- Machine data collection
- OPC UA / MQTT Sensors
- Ethernet Thermometer 2x Pt100/Pt1000 sensors via terminal block, Modbus TCP, REST, MQTT, OPC UA
Ethernet Thermometer 2x Pt100/Pt1000 sensors via terminal block, Modbus TCP, REST, MQTT, OPC UA
Industrial module for remote monitoring and data acquisition of two temperatures, measured via 2x independent Pt100 W&T sensors -50C...180C, via measuring input with range -200C...650C each. Sensor connection via 8-pin terminal block, cable length 2m, can be extended. Temperature data is also provided via OPC UA/DA, REST, MQTT, Modbus TCP or Web Server. Built-in data logger for archiving data to FTP, Excel, ODBC, W&T cloud or custom memory with min 16 weeks and max 20 years, storage in 15,30sec or 1,5,15,60min increments. Alarm system with email notification, automatic control of outputs according to input. Data readout after 4sec, power supply 12-48VDC or PoE, DIN mounting. More
Code: 57707
Industrial module for remote monitoring and data acquisition of two temperatures, measured via 2x independent Pt100 W&T sensors -50C...180C, via measuring input with range -200C...650C each. Sensor connection via 8-pin terminal block, cable length 2m, can be extended. Temperature data is also provided via OPC UA/DA, REST, MQTT, Modbus TCP or Web Server. Built-in data logger for archiving data to FTP, Excel, ODBC, W&T cloud or custom memory with min 16 weeks and max 20 years, storage in 15,30sec or 1,5,15,60min increments. Alarm system with email notification, automatic control of outputs according to input. Data readout after 4sec, power supply 12-48VDC or PoE, DIN mounting. More
Code: 57707
Temperature measurement via Ethernet: 2× Pt100/Pt1000
The W&T 57707 connects Pt100 or Pt1000 resistance temperature sensors to an Ethernet network. It displays the temperature in a web browser, stores historical data and provides measured data via OPC UA, MQTT, REST or Modbus TCP.
Do you need to select or order the W&T 57707?
Please send us the required quantity and a description of the wiring configuration. We will check availability and suitable accessories.
Successor model
W&T lists the successor model 57107 for this product. The specifications on this page relate to the original order number 57707. Before selecting a replacement, we will verify the wiring, functions and suitability for the specific application.
Usage
It is used to monitor temperatures in technical rooms, switchboards and industrial equipment. The web-based display of data trends and customisable alerts facilitate long-term monitoring without the need for a separate computer to carry out the measurements.
Technical specifications for the W&T 57707
| Temperature sensor | 2x Pt100/Pt1000 measurement inputs W&T probe cable: 2 m, can be extended depending on the connection Probe protection rating: IP67 |
|---|---|
| Temperature input connection | 8-pin terminal block Conductor cross-sectional area 0.2–1.3 mm² Length of stripped section: 6–8 mm |
| Network interface | 10/100BaseT, auto-detection / Auto-MDIX RJ45 IPv6 on request |
| Galvanic isolation | Network interface section: min. 1500 V |
| Power supply | Power-over-Ethernet (PoE) or 12–48 V DC (±10 %) |
| Current consumption | PoE Class 1 (0.44–3.84 W) typ. 70 mA at 24 V DC with an external power supply |
| Signalling | 1 Power LED 2× network status LEDs 4 LEDs for status and faults |
| Sensor | 2× Pt100/Pt1000 connections: two-wire, three-wire or four-wire |
| Measuring range | W&T sensor: -50 °C to 180 °C PT100/PT1000 measurement input: -200 °C to 650 °C |
| Resolution | 1/10 °C |
| Measurement unit error | ±0.3 °C, ±0.2 % |
| Class A Pt100/Pt1000 sensor error | ±0.15 °C, ±0.2 % |
| Measurement period | 4 seconds |
| Save interval | 15 s, 30 s, 1 min, 5 min, 15 min, 60 min |
| History capacity (4 MB memory) | min. 4 weeks, max. 20 years |
| Housing and mounting | Compact plastic housing for DIN rail mounting 105 × 22 × 75 mm (length × width × height) |
| Degree of protection | IP20 |
| Weight | approx. 200 g |
| Ambient temperature | Storage: -40 to +70 °C Operating temperature with spacing between devices: 0 to +60 °C Operating temperature when installed side by side without spacing: 0 to +50 °C |
| Permissible relative humidity | 0 to 95 per cent RH, non-condensing |
| Contents of the delivery | 1x web thermometer 2x 1x Pt100 sensor, 2 m, IP67 1× quick start guide |
Sensors, ranges and temperature recording
- Two measurement inputs on the terminal block. The standard supply includes one Pt100 sensor with a 2 m cable and IP67 protection; a sensor must be ordered separately to use the second input.
- The measurement input covers -200 to +650 °C. The supplied W&T sensor is rated for -50 to +180 °C. The usable range of the entire measurement is limited by the specific sensor and its design.
- Two-wire, three-wire and four-wire Pt100/Pt1000 connections are supported. The selected sensor type and number of wires must correspond to the input settings and wiring.
- The resolution is 0.1 °C and measurements are updated every 4 seconds. The recording interval can be selected independently: 15 or 30 seconds, or 1, 5, 15 or 60 minutes.
- Up to 12 customisable alerts are available, along with email, SNMP and other network services. The length of the history retained depends on the number of measured channels and the set interval.
Commissioning and accessories
Select sensors according to the required temperature and environment. Check the wiring, shield connection and Pt100/Pt1000 settings. After setting the IP address, select the units, logging interval and alarm limits. The IP20 rating specified applies to the network module itself, not automatically to the probe.
Contents of the delivery
- 1x web thermometer 2x
- 1x Pt100 sensor, 2 m, IP67
- 1× quick start guide
Frequently Asked Questions
Does the supplied sensor measure the full range from -200 to +650 °C?
No. This range applies to the measurement input. The supplied W&T sensor has a range of -50 to +180 °C. A suitable, compatible sensor is required for a different range.
How many sensors are included in the delivery?
Two measurement inputs on the terminal block. The standard supply includes one Pt100 sensor with a 2 m cable and IP67 protection; a sensor must be ordered separately to use the second input.
Is resolution the same as accuracy?
No. A resolution of 0.1 °C determines the smallest displayed increment. The total measurement error includes the unit of measurement, the sensor and the effect of the wiring; the individual values are listed in the technical table.
Why order from FOXON?
Before placing an order, we will check the current availability of the part and confirm the estimated delivery date. We will assist you in selecting the equipment and necessary accessories based on the wiring configuration and required communication. We will confirm the warranty terms and the scope of any diagnostics or repairs for the specific quotation.
Documentation and technical consultancy
Technical data and documentation for W&T 57707
Manuals, firmware and tools for this model can also be found in the Downloads tab. For service enquiries, please use sale and repair of FOXON industrial parts.
Do you need to select or order the W&T 57707?
Please send us the required quantity and a description of the wiring configuration. We will check availability and suitable accessories.
Diagrams and illustrations

Further related links
Technical specifications for the W&T 57707
| Temperature sensor | 2x Pt100/Pt1000 measurement inputs W&T probe cable: 2 m, can be extended depending on the connection Probe protection rating: IP67 |
|---|---|
| Temperature input connection | 8-pin terminal block Conductor cross-sectional area 0.2–1.3 mm² Length of stripped section: 6–8 mm |
| Network interface | 10/100BaseT, auto-detection / Auto-MDIX RJ45 IPv6 on request |
| Galvanic isolation | Network interface section: min. 1500 V |
| Power supply | Power-over-Ethernet (PoE) or 12–48 V DC (±10 %) |
| Current consumption | PoE Class 1 (0.44–3.84 W) typ. 70 mA at 24 V DC with an external power supply |
| Signalling | 1 Power LED 2× network status LEDs 4 LEDs for status and faults |
| Sensor | 2× Pt100/Pt1000 connections: two-wire, three-wire or four-wire |
| Measuring range | W&T sensor: -50 °C to 180 °C PT100/PT1000 measurement input: -200 °C to 650 °C |
| Resolution | 1/10 °C |
| Measurement unit error | ±0.3 °C, ±0.2 % |
| Class A Pt100/Pt1000 sensor error | ±0.15 °C, ±0.2 % |
| Measurement period | 4 seconds |
| Save interval | 15 s, 30 s, 1 min, 5 min, 15 min, 60 min |
| History capacity (4 MB memory) | min. 4 weeks, max. 20 years |
| Housing and mounting | Compact plastic housing for DIN rail mounting 105 × 22 × 75 mm (length × width × height) |
| Degree of protection | IP20 |
| Weight | approx. 200 g |
| Ambient temperature | Storage: -40 to +70 °C Operating temperature with spacing between devices: 0 to +60 °C Operating temperature when installed side by side without spacing: 0 to +50 °C |
| Permissible relative humidity | 0 to 95 per cent RH, non-condensing |
| Contents of the delivery | 1x web thermometer 2x 1x Pt100 sensor, 2 m, IP67 1× quick start guide |

VIDEO: Easily Collect Machine Data via OPC UA & MQTT
At the beginning of 2024 we introduced a new product from the German manufacturer of industrial modules W&T to the Czech market. Check out our short videos to see how easy it is to set up and use W&T sensors and digital and analogue inputs and outputs for data acquisition using OPC UA and MQTT communications.
Highlighted items are mandatory.