- UPS and power supplies
- UPS 12/24 VDC
- 144 W 24 VDC / 6 A Bicker UPS backup power supply with LiFePO4 battery and USB-C + RS485 Modbus interfaces
144 W 24 VDC / 6 A Bicker UPS backup power supply with LiFePO4 battery and USB-C + RS485 Modbus interfaces
Smart industrial DC UPS backup power supply 24 VDC / 6 A, 144 W, integrated LiFePO4 battery with 33 Wh capacity, configuration via UPScom software, USB-C and RS485 Modbus interfaces, DIN rail mounting. More
Code: UPSI-2406R2DP3MB
Smart industrial DC UPS backup power supply 24 VDC / 6 A, 144 W, integrated LiFePO4 battery with 33 Wh capacity, configuration via UPScom software, USB-C and RS485 Modbus interfaces, DIN rail mounting. More
Code: UPSI-2406R2DP3MB
Bicker UPSI-2406R2DP3MB · intelligent DC UPS
Protect 24VDC devices and data from power outages
Industrial DIN rail backup power supply with 144 W output, integrated 33 Wh LiFePO₄ battery and USB-C / RS485 Modbus communication. It keeps critical loads running and gives the system time to safely shut down.

Need to check the backup time for an IPC, PLC or communication device?
Send us the load power consumption and required backup time; we will help you choose the right backup system and power supply.
Reliable backup for industrial automation
The UPSI-2406R2DP3MB protects control, communication and measurement systems from outages, voltage dips and voltage fluctuations on the 24V supply line. If the power supply fails, the integrated LiFePO₄ battery takes over; switching to backup mode takes less than 600 µs. It is therefore suitable for industrial computers, PLCs, IIoT gateways, network devices, sensors, and measurement, control and safety systems.
Up to 6 A and 144 W for protected 24VDC loads, with regulated output voltage in backup mode.
USB-C (HID-UPS) for IPC and RS485 Modbus RTU for PLC/SCADA. Power Fail relay contact is also available.
The LiFePO₄ battery with BMS, 33 Wh capacity and up to 6 000 cycles is suitable for long-term operation in a control cabinet.

For new control cabinets and modernisation of existing equipment
The UPSI-2406R2DP3MB is a suitable choice for new industrial control cabinets where you want to protect 24V control systems from frequent short outages, voltage dips and supply line fluctuations from the outset.
It helps keep PLCs, computers, PROFINET and Ethernet switches, and other systems running while the rest of the equipment stops safely or a stable power supply is restored. DIN rail mounting makes it easy to integrate into a new project or an existing control cabinet during modernisation.

LiFePO₄: safe energy for years of operation
The integrated LiFePO₄ battery combines stable chemistry with a service life of up to 10 years and up to 6 000 complete charge and discharge cycles. The Battery Management System continuously monitors charging and discharging and protects the battery module in the event of a fault.
Compared to a lead-acid battery, LiFePO₄ offers significantly higher cycle endurance and the full rated capacity can be used. The lower need for maintenance and replacements has a positive impact on the total costs over the life of the device.

Backup time curve by output power
This curve shows the expected backup time of the UPSI-2406R2DP3MB depending on output power. It is a practical aid when designing protection: at lower power, the 33Wh LiFePO₄ battery supplies energy for longer; at higher power, backup time is shorter. The actual value depends on battery condition, ambient temperature and operating conditions.

You can set the UPS parameters from the browser
UPScom software enables online monitoring and configuration of the DC UPS through an intuitive web interface. It displays the charge status and allows parameters to be set without a complicated service intervention.
For normal use, USB-C also works as a standard HID-UPS: supported operating systems recognize it as a UPS or battery without installing a separate driver. If a custom procedure is to be performed before the system shutdown in the event of a power outage, UPScom can control it with a script.
- load sensor in mA and minimum load detection,
- shutdown delay, maximum backup time and minimum charge before startup,
- email notifications in case of loss of connection, power outage or system shutdown,
- controlled shutdown and optional execution of a custom script before the system shutdown.
Safe shutdown and automatic computer restart
After detecting a power outage, the UPS informs the connected system via integrated interfaces. The computer can properly save data and shut down instead of being suddenly disconnected. When input voltage returns, the Reboot function automatically restarts the powered device — especially useful for autonomous systems in hard-to-reach places.
USB-C in HID-UPS mode is recognized by the operating system as a standard UPS without a special driver. RS485 Modbus RTU gives the possibility to read status data and control backup logic directly from PLC or SCADA.

From the manufacturer's manual
Practical features that help in real operation
The UPSI-2406R2DP3MB does more than bridge a power outage with a battery. It continuously evaluates the load, stored energy status and configured shutdown procedure, helping protect data and connected equipment without unnecessary downtime.
The DP3 variant can handle up to 192 W of power for a short time when starting the load. The power reserve is monitored in a time window, so it helps with start-up peaks, but does not represent permanent extra power.
The shutdown logic can be linked to the minimum state of charge, maximum backup time, a time schedule or a drop in load. This gives the control system time to save data, stop the process and only then disconnect the output.
Good airflow and a reasonable depth of discharge benefit the LiFePO₄ battery. Correctly sizing the power to be backed up therefore protects the equipment and also extends battery life.
Immunity and protection functions
The device is designed for demanding industrial operation at temperatures from −20 to +50 °C. It complies with IEC/EN/UL 61010-1 and IEC/EN/UL 61010-2-201; the high-performance LiFePO₄ battery pack has IEC 62133-2 safety certification.
Higher surge immunity helps maintain stable UPS operation even in environments with fast transients and surges on the power line.
Immunity to fast transients according to EN 61000-4-4: 2 kV, criterion A. Surge immunity according to EN 61000-4-5: ±0,5 kV L–N and ±1 kV L–PE/N–PE, criterion A.
Protection against input polarity reversal, overcurrent and output short circuit. BMS monitors the safe operating limits of the battery.
Power-fail timer, Battery Start, minimum load detection and automatic output disconnection protect the battery from deep discharge.
Technical parameters
| Manufacturer's order code | UPSI-2406R2DP3MB |
|---|---|
| Input voltage | 24 VDC, range 23–30 VDC |
| Output | 24 VDC; in normal mode approximately VIN − 0,5 V, regulated to 23,5 VDC in backup mode |
| Output current / power | 6 A / 144 W |
| Battery | LiFePO₄, 2,5 Ah / 33 Wh, integrated BMS |
| Switching time | < 600 µs |
| Communication / signalling | USB-C HID-UPS, RS485 Modbus RTU, potential-free Power Fail relay contact |
| Mounting and degree of protection | DIN rail EN 60715, IP20 |
| Dimensions (W × H × D) | 63 × 120,5 × 105 mm |
| Weight | 0,68 kg (manufacturer's shipping weight 0,702 kg) |
| Operating conditions | −20 to +50 °C; max. 95 % relative humidity without condensation; altitude up to 4 000 m |
About the manufacturer
Bicker Elektronik
Bicker Elektronik is a German manufacturer that has been developing, manufacturing and supplying industrial power supplies, UPS backup systems and system components since 1994.
Its solutions are used in automation, robotics, Industry 4.0 and IIoT, measurement and control technology, medical applications and communication systems. For the UPSI-2406R2DP3MB, this means a focus on long-term operation in a control cabinet, system communication and protection of critical loads.
Frequently Asked Questions
How long can the UPSI-2406R2DP3MB keep a device running during an outage?
Backup time is not fixed. It depends on actual power consumption, temperature, battery condition and the selected settings. The battery has 33 Wh; for accurate sizing, send us the load power consumption and required backup time.
Is it possible to monitor the UPS from a PLC?
Yes. The RS485 interface with Modbus RTU is designed for communication with a PLC or SCADA. The UPS can be connected to an industrial computer as a HID-UPS via USB-C.
What is Battery Start?
The function allows you to manually start the 24V output directly from the battery when it is sufficiently charged, even without the input voltage present.
What happens when current draw is low or the battery discharges?
The UPS can detect a current drop below the set level and disconnect the output after the load has been correctly switched off. At the same time, it protects the battery from deep discharge.
Is LiFePO₄ or a supercapacitor better?
LiFePO₄ makes sense for longer backups. The supercapacitor is especially suitable for short backups and an extremely high number of cycles. The choice is determined by the required operating time in the event of a power outage.
Why buy from FOXON
Does your system require controlled shutdown in the event of a 24 VDC failure?
Send us the power of the protected load, the required backup time and the method of communication. We will suggest a suitable configuration.
Request a solutionUPS configuration via USB
Connect the UPSI-2406R2DP3MB to your computer using a USB cable. In UPS Gen² Configuration, you can configure UPS behaviour and view its operating data. The screenshots below show the individual program tabs.
The UPSI-2406R2DP3MB uses a LiFePO₄ battery. The screenshots show settings and operating data from specific setups; the values are not recommended settings for every application. Click an image to open it separately for a detailed view.
The power and battery overview at the top and the identification bar at the bottom appear in all five screenshots. These are read-only data; settings are changed in the individual tabs.
Common information on all screens
- Input Voltage [V]
- UPS input voltage. This value is available during normal operation from the upstream power supply.
- Output Voltage [V]
- Voltage at the UPS output supplying the connected equipment. It is displayed during both normal and backup operation.
- Output Current [A]
- Current drawn by the equipment connected to the UPS output.
- Runtime to Full [min.]
- Estimated charging time until the battery reaches 100% charge.
- Runtime to Empty [min.]
- Estimated remaining backup time under the current load. This is not a guaranteed operating time.
- Battery Voltage [V]
- Current battery voltage.
- Battery Current [A]
- Battery current. A positive value indicates charging; a negative value indicates discharging.
- State of Charge [%]
- Current battery state of charge, abbreviated SOC. The percentage thresholds for startup and shutdown use this value.
- Battery Temperature [°C]
- Temperature reported by the battery temperature sensor. Availability of this measurement depends on the battery module used.
- Status indicator and UPS OK.
- Indication of the current UPS operating state. The example shows a green indicator and the message UPS OK.
- Program name and version
- The title bar shows the configuration program name and version. The screenshots show UPS Gen² Configuration v2.8.2.
- UPS / Shutdown / Interface / Battery / Info
- Tabs for UPS settings, shutdown conditions, communication interfaces, battery data and device identification. The operating data overview at the top remains the same on all five screens.
- Device identification
- Model reported by the connected UPS. The screenshots show UPSI-2406R2DP3. The full order designation of this product is UPSI-2406R2DP3MB; the MB suffix identifies the RS485 Modbus variant.
- Fw
- Version of the firmware installed in the UPS. The screenshots show 1.7.1. This is different from the version of the program on the computer.
- Hw
- UPS hardware version. All screenshots show 11.4.1.
- Port
- Port used for the USB-C connection between the program and the UPS, here COM7. This is a virtual serial port on the computer, not a device address on the Modbus network.
- Save Parameter
- Function for saving modified parameters to the UPS. The configuration program can be closed after saving. The Save Parameter button is not shown in these screenshots.
- Reset Parameter
- Restores the default parameter values. This is not the button for saving settings normally.
UPS tab settings
- Min. SOC to start-up [%]
- Minimum battery charge required to enable the UPS output. After being switched on or restarted, the UPS waits until the battery reaches the set charge level before allowing power to the load. The screenshot shows 20 %, but the option is not checked.
- Battery Low Threshold [%]
- Low battery charge threshold for relay signalling. The screenshot shows 20 % and the field is inactive. This threshold is used for battery signalling; it is separate from the command to shut down the operating system.
- Restart Delay [sec.]
- Time for which the output remains off during a restart sequence before being switched on again. It provides a defined off period during which capacitances in the connected equipment can discharge. The screenshot shows 10 seconds. Automatic computer startup also requires the appropriate BIOS settings.
- Relay Event / EvId
- Selects the event signalled by the UPS relay contact. EvId means the identifier of the selected event. The screenshot shows the expanded menu; the field at the top does not display a selected event.
Relay Event menu options
- Power Fail - NC
- Input power failure indication with NC contact logic. Verify the actual contact state during normal and backup operation for the R2 firmware used.
- Power Fail - NO
- Input power failure indication with NO contact logic. Verify the actual contact state during normal and backup operation for the R2 firmware used.
- Shutdown Impuls
- A short relay pulse to initiate computer shutdown. The relay is connected in parallel with the computer's power button. The pulse is associated with enabled shutdown by time or SOC.
- Battery Low - NC / Battery Low - NO
- Relay signalling of low charge according to Battery Low Threshold. NC and NO designate different contact logic. The actual contact state when the threshold is reached must be confirmed for the firmware used.
- Battery Defect - NC / Battery Defect - NO
- Relay signalling of a missing or unrecognised energy storage device. The NC and NO variants differ in their contact logic; the exact conditions and contact state must be confirmed for the firmware used.
- Battery Defect & Low - NC / Battery Defect & Low - NO
- Names of options for combined signalling of a battery fault and low charge. The exact combination of trigger conditions and the contact state must be confirmed for the firmware used.
- any fail - NC / any fail - NO
- Options for combined fault indication with NC or NO contact logic. Verify the exact list of included events and the contact state for the R2 firmware used; the name any fail alone does not define them.
NC means Normally Closed; NO means Normally Open. Relay settings depend on the supported UPS hardware and firmware version. Before connecting the relay to a machine control system, we will help verify the required event and the resulting contact logic.
The upper section again displays power supply data, load current, battery charge and temperature; the bottom bar identifies the UPS, firmware, hardware and communication port. The Shutdown tab determines when computer shutdown begins or the UPS output is disconnected.
- Shut Down OS in [sec.]
- Time from the start of backup operation until the command to shut down the operating system is sent. If input power returns sooner, the timed shutdown condition does not take effect. The screenshot shows 60 seconds, but the option is not checked.
- Load Sensor [mA]
- Low load detection. If the load current falls below the set limit during backup operation, the UPS switches off its output and disconnects the energy storage device to limit discharge. In the screenshot, the function is enabled with a threshold of 200 mA.
- Shut Down OS at SOC [%]
- Initiates operating system shutdown when charge falls below the set threshold while the UPS is still running on battery power. The screenshot shows 20 %, but the option is not enabled.
- Power Off UPS at SOC
- Option for switching off the UPS according to its state of charge. It is separate from the Shut Down OS at SOC command. Its exact threshold and interaction with operating system shutdown must be confirmed for the firmware used; the option is not enabled in the screenshot.
- Maximum Backup Time [sec.]
- Maximum permitted backup operating time. When the configured limit expires, the UPS disconnects power to the load. The screenshot shows 60 seconds, but the function is not enabled. The limit does not guarantee that the stored energy will last that long. For a computer, allow enough time for the operating system to shut down completely before disconnecting the output.
- Checkboxes
- Enable or disable the corresponding condition. A number shown in an unchecked field does not by itself mean that the function is active.
Using time and charge thresholds together: if both Shut Down OS in and Shut Down OS at SOC are enabled, whichever condition occurs first triggers shutdown.
Windows settings: for shutdown via USB HID, set the power button action to Shut down. Disable automatic sleep while powered by the UPS; otherwise its low current draw could activate Load Sensor.
In addition to USB-C, the UPSI-2406R2DP3MB has an RS485 interface with Modbus RTU. The configuration program connects via USB; this tab configures communication with a PLC or another Modbus client. The values in the screenshot are examples, not universal settings for every network.
- Additional Com-Module
- Type of additional communication interface. The screenshot shows RS-485 (Modbus), matching the MB variant of this product.
- RS-485 (Modbus)
- Serial link for Modbus RTU communication, for example with a PLC or SCADA system. This is neither an RS232 interface nor Modbus TCP over Ethernet.
- Baudrate
- RS485 line transmission rate. The screenshot shows 19200 baud. The rate must match the settings of the other devices on the same line.
- Device Address
- Device address on the Modbus network. The screenshot shows 11. The client must use the same address, and individual devices on the line must have different addresses. This is not the USB port number COM7.
- Byte Order
- Byte order used when transferring data. The screenshot shows Big Endian, meaning the most significant byte is sent first. The setting must match how the client processes data; this option alone does not define the register map or the order of multiple registers within a value.
- Line Termination 120 Ohm
- Option for terminating the RS485 line with a 120 Ω resistor. It is unchecked in the screenshot. Termination is used at both ends of the main line, not automatically at every device; it depends on the actual bus wiring.
- Modbus Protocol over USB
- Option for selecting Modbus communication over USB. It is inactive and unchecked in the screenshot. This example does not confirm that the mode is available for the firmware used; support must be verified before use.
- Port COM7
- Virtual serial port used for the USB-C connection between the configuration program and the UPS. It is independent of the Modbus device address and is not a device number on the RS485 line.
This tab displays identification and operating data reported by the battery module. It is not a form for changing the battery type or capacity. The upper overview continues to show its instantaneous voltage, current, charge and temperature.
- Battery Name
- Designation of the connected battery module. The example shows BP-LFP-1325S, the LiFePO₄ battery used in the UPSI-2406R2DP3MB.
- Serial Number
- Serial number reported by the battery. The screenshot shows 2530B0230060. It identifies the battery module, not the UPS itself; the UPS serial number is on the Info tab.
- Battery Chemistry
- Battery chemistry. The abbreviation LFP in the example denotes LiFePO₄, or lithium iron phosphate.
- Version
- Version reported by the battery module, here 3. This is neither the configuration program version nor the firmware version of the entire UPS.
- Operating Time
- Displayed operating time counter in days, hours and minutes; the example shows 0 Days, 00:07. This value alone does not establish the battery's manufacturing date or age.
- Nominal Voltage [mV]
- Nominal voltage reported by the battery module in millivolts. It is separate from the instantaneous Battery Voltage shown in the upper overview.
- Nominal Capacity [mAh]
- Nominal capacity reported by the battery module in milliampere-hours; the example shows 2200 mAh. This is neither the current charge percentage nor the backup time. When designing a backup system, use the specifications of the supplied battery and the actual load rather than this example value alone.
- Number of Cycles [Cycles]
- Number of full charge and discharge cycles reported by the battery. The screenshot shows 0. Availability and interpretation of the counter depend on battery module and firmware support; zero alone does not confirm that the battery is new or establish its remaining service life.
- Avg. Temperature [°C]
- Average temperature reported in the battery overview. It is different from the instantaneous Battery Temperature at the top of the window.
- State of Health [%]
- Battery health indicator, abbreviated SOH. Do not confuse it with SOC, the current state of charge. SOH support must be confirmed for the specific battery module and firmware; a displayed value of 100 % alone does not confirm a measured remaining battery capacity.
The values in the screenshot relate to one specific connected setup. When designing a backup system, use the specifications of the supplied model and battery rather than the figures in this program example.
This tab summarises the information needed for device identification, version checks and technical support. The upper section displays the same power supply and battery operating data as the previous screens.
- Device Name
- Model reported by the UPS in the program, here UPSI-2406R2DP3. The order designation of this product is UPSI-2406R2DP3MB, the variant with an RS485 Modbus interface.
- Serial Number
- Serial number of the UPS itself, used to identify the individual unit for technical support or servicing.
- Hardware Version
- UPS hardware version, 11.4.1 in all screenshots. The same value appears as Hw in the bottom bar.
- Firmware Version
- UPS internal firmware version, here 1.7.1. The same value appears as Fw in the bottom bar. This is not the version of the configuration program on the computer. Any update must be selected for the exact UPS model and hardware version.
- CPU Temperature [°C]
- Temperature of the processor in the UPS control electronics. This is neither the battery temperature nor the temperature of the connected computer.
- Bottom bar and Reset Parameter
- The model, Fw, Hw and Port repeat the identification and connection information. Reset Parameter restores the default UPS parameters; its meaning remains the same when switching tabs.
Schedule an online meeting
Need to quickly discuss backup time, wiring or UPS communication? Choose a time for a short online consultation directly in the calendar below.
Technical parameters
Basic features
- Device type: intelligent DC UPS module for 24 V systems
- Input voltage: 24 VDC (range 23–30 V)
- Output voltage: normal mode ≈ VIN − 0.5 V / backup mode 23.5 VDC regulated
- Output current: 6 A nominal
- Power: 144 W
- Battery technology: LiFePO4
- Mounting: on DIN rail according to EN 60715
Backup and battery
- Battery capacity: 2.5 Ah / 33 Wh
- Battery lifetime: up to 6000 charge and discharge cycles
- Battery management system (BMS): integrated
- Charging method: CC / CV / CP
Output and power
- Switching time: <600 µs
- Capacitive load: max. 3000 µF (in normal mode, during start-up, load 0 A)
Input parameters and power supply
- Max. input current: 6.2 A
Communication and signalling
- Communication interfaces: USB-C (HID-UPS), RS-485 (Modbus RTU)
- Signalling: potential-free relay contact for Power Fail
Functions and protections
- Functions: intelligent input power control (Power Sharing), minimum load detection, timer on power failure, controlled system shutdown, automatic device restart, battery charge status indication
- Protections: protection against input polarity reversal, overcurrent and output short circuit
Operating conditions
- Operating temperature: −20 to +50 °C
- Storage temperature: −30 to +55 °C
- Max. humidity: ≤95%, non-condensing
- Max. altitude: 4000 m
Mechanical design
- Protection rating: IP20
- Dimensions (W x H x D): 63 x 120.5 x 105 mm
- Weight: 0.68 kg
Frequently Asked Questions about the Bicker UPSI-2406R2DP3MB DC UPS with LiFePO4 battery
What is UPSI-2406R2DP3MB?
The UPSI-2406R2DP3MB is an intelligent DC UPS module for 24 V industrial systems with an integrated LiFePO4 battery (33 Wh), designed to ensure uninterrupted power supply during outages or voltage fluctuations.
How does a DC UPS work in an industrial system?
The UPS is installed between the power supply and the protected device. In normal operation, it passes the input voltage to the output and charges the battery. In case of power failure, it automatically switches to backup mode and supplies power from the battery.
What is the difference between UPSI-2406R2DP3MB and UPSI-2406R2DP2MB?
The UPSI-2406R2DP3MB model uses a LiFePO4 battery, which provides a significantly longer backup time and is suitable for applications where devices need to remain operational for extended periods. The UPSI-2406R2DP2MB variant uses supercapacitors with an extremely long service life of up to 500,000 cycles and very fast charging, but is intended only for short backup durations in the range of seconds.
What is the output voltage during a power failure?
In backup mode, the UPS provides a regulated output voltage of 23.5 VDC, ensuring stable power supply even during battery discharge.
How long can the UPS power the device?
The backup time depends on the load. At full load (6 A), the typical backup time is approximately 11 minutes (depending on conditions). At lower loads, it can be significantly longer.
What is the battery capacity and type?
The UPS includes an integrated LiFePO4 battery with a capacity of 2.5 Ah (33 Wh), known for its high safety and long lifespan.
What is the battery lifetime?
The LiFePO4 battery can achieve up to 6,000 charge cycles depending on operating conditions.
How fast does the UPS switch during a power failure?
The transfer from normal to backup mode is very fast, typically within 600 µs, so connected devices usually do not detect the interruption.
How can the UPS be monitored or configured?
The UPS can be connected via USB-C (HID-UPS) or RS-485 using Modbus RTU. Advanced configuration and monitoring are available via UPScom software.
What does HID-UPS mode mean?
In HID-UPS mode, the device is recognized by the operating system as a standard UPS without the need for additional drivers, enabling automatic power management and safe system shutdown.
How does the UPS signal a power failure?
The UPS signals its status via a potential-free relay contact (power fail) and diagnostic information available through communication interfaces.
What is the Power Sharing function?
Power Sharing ensures intelligent distribution of input power between the load and battery charging, eliminating the need to oversize the power supply.
What does minimum load detection mean?
The UPS can detect when the load drops below a defined threshold and automatically switch off the output, for example after a controlled system shutdown.
What is the Battery Start function?
Battery Start allows the UPS output to be activated directly from the battery even without input power (only if the battery is sufficiently charged).
What is the power-fail timer?
The power-fail timer allows you to define a delay before initiating a controlled shutdown of connected devices after a power failure.
What happens when the battery is fully discharged?
The UPS protects the battery against deep discharge. Once the minimum level or maximum backup time is reached, the output is automatically disconnected to protect the battery.
How does the UPS behave at low temperatures?
At low temperatures, the available battery capacity may decrease and charging time may increase, which is a typical characteristic of LiFePO4 technology.
What applications is UPSI-2406R2DP3MB suitable for?
The UPS is suitable for industrial PCs (IPC), PLC systems, communication devices, IIoT gateways, SCADA systems, and other applications where power continuity and data protection are critical.

Bicker Review: Jarda Blažek compared 2 smart UPS units with a supercapacitor and a battery
Smart industrial backup power supplies from Bicker protect your production systems and industrial PCs against unexpected power outages, voltage drops, and fluctuations. Jarda Blažek (blaja.cz) investigated the practical differences between UPS units with an integrated supercapacitor and those with a LiFePO4 battery.