it should have? And for how long did it supply the device with power? Find out in the video below.
Highlighted items are mandatory.