6ES7623-1AE01-5AA0 – SIEMENS – batteries for HMI, C7 and PG
The 6ES7623-1AE01-5AA0 lithium battery is an accessory for SIMATIC HMI, C7, S7 and PG. It has a voltage of 3.6 V and a capacity of 1.6 Ah; it is a non-rechargeable battery.
Need to confirm the correct battery configuration?
Please send a photograph of the battery, the connector and the device label. We will confirm availability and the delivery date.
Battery application
It is designed for selected panels, such as the TD17, OP17, OP25, OP27, OP35, OP37, TP27, TP37, OP/TP270, MP270, MP270B and MP370, as well as the C7 and PG 7xx variants listed below. Please check the appropriate connections for your specific device.
Technical specifications
| Order number | 6ES7623-1AE01-5AA0 |
|---|---|
| Voltage / capacity | 3.6 V / 1.6 Ah |
| Charging | No |
| Cell type | SL-361; size 2/3 AA |
| Cell length × diameter | 33 × 14.7 mm |
| Weight without / with packaging | 14 / 16 g |
| Operating temperature | 0 to +55 °C |
Configuration and replacement selection
Check the connections and ensure the cable is of the required length. Batteries for HMIs are not automatically interchangeable with the Mobile Panel’s main rechargeable battery. We will confirm the range of cable accessories for the specific delivery.
Scope of delivery
One lithium battery, a connection cable, an extension cable and two cable ties. We will confirm the length of the connection cable in the quotation.
Frequently asked questions about batteries
What is the purpose of the backup battery in an HMI panel?
Depending on the panel design, it ensures that the real-time clock continues to run or that selected data is retained when the power supply is disconnected. The battery does not power the display or the panel’s normal operation. Please check the exact scope of the backup function for the specific panel order number.
How often should the battery be replaced?
Adhere to the preventive replacement interval specified by the manufacturer of the specific equipment. Service life is influenced by the current draw of the circuits being backed up, the duration without mains power, temperature and the age of the battery. Record the date of installation and include the replacement in the maintenance schedule. Capacity figures alone do not determine the number of years of operation; there is no universal replacement interval applicable to all devices.
How do I recognise a low or faulty battery?
Depending on the type of control unit, the fault will be indicated by an indicator light, a diagnostic message or a status displayed in the programming software. Check the exact meaning of the message for the specific device: the cause may also be a missing battery or a connection problem. The message does not reliably indicate the remaining backup time. First ensure that data is backed up and resolve the fault before the planned power cut.
What happens if I do not replace a depleted battery?
Disconnecting the mains supply may cause the clock to stop or result in the loss of battery-dependent data. A non-volatile project will not be erased simply by the battery discharging. During maintenance, check the date and time, diagnostics and any data that the specific panel backs up.
How do winter conditions and low temperatures affect the battery?
In lithium cells, internal resistance increases as the temperature drops, and both voltage and usable capacity decrease during discharge. The actual temperature of the battery inside the device is the decisive factor. Cold temperatures therefore limit the backup capacity, particularly in older batteries. At the same time, observe the temperature limits for the cell, the entire battery pack and the device; a wide operating range for the cell itself does not imply the same resilience for the entire device.
Does high temperature shorten battery life?
Yes. In lithium backup cells, high temperature accelerates self-discharge and affects their ability to supply the required current. When planning maintenance, take account of the temperature inside the control cabinet and the storage conditions for spare batteries. Nominal capacity measured at room temperature does not guarantee the same service life in a hot control cabinet.
Is the battery replaced whilst the device is switched on or off?
The procedure is specified by the manufacturer of the specific control unit. For some battery-backed devices, the mains power supply must remain switched on during replacement to prevent data loss. This procedure cannot be applied to all control units. Before disconnecting the battery, check the specified power supply status, the control unit’s operating mode and the machine’s service conditions.
What should be checked before and after replacement?
Before replacement, check the availability of a suitable programme backup and the necessary data, as well as the new battery’s designation, connector and polarity. Record the diagnostic status and prepare the intervention in accordance with the equipment’s service procedure. After replacement, check the battery indicators, diagnostics and the required status of the control unit. If the clock or operating values are backed up, check these as well. Record the date and type of the installed battery in the maintenance log.
Is the same voltage enough when selecting a replacement?
No. Also compare the chemical system, dimensions, capacity required for the specific device, connector, wiring configuration and polarity. A connector that is the same but with a different wiring configuration is not a suitable replacement. Do not replace a battery with a cable connection with a loose cell without verifying the entire design.
Can I determine the remaining service life by measuring voltage?
Open-circuit voltage alone does not determine remaining capacity. In Li-SOCl₂ cells, voltage changes very little through much of the discharge; temperature and load also affect the result. Use device diagnostics and the battery manufacturer’s procedure to assess its condition. An open-circuit measurement does not replace preventive replacement.
How should a spare primary lithium battery be stored?
Store it in its packaging, in a dry and cool place in accordance with the manufacturer’s instructions. Protect the connector and terminals from short-circuiting and check the battery’s markings and age. A primary lithium battery is not rechargeable: do not connect it to a charger, do not short-circuit it and do not solder directly onto the cell body. The required terminals must be of a suitable, ready-made design.
Why buy a backup battery from FOXON?
Batteries for industrial equipment in one place
In one e-shop, we offer backup batteries for well-known PLCs, HMI panels, robots and other industrial equipment. Order batteries for different machines from one supplier, without searching several e-shops.
Standard batteries and custom assemblies
We supply standard batteries and custom assemblies. If you cannot find the battery in our e-shop, send a photo of the original battery or its order number. We will clarify the required specifications and arrange production of the appropriate configuration.
Help with selecting a replacement
We compare the battery designation, electrical specifications, dimensions, connector and polarity. Using a photo of the battery and device nameplate, we help identify the configuration required.
Availability and delivery date
We check current battery availability and confirm the expected delivery date before you place an order.
Battery versions available for purchase
Request a new battery in the appropriate configuration. We will check any compatible replacement separately against your device.
Automation spare parts and repairs
Do you also need a PLC, HMI panel or drive component for the same machine? FOXON supplies spare parts and arranges repairs of industrial electronics. Sales and repairs of automation parts.
Send us the battery designation
Please provide the quantity, a photograph of the connector and a photograph of the device label. We will verify the model, price and availability.
Request a battery or confirm the configurationHighlighted items are mandatory.