Converter EtherCAT Slave / CAN - HD67E07-A1

Converter EtherCAT Slave / CAN - HD67E07-A1


ADFweb

The ADFweb HD67E07-A1 connects CAN devices to an EtherCAT control system. It operates as an EtherCAT Slave and transfers configured values between process data and CAN messages. More

Code: HD67E07-A1

399 EUR excl. VAT (482,79 EUR Incl. VAT)
Delivery 3-8 days
pcs
(0 pcs In stock)

Rezervace termínu

Get a quote
ADFweb

The ADFweb HD67E07-A1 connects CAN devices to an EtherCAT control system. It operates as an EtherCAT Slave and transfers configured values between process data and CAN messages. More

Code: HD67E07-A1

ADFweb HD67E07-A1

EtherCAT Slave / CAN

The ADFweb HD67E07-A1 connects CAN devices to an EtherCAT control system. It operates as an EtherCAT Slave and transfers configured values between process data and CAN messages.

We will check your selection and prepare a quotation
Send us the device models, required connection and quantity.

Request the converter
EtherCAT Slave / CANProtocol connection
35 mm DIN railHardware version
SW67E07Configuration tool

Converter applications

Use it to integrate CAN communication devices into an EtherCAT Master project. Map received and transmitted CAN messages to EtherCAT variables using message identifiers and the meaning of the data bytes.

Technical specifications HD67E07-A1

Order codeHD67E07-A1
Protocol connectionEtherCAT Slave / CAN
Converter rolesEtherCAT Slave; CAN
Interfaces and ports2× EtherCAT RJ45 (IN/OUT); CAN; Ethernet RJ45 for configuration
CAN data rateup to 1 Mbit/s
Power supply8-24 V AC / 12-35 V DC
Consumption at 24 V DC3.5 W
Operating temperature-40 °C to +85 °C
Mounting35 mm DIN rail
Dimensions of the version shown (D × W × H)120 × 23 × 107 mm
Device weightapproximately 200 g
Configuration softwareSW67E07

For an older device, check the hardware version and connections against its label.

Communication and configuration

In SW67E07, configure EtherCAT, the CAN data rate and messages for both transfer directions. Define data mapping and export an ESI file for the EtherCAT Master.

This model is intended for CAN. Select the HD67E08-A1 version for CANopen. The Ethernet port is used for configuration and updates; distinguish it from the EtherCAT IN/OUT pair.

Supply and accessories

Please provide the complete order code. If you need a power supply, connection cables or help with configuration, include them in your enquiry. We will confirm the scope of supply and required accessories for your installation in the quotation.

Documentation and software

Diagrams and hardware version

Dimensional drawing of the version shown - HD67E07-A1
Dimensional drawing of the version shown - HD67E07-A1

The images help identify the hardware version. When replacing an older unit, compare its label, connectors and dimensions; we will confirm the version to be supplied in the quotation.

Frequently asked questions

Is knowing the two protocols enough?

The device roles, physical interfaces and data to be transferred must also be checked. This model is intended for CAN. Select the HD67E08-A1 version for CANopen. The Ethernet port is used for configuration and updates; distinguish it from the EtherCAT IN/OUT pair.

How is this converter configured?

In SW67E07, configure EtherCAT, the CAN data rate and messages for both transfer directions. Define data mapping and export an ESI file for the EtherCAT Master.

What information should I send to check the selection?

Send the exact device models at both ends, the protocols and communication roles, the number of devices and the required values. For a PLC, include the firmware and method of accessing its data.

FOXON support with selection and ordering

Selection based on your devices

We will review the specific connection, communication roles and required data.

Availability check

Before you place an order, we will confirm current availability and the possible delivery date.

Documentation for the exact order code

We select the documentation and configuration tool using the complete order code.

Accessories for your installation

We will include the requested accessories in the quotation to suit the connection arrangement.

Choosing the correct version

Two devices with the same protocols can have different functions. Check the gateway role on each side, the connectors and the complete order code.

This model is intended for CAN. Select the HD67E08-A1 version for CANopen. The Ethernet port is used for configuration and updates; distinguish it from the EtherCAT IN/OUT pair.

Converter enquiry HD67E07-A1

Provide the order code, quantity and the devices you need to connect. We will check the suitable version and prepare a quotation.

Request the converter

Technical specifications HD67E07-A1

Order codeHD67E07-A1
Protocol connectionEtherCAT Slave / CAN
Converter rolesEtherCAT Slave; CAN
Interfaces and ports2× EtherCAT RJ45 (IN/OUT); CAN; Ethernet RJ45 for configuration
CAN data rateup to 1 Mbit/s
Power supply8-24 V AC / 12-35 V DC
Consumption at 24 V DC3.5 W
Operating temperature-40 °C to +85 °C
Mounting35 mm DIN rail
Dimensions of the version shown (D × W × H)120 × 23 × 107 mm
Device weightapproximately 200 g
Configuration softwareSW67E07

For an older device, check the hardware version and connections against its label.